1207 West 23th St

Client(s):  Gwendolyn Ruvalcaba
Property address:  1207 West 23th St San Bernardino CA 92405
Inspection date:  Tuesday, August 22, 2017

This report published on Wednesday, August 23, 2017 7:52:19 PM PDT

Dear customer:

Thank you for choosing New Beginning Home Inspections to perform the following inspection on the property you wish to purchase.
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

All findings should be made to New Beginning Home Inspections.

This report represents our professional opinion of the condition of the inspected elements of the subject property, determine during a limited time inspection. This inspection was performed, where applicable, in a manner consistent with the standards of the home inspection industry, terms and conditions of the inspection agreement and limitations noted in the inspection agreement. Information contained herein was prepared exclusively for the named client and their authorized representatives.

We have inspected the subject property and must report to you exactly what we found. Because of the age, design and location of the home, we might find some hairline cracks on driveways or walls, may hear squeaking on raised or second story floors, see paint peeling off Walls, cracks on tiles, chipped bathtubs or some cracks over windows and doors. These are normal and cosmetic conditions.

While due care was exercised in the performance of this inspection, the company makes no representations or guarantees with respect to latent deficiencies or future conditions as part of the inspection or this report. This report is valid only for a period of thirty (30) days from the date of the inspection. This report, including any attachments, should be reviewed in its entirety. Any questions about the inspection or report should be resolved prior to title transfer.

This inspection report was prepared in a format specifically for the named client and such transfer does not cover all potential areas of concern a third party may have. This report is transferable only with the consent of the named client and such transfer does not imply any warranty or guarantee regarding the report by inspection firm.

If you have any questions regarding this report, please feel free to call us.



LIMITED WARRANTY

This inspection report is a written communication describing the condition of the property inspected. Its purpose is to indicate the existing condition of the subject property. It is not meant to be a demand for repairs by the owner of subject property and communicates a written report of the then existing conditions on the property at the time of the inspection.


During the inspection, our inspectors do not take apart equipment, structures, apply stress and/or perform destructive testing or move furniture and equipment to view areas. Any areas which are visually hidden or not readily accessible are not covered in this report.

Additionally, this report does not include and is not a substitute for a Real Estate Transfer Disclosure Statement, Form TDS-14, California Civil Code Section 1102.

This report does not cover the following items: Evaluate as to whether there are any city, county, or state code violations on the property.
• Evaluate the slopes, grading or credibility of any retaining walls or drainage on the property.
• Perform termite inspections.
• Test security devices.
• Evaluated the presence or extent of insulation and vapor barriers in exterior walls and soffits.
• Enter crawl areas where headroom is less than three feet or where other adverse conditions exist.
• Walk on the roof where it could damage the roof materials or be unsafe for the inspector.
• Enter attic spaces that are not readily accessible or where headroom above the access panel is less than three feet.
• Inspect underground drainage pipes or internal rain gutters and downspouts.
• Operate any main branch or fixture valves that are turned off.
• Inspect any plumbing components that are not visible or readily accessible.
• Inspect water quality, water conditioning equipment and solar water heating systems.
• Evaluate the ability of the systems to comply with the current codes.
• Inspect or activate interior fire sprinkler systems.
• Activate or operate any system that has been shut down.
• Evaluate the mounting of any kitchen cabinets.
• Make repairs or give estimates. Inspect septic tanks.
• Inspect septic tanks. Inspect or test electronic thermostats.
• Turn on or off pool valves.
• Guarantee any appliances and/or pool equipment
• Determine or test for leaks in the roof.
• Any damage done in the attic or under the house, including air ducts, if a termite inspection is made to the property after the completed inspection.
• Damage caused by testing and/or termite inspection.

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeServiceableItem or component is in serviceable condition
Concern typeCommentFor your information
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary


General Information
Return to table of contents

Report number: 135/17
Time started: 3:00 pm
Time finished: 5:00 pm
Present during inspection: Tenant
Client present for discussion at end of inspection: No
Inspector: Jose Antonio Feo
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Hot
Ground condition: Dry
Recent weather: Dry (no rain)
Overnight temperature: Warm
Inspection fee: $299.00
Payment method: Check
Type of building: Single family
Buildings inspected: One house - 1,188 sq ft
Age of main building: 1948
Occupied: Yes

1) Based on substandard construction observed, modifications and/or garage to this property may have been made without the owner having attained permits or inspections from the municipality. Work may have been performed by someone other than a qualified contractor or person. Consult with the property owner about this, and if necessary research permits.

At worst case, if substantial work was performed without permits, this knowledge must be disclosed when the building is sold in the future. This can adversely affect future sales. Also, the local municipality could require costly alterations to bring the building into legal compliance or even require that the additions or modifications be removed.
Photo
Photo 1-1
Photo
Photo 1-2

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Condition of fences and gates: Appeared serviceable
Fence and gate material: Wrought iron
Condition of retaining walls: Appeared serviceable
Retaining wall material: Masonry block
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Concrete

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Metal
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
Foundation/stem wall material: Poured in place concrete, Post and pier construction, no stem wall

2) Many sections of siding and/or trim were deteriorated, loose, split, warped, missing, damaged and/or substandard . Recommend that a qualified person repair, replace or install siding or trim as necessary.
Fungal rot was found at one or more sections of siding or trim, window sills, window frames, soffits, fascia, gable ends, rafter, tails and/or exposed beams . Conducive conditions for rot should be corrected (e.g. wood-soil contact, reverse perimeter slope). Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Glass in one or more windows was cracked, broken and/or missing. Recommend that a qualified contractor replace glass where necessary.
Photo
Photo 2-1
Photo
Photo 2-2
Photo
Photo 2-3
Photo
Photo 2-4
Photo
Photo 2-5
 

3) The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 3-1
 

4) Exterior of the property needs some repairs and re painted.
Photo
Photo 4-1
Photo
Photo 4-2
Photo
Photo 4-3
Photo
Photo 4-4
Photo
Photo 4-5
Photo
Photo 4-6
Photo
Photo 4-7
Photo
Photo 4-8
Photo
Photo 4-9
 

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Location of crawl space access point #A: Building exterior
Condition of floor substructure above crawl space: Appeared serviceable
Pier or support post material: Wood, Concrete

5) Under the bathroom:
Standing water was found at one or more locations in the crawl space. Water from crawl spaces can evaporate and enter the structure above causing high levels of moisture in the structure. This is a conducive condition for wood-destroying organisms. While a minor amount of seasonal water is commonly found in crawl spaces, significant amounts should not be present.

Rain runoff is the most common cause of wet crawl spaces, but water can come from other sources such as groundwater or underground springs. Recommend that a qualified person correct any issues related to outside perimeter grading and/or roof drainage (see any other comments about this in this report). If standing water persists, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typically such repairs include:[list]
  • Repairing, installing or improving underground footing and/or curtain drains
  • Applying waterproof coatings to foundation walls
  • Digging trenches in the crawl space to collect or divert water
  • Installing sump pumps

One or more leaks were found in water supply pipes or fittings. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 5-1
Photo
Photo 5-2
Photo
Photo 5-3
 

6) Foundation and post piers were in serviceable and good condition.
Photo
Photo 6-1
Photo
Photo 6-2
Photo
Photo 6-3
Photo
Photo 6-4

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Need repaired

7) Flashings at the base of one or more air conditioning unit were missing, loose and/or damaged . Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 7-1
Photo
Photo 7-2

8) In general, at the time of the inspection, roof was in serviceable condition.
Photo
Photo 8-1
Photo
Photo 8-2
Photo
Photo 8-3
Photo
Photo 8-4

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Location of attic access point #A: Hallway
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Ceiling beams
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass loose fill

9) Attic was in serviceable and good condition. Attic had good ventilation and insulation. Roof structure was in serviceable condition.
Photo
Photo 9-1
Photo
Photo 9-2
Photo
Photo 9-3
Photo
Photo 9-4
Photo
Photo 9-5
 

Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood
Condition of garage vehicle door(s): Required repair, replacement and/or evaluation (see comments below)
Type of garage vehicle door: Tilt

10) One or more springs were broken on garage vehicle door(s). This is a safety hazard since the door(s) can fall shut when opened. A qualified contractor should repair as necessary.
Photo
Photo 10-1
 

11) 1) One or more garage vehicle doors were damaged or deteriorated. Recommend that a qualified contractor repair or replace replace door(s) as necessary.
2) Garage was converted into a room with bathroom. Clients should consult about permits
3) Exterior fixtures light was damaged
4) The clothes washer was configured so as to drain to the grounds at the building exterior. This is considered an unsanitary practice. Recommend that a qualified plumber reconfigure the drain to tie into the main waste system per standard building practices.
Photo
Photo 11-1
Photo
Photo 11-2
Photo
Photo 11-3
Photo
Photo 11-4
Photo
Photo 11-5
Photo
Photo 11-6
Photo
Photo 11-7
Photo
Photo 11-8
Photo
Photo 11-9
 

12) One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide detectors is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide detectors should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 120
Primary service overload protection type: Circuit breakers
Main disconnect rating (amps): 100
Condition of main service panel: Appeared serviceable
Condition of branch circuit wiring: Serviceable

13) Substandard wiring was found in the attic. For example, exposed wiring. This is a safety hazard. Recommend that a qualified electrician evaluate and repair as necessary and per standard building practices.
Photo
Photo 13-1
Photo
Photo 13-2

14) One or more electric receptacles (outlets) and/or the boxes in which they were installed were loose and/or not securely anchored. Wire conductors can be damaged due to repeated movement and/or tension on wires, or insulation can be damaged. This is a shock and fire hazard. Recommend that a qualified electrician repair as necessary.

15) One or more smoke alarms were missing, damaged, or missing components. Smoke alarms should be replaced as necessary. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
Photo
Photo 15-1
 

16) Cover for the main panel was missing.
Photo
Photo 16-1
Photo
Photo 16-2

17) One or more cover plates for switches, receptacles (outlets) or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 17-1
Photo
Photo 17-2

18) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.google.com/search?q=old+smoke+alarms
Photo
Photo 18-1
Photo
Photo 18-2
Photo
Photo 18-3
Photo
Photo 18-4

19) One or more ceiling fans appeared to be inoperable, or the inspector was unable to find normal controls with which to operate the fan(s). Recommend asking the property owner about their operation, and if necessary, that a qualified electrician evaluate and repair.
Photo
Photo 19-1
Photo
Photo 19-2

20) Electric lights and switches/receptacles should be re evaluated and repairs as necessary.

Photo
Photo 20-1
Photo
Photo 20-2
Photo
Photo 20-3
Photo
Photo 20-4

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Location of main water meter: By street
Location of main water shut-off: Building exterior
Water service: Public
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Required repair, replacement and/or evaluation (see comments below)
Drain pipe material: Plastic
Condition of waste lines: Required repair, replacement and/or evaluation (see comments below)
Waste pipe material: Plastic, Cast iron
Location(s) of plumbing clean-outs: Crawl space
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Above ground
Location of main fuel shut-off valve: At gas meter

21) 1) One or more leaks were found in water supply pipes or fittings. A qualified plumber should evaluate and repair as necessary.
2) The main water service pipe material was made of galvanized steel. Based on the age of the building, the apparent age of the pipe, drain and/or waste, this service pipe may have significant corrosion or rust on the inside
Recommend that a qualified plumber inspect the waste lines using a video scope device to determine if they need repair or replacement.
3) One or more sink drains were leaking. A qualified person should repair as necessary.
Photo
Photo 21-1
Photo
Photo 21-2
Photo
Photo 21-3
Photo
Photo 21-4
Photo
Photo 21-5
Photo
Photo 21-6
Photo
Photo 21-7
Photo
Photo 21-8
Photo
Photo 21-9
Photo
Photo 21-10
Photo
Photo 21-11
 

22) Gas meters was in serviceable condition.
Photo
Photo 22-1
Photo
Photo 22-2

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 40
Location of water heater: exterior
Condition of burners: Appeared serviceable

23) 1) Water heater was in serviceable and working condition.
It was hot water in the kitchen and bathrooms.
2)The gas supply to the furnace, water heater and/or clothes dryer used only rigid pipe. An approved flexible connector should be installed between appliances and rigid gas piping so the piping won't break loose during an earthquake. Recommend that a qualified contractor repair per standard building practices.
3) The source of combustion and/or dilution air for the water heater was substandard because the duct was loose.A qualified person should repair per standard building practices as necessary.

Photo
Photo 23-1
Photo
Photo 23-2
Photo
Photo 23-3
Photo
Photo 23-4
Photo
Photo 23-5
Photo
Photo 23-6

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Location of forced air furnace: roof
Condition of furnace filters: Required replacement
Location for forced air filter(s): At base of air handler
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Natural gas

24) The last service date of the forced air heating/cooling system appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor service this system and make repairs if necessary. Because this system has a compressor and refrigerant system, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the contractor when it's serviced.
Photo
Photo 24-1
 

25) At the time of the inspection, air conditioning unit was in serviceable working condition.
Photo
Photo 25-1
Photo
Photo 25-2
Photo
Photo 25-3
Photo
Photo 25-4
Photo
Photo 25-5
 

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.

26) 1) No spark screen or rain cap was installed at one or more chimney flue terminations. Spark screens reduce the chance of embers exiting the flue and causing fires. They also prevent wildlife (e.g. birds, rodents, raccoons) from entering flues. Rain caps prevent water from entering flues, mixing with combustion deposits and creating caustic chemicals which can corrode flues. They also prevent damage to masonry from freeze-thaw cycles and prevent metal components (e.g. dampers, metal firebox liners) from rusting. Recommend that a qualified person install rain caps with spark screens per standard building practices where missing.
2) Single-wall metal stove or gas pipe was sealed. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 26-1
Photo
Photo 26-2
Photo
Photo 26-3
Photo
Photo 26-4

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: Near, at or beyond service life
Condition of range, cooktop: Required repair, replacement and/or evaluation (see comments below)
Range, cooktop type: Natural gas
Condition of refrigerator: Appeared serviceable

27) The dishwasher was inoperable. Recommend that a qualified specialist evaluate and repair or replace as necessary.
Photo
Photo 27-1
Photo
Photo 27-2
Photo
Photo 27-3
Photo
Photo 27-4

28) One or more cabinets, drawers and/or cabinet doors were damaged or deteriorated. Recommend that a qualified person repair or replace as necessary.

29) The cooktop exhaust fan was inoperable. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 29-1
Photo
Photo 29-2

30) 1) Countertops and/or backsplashes were damaged or deteriorated. Recommend repairing or replacing as necessary.
2) One or more cabinets, drawers and/or cabinet doors were damaged or deteriorated. Recommend that a qualified person repair or replace as necessary.
3) One or more tiles were broken or damaged and should be repair as necessary.
4) The cooktop exhaust fan was inoperable . Recommend that a qualified person repair or replace as necessary.
Photo
Photo 30-1
Photo
Photo 30-2
Photo
Photo 30-3
Photo
Photo 30-4

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Required repair, replacement and/or evaluation (see comments below)

31) One or more cabinets, drawers and/or cabinet doors at location(s) #A were damaged or deteriorated. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 31-1
Photo
Photo 31-2
Photo
Photo 31-3
 

32) 1) The exhaust fan was inoperable . Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person clean, repair or replace fans as necessary.
2) One or more sink drains were leaking . A qualified person should repair as necessary.
3) The floor and/or wall by the bathtub was water-damaged. Recommend that a qualified person repair as necessary.
4) The toilet ran water continuously or didn't shut off after being flushed, and water leaked from the tank into the bowl. Significant amounts of water can be lost through such leaks. If this system uses a septic system, the septic system can be overloaded and cause significant and potentially expensive damage. A qualified person should repair or replace components as necessary.
5) The bathtub drained slowly. Recommend clearing drain and/or that a qualified plumber repair if necessary.
Photo
Photo 32-1
Photo
Photo 32-2
Photo
Photo 32-3
Photo
Photo 32-4
Photo
Photo 32-5
Photo
Photo 32-6
Photo
Photo 32-7
Photo
Photo 32-8
Photo
Photo 32-9
Photo
Photo 32-10

33) Conducive conditions One or more sink drains were leaking at location(s) #A. A qualified person should repair as necessary.

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors:
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Metal
Condition of walls and ceilings: Need painted
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Tile

34) Carpeting in one or more areas was damaged or deteriorated. Recommend that a qualified contractor replace as necessary.

35) Tile, stone and/or grout in the flooring in one or more areas was deteriorated (e.g. loose or cracked tiles, missing grout) or substandard. If in a wet area, water can damage the the sub-floor. Recommend that a qualified contractor repair as necessary.

Walls should be painted as necessary.
The interior of the property should be cleaned.
Photo
Photo 35-1
Photo
Photo 35-2
Photo
Photo 35-3
Photo
Photo 35-4
Photo
Photo 35-5
Photo
Photo 35-6
Photo
Photo 35-7
Photo
Photo 35-8
Photo
Photo 35-9
Photo
Photo 35-10
Photo
Photo 35-11
 

36) Screens were missing from some windows. These windows may not provide ventilation during months when insects are active.