Property Inspection Report

Client(s):  Client Name
Property address:  Client Address
Inspection date:  Saturday, August 01, 2015

This report published on Monday, August 03, 2015 6:28:19 PM CDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard
Repair/ReplaceRecommend repairing or replacing
Repair/MaintainRecommend repair and/or maintenance
Minor DefectCorrection likely involves only a minor expense
MaintainRecommend ongoing maintenance
EvaluateRecommend evaluation by a specialist
CommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp



General Information

Time started: 345
Time finished: 512
Present during inspection: Tenant
Client present for discussion at end of inspection: No
Weather conditions during inspection: Dry (no rain), Sunny
Temperature during inspection: Warm, 87
Inspection fee: Free
Payment method: Friendship
Type of building: Single family
Buildings inspected: One house
Age of main building: 2001
Source for main building age: Municipal records or property listing
Front of building faces: Southeast
Main entrance faces: Southeast
Occupied: Yes

1) Maintain - Wasp Nest found on back side of house by covered patio. A pest control service can advice you further.
Photo
Photo 1-1
 

2) Comment - Main water shut off valve is found under guest bathroom sink.
Photo
Photo 2-1
 

3) Comment - AC Label for your reference.
Photo
Photo 3-1
Photo
Photo 3-2

4) Comment - Water Heater label for your refrence.
Photo
Photo 4-1
Photo
Photo 4-2
Photo
Photo 4-3
 

Grounds

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Required repairs, replacement and/or evaluation (see comments below)
Deck, patio, porch cover material and type: Open
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Plastic fiber

5) Repair/Maintain, Comment - Rot was found in support posts at one or more structures covering decks, patios and/or porches. Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Photo
Photo 5-1
Photo
Photo 5-2

Exterior and Foundation

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Wall covering: Wood fiber
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Concrete slab on grade

6) Repair/Replace, Comment - Rot was found at one or more sections of siding or trim and/or soffits. Conducive conditions for rot should be corrected (e.g. wood-soil contact, reverse perimeter slope). Recommend that a qualified contractor repair as necessary. All rotten wood should be replaced.
Photo
Photo 6-1
Yellow circle shows possible results of failing flashing. Black arrow shows possible failing flashing.
Photo
Photo 6-2
Photo
Photo 6-3
 

7) Maintain - Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo
Photo 7-1
 

8) Comment - Firewood was stored so that it was in contact with or close to the building exterior. This is a conducive condition for wood-destroying organisms. Recommend storing firewood outdoors in an open area, and as far away from buildings as practical to keep insects away from buildings. For more information visit:
http://www.reporthost.com/?FWWDI
Photo
Photo 8-1
 

Roof

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable, Shed
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)

9) Repair/Replace, Comment - Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 9-1
 

10) Repair/Maintain, Comment - One or more roof flashings were corroded. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 10-1
Yellow circle shows possible results of failing flashing. Black arrow shows possible failing flashing.
 

Attic and Roof Structure

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt, Cellulose loose fill
Approximate attic insulation R value (may vary in areas): R-30
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Ridge vent(s), Gable end vents, Enclosed soffit vents

11) Safety, Repair/Replace, Evaluate - "One or more holes were found in the roof decking. Water could penetrate this area or roof may start to sag in this area. Leaks were not observed at the time of inspection but they will leak eventually. Anyone walking on this roof could fall through. Because this is a potential personal injury hazard, repairs should be made immediately. Have a roofing contractor or carpenter correct this issue."
Photo
Photo 11-1
 

12) Repair/Maintain, Comment - One or more exhaust ducts (e.g. bathroom fan, clothes dryer) in the attic have come apart, were loose or have fallen down. This can result in increased moisture levels inside the structure and is a conducive condition for wood-destroying organisms. Recommend that a qualified person make permanent repairs as necessary.
Photo
Photo 12-1
 

Garage or Carport

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Condition of garage vehicle door(s): Required repair, replacement and/or evaluation (see comments below)
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Required repair or evaluation (see comments below)

13) Safety, Repair/Replace, Comment - One or more holes were found in the attached garage ceilings. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. Recommend that a qualified person repair per standard building practices. For example, by patching openings or holes, firestopping holes or gaps with fire-resistant caulking, and/or installing fire-resistant wall covering (e.g. Type X drywall). For more information, visit:
http://www.reporthost.com/?AGFR
Photo
Photo 13-1
 

14) Safety, Repair/Replace, Comment - Appliances such as the water heater and/or furnace were subject to damage from vehicles because no protective barrier was installed in front of them. This is a potential safety hazard for fire and/or shock. A qualified contractor should install a barrier per standard building practices. For example, a steel post or specially made wood partition anchored in the concrete slab floor.
Photo
Photo 14-1
 

15) Repair/Replace, Comment - One or more garage vehicle doors were damaged or deteriorated. Recommend that a qualified contractor repair or replace door(s) as necessary.
Photo
Photo 15-1
Photo
Photo 15-2

Electric

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Underground
Location of main service panel #A: Garage
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Ground fault circuit interrupter (GFCI) protection present: Yes

16) Safety, Repair/Replace, Comment - One or more receptacles were worn. Worn receptacles can work intermittently or when the plug is wiggled. They can overheat or arc and spark due to loose connections. This is a potential fire hazard. Recommend that a qualified electrician replace such receptacles as necessary.
Photo
Photo 16-1
Photo
Photo 16-2
Photo
Photo 16-3
Photo
Photo 16-4

17) Safety, Repair/Replace, Comment - One or more modern, 3-slot electric receptacles were found with an open ground. This is a shock hazard when appliances that require a ground are used with these receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. Recommend that a qualified electrician repair as necessary so all receptacles are grounded per standard building practices.
Photo
Photo 17-1
 

18) Safety, Repair/Replace - One or more electric receptacles were incorrectly wired with an open neutral. Recommend that a qualified electrician repair as necessary.
Photo
Photo 18-1
 

19) Repair/Replace, Comment - The inspector was unable to open and evaluate panel(s) #A because items were blocking access. These panel(s) are excluded from this inspection. Recommend that repairs, modifications and/or cleanup should be made as necessary so panels can be opened and fully evaluated.
Photo
Photo 19-1
Photo
Photo 19-2

20) Repair/Replace - One or more receptacles have been painted, and slots were clogged with paint. Recommend that a qualified electrician replace such receptacles as necessary.
Photo
Photo 20-1
 

21) - Bulbs in one or more light fixtures were missing. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 21-1
 

Plumbing / Fuel Systems

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of supply lines: Appeared serviceable
Supply pipe material: CPVC plastic
Condition of drain pipes: Appeared serviceable

Water Heater

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Estimated age: 2010
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Garage

22) Safety, Repair/Replace, Comment - The temperature-pressure relief valve drain line was longer than 15 feet and/or had more than 4 elbows. This is a potential safety hazard due to the risk of explosion from restricted flow. A qualified plumber should repair per standard building practices. For more information, visit:
http://www.reporthost.com/?TPRVALVE
Photo
Photo 22-1
 

23) Repair/Maintain, Comment - The water heater was installed in an unheated space on a concrete floor and was not resting on an insulated pad. The bottom of the casing is likely to rust, and energy efficiency may be reduced. Recommend installing an insulated pad under the water heater.
Photo
Photo 23-1
 

Heating, Ventilation and Air Condition (HVAC)

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2011
Location of forced air furnace: Attic
Forced air system capacity in BTUs or kilowatts: 88,000
Condition of forced air ducts and registers: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Type: Split system
Condition of controls: Appeared serviceable

24) Safety, Repair/Replace, Evaluate, Comment - Combustible materials were found too close to the sides and/or front of the furnace cabinet. General guidelines require the following clearances:
  • Minimum 6 inches from the top and sides
  • Minimum 18 inches from the front when electric
This is a potential fire hazard. Recommend any or all of the following as necessary:
  • Research manufacturer's installation instructions to verify minimum allowable clearances
  • Move combustible materials
Photo
Photo 24-1
 

25) Repair/Maintain, Evaluate, Comment - The last service date of the forced air heating/cooling system appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor service this system and make repairs if necessary. Because this system has a compressor and refrigerant system, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the contractor when it's serviced.
Photo
Photo 25-1
 

Fireplaces, Stoves, Chimneys and Flues

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Ceramic and masonry
Condition of chimneys and flues: Appeared serviceable

26) Safety, Repair/Maintain, Evaluate, Comment - One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
Photo
Photo 26-1
Photo
Photo 26-2

27) Minor Defect, Maintain, Evaluate - Fireplace damper would not easily close. To save energy (cooled air) from escaping up the flue of the fireplace. Close vent or contact a chimney sweep to evaluate the damper.
Photo
Photo 27-1
 

Kitchen

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Required repair, replacement and/or evaluation (see comments below)
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable

28) Repair/Replace, Evaluate, Comment - No high loop or air gap was visible for the dishwasher drain. A high loop is created by routing the drain line up to the bottom surface of the counter top above and securely fastening it to that surface. An air gap is a device that makes the drain line non-continuous. Both of these prevent waste-water backflow from entering the dishwasher, and possibly flooding out of the dishwasher if/when a siphon occurs. Some newer dishwashers have these devices built in. The client should try to determine if these devices are built in to this brand and model of dishwasher (e.g. review installation instructions). If not, or if this cannot be determined, then recommend that a qualified contractor install a high loop and air gap per standard building practices.
Photo
Photo 28-1
This "tube" is found under the kitchen sink.
 

Bathrooms, Laundry and Sinks

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Location #B: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)

29) Repair/Maintain, Comment - The bathtub at location(s) #A was worn, blemished or deteriorated.

May cause water damage which could lead to mold or rot.
Photo
Photo 29-1
Photo
Photo 29-2

Interior, Doors and Windows

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Condition of walls and ceilings: Appeared serviceable

Wood Destroying Organism Findings

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.

Thermal Imaging

: Thermal imaging is above and beyond a home inspector’s role. I offer thermal imaging as a complementary service to help further your knowledge of the house. Thermal imaging cameras do have limitations and cannot see every issue. I use a Seek Thermal imaging camera.

30) -
Photo
Photo 30-1
Photo
Photo 30-2
Photo
Photo 30-3
Photo
Photo 30-4
Photo
Photo 30-5
Photo
Photo 30-6
Photo
Photo 30-7
Photo
Photo 30-8
Photo
Photo 30-9
Photo
Photo 30-10
Photo
Photo 30-11
Photo
Photo 30-12
Photo
Photo 30-13
Photo
Photo 30-14
Photo
Photo 30-15
Photo
Photo 30-16