Property Inspection Report

Client(s):  Sample Client
Property address:  Sample Address
Memphis, TN
Inspection date:  Monday, March 27, 2017

This report published on Wednesday, August 02, 2017 10:15:54 AM CDT

A home inspection is designed to find things wrong with the home. Sometimes it can seem overwhelming when you are wanting to buy a house, and you get a report of only negative things. If there is an area of concern for you, I want to encourage you to contact a professional for further evaluation.

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard
Major DefectCorrection likely involves a significant expense
Repair/ReplaceRecommend repairing or replacing
Repair/MaintainRecommend repair and/or maintenance
Minor DefectCorrection likely involves only a minor expense
MaintainRecommend ongoing maintenance
EvaluateRecommend evaluation by a specialist
MonitorRecommend monitoring in the future
CommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp



General Information

Time started: 4:00
Time finished: 5:30
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Warm
Inspection fee: 575
Payment method: Check
Type of building: Single family
Buildings inspected: One house
Source for main building age: Municipal records or property listing, 2002
Occupied: Yes

1) Repair/Maintain, Evaluate - Microbial growths were found at one or more locations in interior rooms. It is beyond the scope of this inspection to identify what substance or organism this staining is. However such staining is normally caused by excessively moist conditions, which in turn can be caused by plumbing or building envelope leaks and/or substandard ventilation. These conducive conditions should be corrected before making any attempts to remove or correct the staining. Normally affected materials such as drywall are removed, enclosed affected spaces are allowed to dry thoroughly, a mildewcide may be applied, and only then is drywall reinstalled. For evaluation and possible mitigation, consult with a qualified industrial hygienist or mold/moisture mitigation specialist. For more information, visit:
http://www.reporthost.com/?MOLDCDC
http://www.reporthost.com/?MOLDEPA
Photo
Photo 1-1
Photo
Photo 1-2

Roof

Roof inspection method: Viewed from eaves on ladder
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable

2) Repair/Replace - Some composition shingles were missing. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.
Photo
Photo 2-1
 

3) Repair/Maintain - One or more roofing nails weren't fully seated and shingles were lifting or nail heads were protruding through shingle surfaces. The nails may have loosened, or were not pounded in fully when installed. Shingles are likely to be wind damaged, and leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.
Photo
Photo 3-1
 

Exterior and Foundation

Wall inspection method: Viewed from ground, from a ladder
Condition of wall exterior covering: Appeared serviceable
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade

4) Repair/Replace - Some sections of siding and/or trim were damaged. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 4-1
Photo
Photo 4-2
Photo
Photo 4-3
Photo
Photo 4-4

5) Maintain - Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 5-1
Photo
Photo 5-2

6) Comment - Rotting wood was found, it was in contact with or close to the building exterior. This is a conducive condition for wood-destroying organisms. Recommend removing or replacing. For more information visit:
http://www.reporthost.com/?FWWDI
Photo
Photo 6-1
Photo
Photo 6-2

Grounds

Site profile: Level
Condition of driveway: Appeared serviceable
Condition of sidewalks and/or patios: Appeared serviceable
Condition of deck, patio and/or porch covers: Required repairs, replacement and/or evaluation (see comments below)

7) Maintain - Wooden deck or porch covers were overdue for normal maintenance. Recommend that a qualified person clean and preserve as necessary. Where decks have been coated with a finish such as opaque stains or paint, it may be too difficult to strip the finish and apply anything but paint or opaque stain. Where transparent stain or penetrating oil has been applied in the past, recommend that a penetrating oil be used. For more information, visit:
http://www.reporthost.com/?PENOIL
http://www.reporthost.com/?DKMAIN
Photo
Photo 7-1
Photo
Photo 7-2

Garage or Carport

Type: Attached
Condition of door between garage and house: Appeared serviceable
Condition of garage vehicle door(s): Appeared serviceable
Number of vehicle doors: 2
Condition of automatic opener(s): Required repair, replacement and/or evaluation (see comments below)
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): No
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable

8) Safety, Repair/Maintain, Evaluate - The auto-reverse mechanism on one or more automatic openers for garage vehicle doors was inoperable. This is a potential safety hazard. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
http://www.reporthost.com/?NRGD
Photo
Photo 8-1
Photo
Photo 8-2

9) Safety, Repair/Maintain - The automatic opener for one or more garage vehicle doors didn't reverse when the photoelectric sensors were blocked. These sensors should reverse the door when closing to prevent injury when a person or pet passes through the sensors' beam. This is a safety hazard. A qualified person should repair as necessary. For more information on garage door safety issues, visit:
http://www.reporthost.com/?GDPES
Photo
Photo 9-1
Photo
Photo 9-2

Attic and Roof Structure

Attic inspection method: Partially traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Approximate attic insulation R value (may vary in areas): R-38

Plumbing / Fuel Systems

Condition of service and main line: Appeared serviceable
Water service: Public
Condition of supply lines: Appeared serviceable
Condition of drain pipes: Appeared serviceable
Vent pipe condition: Appeared serviceable

Fireplaces, Stoves, Chimneys and Flues

Condition of gas-fired fireplaces or stoves: Required repair, replacement and/or evaluation (see comments below)

10) Safety, Maintain, Evaluate - Recommend that the client review all available documentation for gas-fired fireplaces and stoves. Depending on how they are operated (for routine heating versus ambiance), such appliances may need servicing annually or every few years. Consult with the property owner and/or a qualified specialist to determine if service is needed now. Any needed repairs noted in this report should be brought to the attention of the specialist when it's serviced. For more information visit:
http://www.reporthost.com/?ANGFINSP
Photo
Photo 10-1
Photo
Photo 10-2

Kitchen

Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Natural gas
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable

Bathrooms, Laundry and Sinks

Location #A: Full bath, second floor
Location #B: Full bath, second floor
Location #C: Full bath, first floor
Location #D: Full bath, Master bath, first floor
Location #E: Laundry room/area
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: with individual ducts
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes

11) Repair/Maintain - One or more sink drains were leaking at location(s) #D. A qualified person should repair as necessary.
Photo
Photo 11-1
Photo
Photo 11-2

12) Minor Defect - The bathtub at location(s) #A and B drained slowly. Recommend clearing drain and/or that a qualified plumber repair if necessary.
Photo
Photo 12-1
Photo
Photo 12-2

Interior, Doors and Windows

Condition of exterior entry doors: Appeared serviceable
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Condition of walls and ceilings: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of stairs, handrails and guardrails: Appeared serviceable

13) Safety, Repair/Replace - One or more exterior doors had double-cylinder deadbolts installed, where a key is required to open them from both sides. This can be a safety hazard in the event of an emergency because egress can be obstructed or delayed. Recommend replacing double-cylinder deadbolts with single-cylinder deadbolts where a handle is installed on the interior side.
Photo
Photo 13-1
Photo
Photo 13-2

14) Repair/Replace, Evaluate - Wood flooring in one or more areas was crowning. This may indicate that the floor has been exposed to water or that the flooring was not allowed to equalize in moisture content before being installed. Consult with the property owner and/or have a qualified specialist evaluate. It's likely that affected areas of the wood flooring will need to be refinished to obtain a flat surface. For more information, visit:
http://www.reporthost.com/?WDFLRPRB
Photo
Photo 14-1
 

15) Repair/Replace - One or more windows that were designed to open and close were stuck shut. Recommend that a qualified person repair windows as necessary so they open and close easily.
Photo
Photo 15-1
Photo
Photo 15-2
Photo
Photo 15-3
 

16) Repair/Replace - Crank handles at some windows were missing. Recommend that a qualified person replace handles or make repairs as necessary.
Photo
Photo 16-1
Photo
Photo 16-2

17) Repair/Replace - One or more walls had substandard repairs. Recommend that a qualified person repair as necessary.

Added due to a concern of the client. Possible entry point for pests entering the home.
Photo
Photo 17-1
 

18) Monitor - Stains were found in one or more wall areas. However, no elevated levels of moisture were found. The stain(s) may be due to past roof and/or plumbing leaks.Consult with the property owner and monitor the stained area(s) in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, then recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 18-1
Photo
Photo 18-2

19) Comment - No window screens were installed. Windows may not provide ventilation during months when insects are active.

Electric

Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded copper
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Garage
Location of sub-panel #C: Garage
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed

20) Safety, Repair/Replace - One or more circuit breakers in panel(s) #A were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?DBLTAP
Photo
Photo 20-1
Photo
Photo 20-2
Photo
Photo 20-3
 

21) Safety, Repair/Replace - Wire splices were exposed and were not contained in a covered junction box. This is a potential shock or fire hazard. Recommend that a qualified electrician repair per standard building practices. For example, by installing permanently mounted junction boxes with cover plates where needed to contain wiring splices.
Photo
Photo 21-1
 

Water Heater

Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 2014
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Attic
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 130
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable

22) Safety - The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.reporthost.com/?SCALD
Photo
Photo 22-1
Photo
Photo 22-2
Photo
Photo 22-3
 

Water Heater 2

Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Temperature-pressure relief valve installed: Yes
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 130
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable

23) Safety - The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.reporthost.com/?SCALD
Photo
Photo 23-1
 

24) Evaluate, Comment - Due to a camera issue the inspector was unable to determine the age of the water heater. The estimated useful life for most water heaters is 8-12 years. The inspector was unable to determine the age of the water heater due to the manufacturer's label being obscured, no serial number being visible, or the serial number not clearly indicating the age. The client should be aware that this water heater may be near, at or beyond its useful life and may need replacing at any time. Recommend attempting to determine the water heater's age.

If found to be near, at or beyond its useful lifespan, recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater does fail. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 24-1
Photo
Photo 24-2

Water Heater 3

Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 2001
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Attic
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 130
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable

25) Safety - The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.reporthost.com/?SCALD

26) Comment - The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 26-1
Photo
Photo 26-2

Heating, Ventilation and Air Condition (HVAC)

General heating system type(s): Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Estimated age of forced air furnace: 2000
Location of forced air furnace: Attic
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Condition of controls: Appeared serviceable

27) Safety, Repair/Maintain, Evaluate - The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP

28) Major Defect, Comment - The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be at this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Photo
Photo 28-1
Photo
Photo 28-2

29) Major Defect, Comment - The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Photo
Photo 29-1
Photo
Photo 29-2

Heating, Ventilation and Air Condition (HVAC) 2

General heating system type(s): Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2000
Location of forced air furnace: Attic
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Condition of controls: Appeared serviceable

30) Safety, Repair/Maintain, Evaluate - The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP

31) Major Defect, Comment - The estimated useful life for most forced air furnaces is 15-20 years. This furnace appeared to be at this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Photo
Photo 31-1
Photo
Photo 31-2

32) Major Defect, Comment - The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be beyond this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.
Photo
Photo 32-1
Photo
Photo 32-2

Heating, Ventilation and Air Condition (HVAC) 3

General heating system type(s): Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2012
Location of forced air furnace: Attic
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Condition of controls: Appeared serviceable

33) Safety, Repair/Maintain, Evaluate - The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP
Photo
Photo 33-1
Photo
Photo 33-2

34) -
Photo
Photo 34-1
Photo
Photo 34-2

Limitations Of An Inspection


35) Comment - Roof: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.

36) Comment - Exterior and Foundation: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.

37) Comment - Grounds: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.

38) Comment - Garage or Carport: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.

39) Comment - Attic and Roof Structure: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.

40) Comment - Plumbing / Fuel Systems: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.

41) Comment - Fireplaces, Stoves, Chimneys and Flues: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.

42) Comment - Kitchen: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.

43) Comment - Bathrooms, Laundry and Sinks: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.

44) Comment - Interior, Doors and Windows: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.

45) Comment - Electric: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.

46) Comment - Water Heater: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.

47) Comment - Heating, Ventilation and Air Condition (HVAC): The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).


Thank you for choosing Olive Branch Home Inspections. If you have any questions please call 901-336-7211 or find us on facebook.