Property Inspection Report
Client(s): Billy Miller
Property address: 991 Elkins Road
Cairo, Ga 39828
Inspection date: 5/27/2010
This report published on Friday, May 28, 2010 12:08:33 AM EDT

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Crawl space
Well
Kitchen
Bathrooms
Interior rooms
General information
 
Exterior Return to table of contents
Footing material: Masonry
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Brick veneer
Driveway material: Gravel
Sidewalk material: None
Exterior door material: Solid core wood
1) One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.

1. Both receptacles on east wall in laundry room have this situation

2) One or more electric receptacles have burn or scorch marks on them. Receptacle(s) and/or wiring to them may be damaged. A qualified electrician should evaluate and make repairs as necessary, such as replacing damaged receptacles and/or wiring.

1. Receptacle in living room has scorch marks.

3) One or more outdoor electric receptacles appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all outdoor receptacles within six feet six inches of ground level have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
4) Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

Photo 14  
Wiring connected outside of junction box.

Photo 15  
Wiring connected outside junction box #2

5) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

Photo 12  
Electrical junction box with no cover

Photo 13  
Electrical junction box with no cover.

6) One or more hornet, bee and/or wasp nests were found. These can pose a safety hazard. Nest(s) should be removed as necessary.
7) Siding is damaged and/or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs and/or replace siding as necessary to prevent water and vermin intrusion.

Photo 1  
Vinyl siding coming out of J-channel

Photo 6  
Hole in vinyl around bottom of sunroom

Photo 11  
Soffit and facia trim not installed correctly
 

8) One or more electric receptacles appear to have no power. Recommend asking the property owner(s) about this. Switches may need to be operated to make some receptacles energized. If necessary, a qualified electrician should evaluate and make repairs as necessary.


1. Receptacles on south wall of living room have this sitituation

9) One or more light fixtures are damaged and/or deteriorated. A qualified electrician should evaluate and repair or replace light fixtures where necessary.

Photo 18  
Cracked lens cover over photo cell on flood light.
 

10) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
 
Roof Return to table of contents
Roof inspection method: Traversed
Roof type: Gable
Roof covering: Asphalt or fiberglass composition shingles
Roof ventilation: Adequate
11) One or more sections of flashing at the base of the chimney are deteriorated and/or substandard. Leaks may occur as a result. A qualified roofing contractor should evaluate and repair as necessary.

Photo 9  
Flashing rusting out
 

12) One or more "rubber boot" flashings are damaged or deteriorated and may result in leaks or vermin intrusion. A qualified contractor should replace flashings where necessary.

Photo 10  
Cracked boot around vent pipe on roof.
 
 
Garage Return to table of contents

13) The pull-down attic stairs in the attached garage ceiling aren't fire-rated. This ceiling should have a one-hour fire rating to slow or prevent the spread of fire from the attached garage to attic spaces above the living areas. A qualified contractor should evaluate and make modifications to these stairs as necessary so they have a one hour fire rating. Other options include removing them or replacing them with commercially made, fire-rated stairs. Examples of possible solutions include:

  • Installing 5/8 inch Type X sheetrock on the lower surface of the stair door and eliminating gaps around the edges of the door.
  • Removing the stairs and installing a traditional hatch made with 5/8 inch Type X sheetrock.
  • Installing a Battic Door and installing sheetrock over it as described at their website.
  • Replacing these stairs with fire-rated stairs such as those from:
    http://www.calvertusa.com/
     
    Attic Return to table of contents
    Inspection method: Traversed
    Roof structure type: Rafters
    Ceiling structure: Ceiling beams
    Insulation material: Fiberglass roll or batt
    Insulation depth: 10-1/2"
    Insulation estimated R value: R30
    14) Some wiring is loose, unsupported, or inadequately supported. Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.

    1. Wiring entering the box for the attic light switch is missing a romex connector

    Photo 16  
    No romex connector on box powering attic lighting
     

    15) The attic exhaust fan was inoperable during the inspection. Recommend consulting with the property owner(s) as to how it operates and/or having a qualified contractor evaluate and repair if necessary.
    16) Pull-down stairs are installed for the attic access. No insulation is installed above the stairs and no weatherstripping is installed around the hatch perimeter. To reduce air leakage, recommend installing weatherstripping and an insulated hatch cover. An example of one can be seen at http://www.batticdoor.com/

    Interior air leaking into the attic results in heating and cooling losses, increased energy costs, and a possible increase in moisture levels in the attic due condensation forming on the underside of the roof sheathing during cold weather.
     
    Electric service Return to table of contents
    Primary service type: Overhead
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120/240
    Location of main service switch: Luandry Room
    Location of sub panels: Laundry Room
    Location of main disconnect: Breaker at top of main service panel
    Service entrance conductor material: Aluminum
    System ground: Ground rod(s) in soil
    Main disconnect rating (amps): 200
    Branch circuit wiring type: Copper
    Solid strand aluminum branch circuit wiring present: Yes
    Smoke detectors present: No
    17) The legend for overcurrent protection devices (breakers or fuses) in the main service panel is missing, unreadable or incomplete. Recommend installing, updating or correcting the legend as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.
     
    Water heater Return to table of contents
    Estimated age: <5years
    Type: Tank
    Energy source: Electricity
    Capacity (in gallons): 40
    Manufacturer: Richmond
    18) No drain line is installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.

    Photo 2  
    Water heater over pressure valve needs to be vented outside
     

    19) Temperature-pressure relief valve drain line is too short. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should extend the drain line to 6 inches from the floor, or route it so as to drain outside.
    20) A water heater is installed over finished living spaces and has no catch pan and drain installed. Recommend having a qualified contractor install a catch pan and drain to prevent water damage to finished interior spaces below if/when the water heater develops a leak or is drained.
     
    Heating and cooling Return to table of contents
    Primary heating system energy source: Electric
    Primary heat system type: Forced air
    Primary A/C energy source: Electric
    Primary Air conditioning type: Heat pump
    Distribution system: Sheet metal ducts
    Filter location: Behind return air grill
    21) Vegetation such as trees, shrubs and/or vines are too close to the outdoor condensing unit. Standard building practices require that there be at least 12 inches of clearance on all sides and at least four to six feet above. Inadequate clearances around the condensing unit can result in reduced efficiency, increased energy costs and/or damage to equipment. Vegetation should be pruned and/or removed as necessary to maintain these clearances.

    Photo 4  
    Vegetation around AC unit.

    Photo 5  
    Vegetation around AC unit
     
    Plumbing and laundry Return to table of contents
    Location of main water shut-off valve: Well
    Water service: Private
    Supply pipe material: Copper
    Vent pipe material: Plastic
    Drain pipe material: Plastic
    Waste pipe material: Plastic
    22) Copper water supply pipes in homes built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client(s) should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client(s) should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:

  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than six hours.
  • Install appropriate filters at points of use.
  • Use only cold water for cooking and drinking. Hot water dissolves lead more quickly than cold water.
  • Use bottled or distilled water.
  • Treat well water to make it less corrosive.
  • Have a qualified plumbing contractor replace supply pipes and/or plumbing components as necessary.

    For more information visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
    http://www.epa.gov/safewater/lead/index.html
    23) Neither the clothes washer nor dryer were operated or evaluated. They are excluded from this inspection.
     
    Fireplaces, woodstoves and chimneys Return to table of contents
    Fireplace type: Metal prefabricated
    Woodstove type: Metal
    Chimney type: Masonry
    24) The masonry chimney crown is deteriorated (cracked or broken) and needs repairs or replacement. The crown is meant to keep water off of the chimney structure. The chimney can be damaged by wet masonry going through freeze-thaw cycles. A properly constructed chimney crown should:

  • Be constructed using either pre-cast concrete slabs, cast-in-place steel reinforced concrete, solid stone, or metal
  • Be sloped down from the flue a minimum of 3 inches of fall per foot of run
  • Extend a minimum of 2-1/2 inches beyond the face of the chimney on all sides
  • Not directly contact the flue liner (if installed), and this gap should be filled with flexible caulk
  • Have flashing installed between the bottom of the crown and the top of the brick chimney

    A qualified chimney service contractor or mason should evaluate and repair or replace the crown as necessary.

    Photo 8  
    Cracks in cap of chimney
     

    25) The gas supply for one or more gas fireplaces and/or stoves was turned off. As per the Standards of Practice for both the National Association of Certified Home Inspectors (NACHI) and the American Society of Home Inspectors (ASHI) the inspector does not operate gas shut off valves or light pilot lights during inspections. These appliances were not fully evaluated.
     
    Crawl space Return to table of contents
    Inspection method: Partially traversed
    Insulation material underneath floor above: None visible
    Pier or support post material: Masonry
    Beam material: Built up wood
    Floor structure above: Solid wood joists
    Vapor barrier present: No
    26) No vapor barrier is installed. This is a conducive condition for wood destroying insects and organisms due to the likelihood of water evaporating into the structure from the soil. A qualified contractor should install a vapor barrier. Standard building practices require the following:

  • The soil below the vapor barrier should be smooth and free from sharp objects.
  • Seams should overlap a minimum of 12 inches.
  • The vapor barrier should lap up onto the foundation side walls.

    Better building practices require that:

  • Seams and protrusions should be sealed with a pressure sensitive tape.
  • The vapor barrier should be caulked and attached tightly to the foundation side walls. For example, with furring strips and masonry nails.
    27) Water supply pipes are uninsulated. Recommend insulating pipes as necessary for better energy efficiency and to prevent water pipes from freezing.
    28) Some crawl space areas were inaccessible due to low height (less than 18 inches), ductwork or pipes blocking, standing water, and/or stored items. These areas are excluded from this inspection.
     
    Well Return to table of contents
    Location of well equipment: North of house
     
    Kitchen Return to table of contents

    29) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
    30) One or more kitchen appliances appear to be near, at, or beyond their intended service life of 10 to 15 years. Recommend budgeting for replacements as necessary.
    31) The refrigerator ice maker is in the "off" position. The inspector was unable to evaluate this component.
    32) One or more light fixtures have missing bulbs and could not be fully evaluated. Bulbs may simply need to be installed, or repairs or replacement may be necessary.
     
    Bathrooms Return to table of contents

    33) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
     
    Interior rooms Return to table of contents

    34) No smoke alarms are visible. This is a safety hazard. A qualified electrician should install smoke alarms as per standard building practices (functioning one exists in hallways leading to bedrooms, and in each bedroom, etc.). For more information, visit:
    http://www.cpsc.gov/cpscpub/pubs/5077.html

    35) An insufficient number of smoke alarms are installed. Additional smoke alarms should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
     
    General information Return to table of contents
    Report number: 0004
    Inspector's name: Brock Ponder
    Structures inspected: 991 Elkins Road home
    Type of building: Single family
    Time started: 6:18 Pm
    Time finished: 7:55 Pm
    Inspection Fee: 250.00
    Present during inspection: inspector only
    Occupied: No
    Weather conditions: Clear
    Temperature: 92 degrees
    Ground condition: Dry
    Front of structure faces: South
    Main entrance faces: South
    Foundation type: Crawlspace
    The following items are excluded from this inspection: Private well, Shed
    36) Propane was not available during the inspection (tank empty, shut off valve turned off, no tank installed, etc.). As a result, some appliances such as water heater(s), forced air furnace(s), gas fireplace(s), stove(s), range(s) and/or gas supply lines weren't fully evaluated. The inspector was unable to test for gas leaks.
     

    Photo 7  
    Some moisture noticed i crawl space

    Photo 17  
    Paint on windows begining to chip

     