Minneapolis Home Inspections, LLC

Website: http://www.minneapolishomeinspections.com
Email: matt@minneapolishomeinspections.com
Phone: (612) 605-8767
880 19th Ave SE 
Minneapolis, MN 55414
Inspector: Matt Butcher

  

Residential Property Inspection
Client(s): John and Jane Doe
Property address: 1234 East River Dr
Bloomington, MN 55343
Inspection date: Friday, June 09, 2006
This report published on 6/13/2006 11:25:32 AM CDT

View summary page

This report is the exclusive property of Minneapolis Home Inspections, LLC and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.


How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and shown in bold type. Items of concern follow descriptive information and are shown as follows:
SafetyPoses a risk of injury or death 
Major defectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor defectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
ServiceableItem or component is in serviceable condition 
CommentFor your information 
Concern items are sorted by the types listed above.  Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Basement
Kitchen
Bathrooms
Interior rooms


General information Return to table of contents  
Type of building: Single family
Age of building: 1931
Time started: 1:00
Time finished: 4:30
Present during inspection: Client(s)
Occupied: No, but furnishings and stored items are present
Weather conditions: Clear
Temperature: Warm
Ground condition: Damp
Foundation type: Unfinished basement
The following items are excluded from this inspection: Security system
1) This property has one or more fuel burning appliances, and no carbon monoxide alarms are visible. This is a safety hazard. Recommend installing one or more carbon monoxide alarms as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
2) Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygenists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:
  • The Environmental Protection Association (http://www.epa.gov)
  • The Consumer Products Safety Commission (http://www.cpsc.gov)
  • The Center for Disease Control (http://www.cdc.gov)
  •  


    Exterior Return to table of contents  
    Exterior Summary: My exterior evaluation is visual in nature and is based on my experience and understanding of common building methods and materials. My review does not take into consideration the normal wear associated with virtually all properties. Window screens are commonly missing or stored away, therefore I may not mention such items. Fences and gates are not inspected as they are not within of the review. Door bells are also not inspected as they are on a low voltage system.
    Foundation material: Concrete block
    Apparent wall structure: Wood frame
    Wall covering: Cement-asbestos shingles
    Driveway material: Poured in place concrete
    Exterior door material: Solid core wood
    3) Flashing is missing from above one or more deck ledger boards. This can cause moisture to accumulate between the ledger board(s) and the structure. Rot may result in this area and cause the ledger board fasteners to fail. The deck may separate from the structure in this event and poses a significant safety hazard. A qualified contractor should install flashing above ledger board(s) where necessary. For more information on installing deck ledger boards visit: http://www.hometime.com/Howto/projects/decks/deck_4.htm

    And for more information on building safe decks in general, visit: http://www.thisoldhouse.com/toh/knowhow/exteriors/article/0,16417,212625,00.html

    Photo 9  
     
    4) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

    Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079
    5) Soffit boards are damaged or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary.

    Photo 10  
     
    6) The perimeter grading slopes towards the structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure with a slope of at least 5% (10% or better is optimal) for at least 6 feet.
    7) One or more minor cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks including:
  • Hydraulic cement. Requires chiseling a channel in the crack to apply. See http://www.quickrete.com/catalog/HydraulicWater-StopCement.html for an example.
  • Resilient caulks (easy to apply). See http://www.quickrete.com/catalog/GrayConcreteRepair.html for an example.
  • Epoxy sealants (both a waterproof and structural repair). See http://www.mountaingrout.com/ for examples of these products.
  • 8) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
    9) Window glazing putty at one or more windows is missing and/or deteriorated. Putty should be replaced and/or installed where necessary. For more information on replacing window putty, visit: http://www.oldhouseweb.com/stories/Detailed/12216.shtml
    10) Recommend cleaning deck(s) and treating with a preservative claiming to waterproof, block ultraviolet light, and stop mildew. Consumer Reports recommends these products:

  • Cabot Decking Stain and PTW Stain
  • Olympic Water Repellent Deck Stain
  • Thompson's House and Deck Stain
  • Wolman PTW Deck Stain
  • Akzo Sikkens Cetol DEK
  • Benjamin Moore Moorwood Clear Wood Finish
  • DAP Woodlife Premium
  • Olympic Natural Look Protector Plus
  •  


    Roof Return to table of contents  
    Roof Summary: My evaluation of the roof is to determine if portions are missing and/or deteriorating and, therefore, subject to possible leaking. Portions of the underlayment and decking are hidden from view and cannot be evaluated by my visual inspection. My review is not a guarantee against roofing leaks nor a certification. Whenever a roof is too tall, too steep or cannot be mounted due to weather conditions, client is advised that only a limited review is possible of the roof and chimneys. When a rain cap is provided on the chimney, the flue cannot be viewed.
    Estimated age of roof: 5 years
    Roof inspection method: Viewed from ground with binoculars
    Roof type: Gable
    Roof covering: Asphalt or fiberglass composition shingles
    Gutter & downspout material: Aluminum
    Roof ventilation: Inadequate
    11) This asphalt or fiberglass composition roof surface has two or more layers of roofing materials. When this roof is replaced, recommend a complete "tear off", where all existing layers of roofing are removed before installing new roofing materials. For 20-year rated composition shingles, additional layers of material reduce the new roof material's lifespan as follows:

  • 16-20 years - First roof
  • 12-16 years - Second layer on existing roof

    Removing existing roofing materials will significantly increase the cost of the next roof.
  • 12) One or more composition shingles have raised, most likely due to nails that have loosened. Leaks may occur as a result. A qualified roofing contractor should evaluate and make repairs as necessary, such as reseating nails.
    13) Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.

    Photo 6  
     
     


    Garage Return to table of contents  
    14) The auto-reverse mechanism on the vehicle door opener is inoperable or requires too much force to activate. This is a safety hazard, especially for small children. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
    15) The electric receptacle on the east wall is loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.
    16) Cover plate is missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

    Photo 7  
     
     


    Attic Return to table of contents  
    Attic Summary: Water stains around roof penetrations such as chimneys, plumbing, vents, and heating vents are very common. It is difficult to determine if these stains are active. Insulation in the attic is one of the best ways to improve the energy efficiency of a home. My report measures insulation materials by depth. Generally the greater the depth of insulation, the more resistance the ceiling has to heat loss. There is a limited view of any areas covered with insulation.
    Ceiling structure: Ceiling beams
    Inspection method: Viewed from hatch
    Roof structure type: Rafters
    Insulation material: Cellulose loose fill
    17) Ventilation is substandard in the attic. Inadequate attic ventilation may result in high attic and roof surface temperatures, reduce the life of the roof covering materials and increase cooling costs. High levels of moisture are also likely, and can be a conducive condition for wood destroying insects and organisms. Standard building practices require one square foot of vent area for 150 to 200 square feet of attic space. Vents should be evenly distributed between soffits, ridges and at corners to promote air circulation. A qualified contractor should evaluate and install vents as per standard building practices.
    18) Ceiling insulation is uneven in some areas. This is likely due to someone having walked on or through the insulation. Recommend installing additional insulation where necessary to restore the original R rating.
    19) One or more attic vents are blocked by insulation and/or debris. This can reduce air flow through the attic, reduce the life of the roof surface because of high temperatures, and/or increase moisture levels in the attic. Repairs should be made as necessary, such as moving insulation or debris, so vents are unobstructed.

    Photo 11  
     
    20) No insulation is installed over the attic access hatch. Recommend installing insulation above hatch for better energy efficiency.

    Photo 12  
     
     


    Electric service Return to table of contents  
    Electrical Summary: While ground fault interrupters may not have been required at the time this home was built, I strongly suggest that they be installed at all receptacles near water sources, such as kitchens and bathrooms. I also recommend that they be installed at the garage and the exterior of the home to enhance your electrical safety. Client is advised that I test all receptacles that are accessible. However, I do not unplug electrical items nor do I move owner’s furniture.
    Primary service type: Overhead
    Service amperage (amps): 100
    Primary service overload protection type: Circuit breakers
    Service voltage (volts): 120/240
    Location of main disconnect: Breaker at top of main service panel
    Service entrance conductor material: Aluminum
    System ground: Cold water supply pipes
    Main disconnect rating (amps): 100
    Branch circuit wiring type: Non-metallic sheathed, (BX) Armor clad
    Solid strand aluminum branch circuit wiring present: No
    21) This property has one or more Federal Pacific Electric brand main service or sub panels that use "Stab-Lok" circuit breakers. Both double and single pole versions of these circuit breakers are known to fail by not tripping when they are supposed to. This is a potential but serious fire hazard. Recommend having a qualified electrician replace any and all Federal Pacific panels. For more information, visit: http://www.inspect-ny.com/fpe/fpepanel.htm

    If the Federal Pacific panel(s) are not replaced, then a qualified electrician should thoroughly evaluate the panel(s) and make repairs as necessary. Recommend installing smoke detectors above Federal Pacific panels.

    Photo 3  
     
    22) One or more overcurrent protection devices (circuit breakers or fuses) are "double tapped", where 2 or more wires are clamped in a terminal designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. A qualified electrician should evaluate and repair as necessary.

    Photo 15  
     
    23) Neutral wires are doubled or bundled together on the neutral bus bar. This is unsafe due to the need to turn off multiple circuit breakers to work on any of the circuits using these wires. A qualified electrician should evaluate and repair as necessary.

    Photo 16  
     
     


    Water heater Return to table of contents  
    Water Heater Summary: Water heaters should be properly equipped with a temperature and pressure relief valve. Although the temperature and pressure relief valve was located and appears to be installed properly, the relief valve was not tested due to the possibility of the valve leaking after it has been opened.
    Estimated age: 12 years
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 40
    Manufacturer: American Standard
    Model: GELN 1003523830
    Water temperature (degrees Fahrenheit): 135
    24) Based on the location of the water heater and the visible venting, the water heater may have an inadequate source of combustion and/or dilution air. All gas appliances require adequate air (approximately 50 cubic feet per 1000 BTU) for combustion, dilution and ventilation. This is a potential safety hazard, and may result in combustion fumes entering living spaces. A qualified contractor should evaluate and make repairs as necessary, such as installing exterior vents, or grills in walls or doors.
    25) The hot water temperature is greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. For more information on scalding dangers, visit http://www.tap-water-burn.com/
    26) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.
     


    Heating and cooling Return to table of contents  
    Heating and Cooling Summary: My evaluation of major systems is both visual and functional provided power and/or fuel is supplied to the component. The inspection of gas lines is not within the scope of this review. A heat source is present in every finished area unless otherwise noted. Identifying or testing for the presence of asbestos, radon, lead based products, or other potentially hazardous materials is not within the scope of this report. Judging the sufficiency of water flow in plumbing or the cooling efficiency of air conditioning is a subjective evaluation, therefore, I only note a poor condition if, in my opinion, the adequacy appears to be less than normal. I urge you to evaluate these systems prior to closing. Dismantling and/or extensive inspection of internal components of any appliance, including heaters and heat exchangers, is beyond the scope of this report.
    Estimated age: 6 years
    Primary heat system type: Forced air
    Primary heating system energy source: Natural gas
    Primary A/C energy source: Electric
    Primary Air conditioning type: Split system
    Manufacturer: Bryant
    27) The furnace or boiler flame(s) are noisy (roaring) and/or "dancing" over the burner(s). This may be caused by an improper gas-air mixture flow velocity and may result in Carbon Monoxide due to incomplete combustion. A qualified heating and cooling contractor should evaluate and repair as necessary.
    28) Significant amounts of debris, dirt and/or dust are visible in one or more sections of supply and/or return air ducts. This can be a health hazard, especially for those with allergies or respiratory problems. The Environmental Protection Association (EPA) recommends considering having ducts professionally cleaned when "ducts are clogged with excessive amounts of dust and debris and/or particles are actually released into the home from your supply registers". At a minimum, the visible debris should be thoroughly cleaned. Recommend having a qualified contractor clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit: http://www.epa.gov/iaq/pubs/airduct.html
    29) The estimated useful life for air conditioning compressors is 8 to 15 years. This unit appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
    30) One or more rooms' interior doors have no gap below, or have a gap less than 3/4". As a result, return air flow out of the room is restricted with closed door(s) and the heating/cooling system on. This may result in the heating and/or cooling system having a reduced efficiency and higher energy costs. To allow adequate return air flow, recommend either trimming the bases of doors as necessary to maintain a 3/4" gap below, or leaving doors open while the heating or cooling system is in operation.
    31) The last service date of this system appears to be more than two years ago. A qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed every few years in the future, or as per the contractor's recommendations.
    32) The cooling fins on the air handler's evaporator coils are dirty. This may result in reduced efficiency and higher energy costs. Some sources claim that energy efficiency is degraded by about five percent each year as the coils get dirtier due to accumulated dust and grime. A qualified heating and cooling contractor should clean the evaporator coils as necessary.

    Photo 14  
     
     


    Plumbing and laundry Return to table of contents  
    Plumbing Summary: The water system was tested for its ability to deliver functional water pressure to installed plumbing fixtures and the condition of the connecting piping that were visible. When low water flow is noted at plumbing fixtures, client should contact a qualified plumber for further review is concerned. Also, shutoff valves under the sink as well as the main shut off and angle stops under kitchen and bathroom sinks and toilets are not tested during the inspection due to the possibility of creating a leak at the valve stem packings. I suggest that all shut off valves be tested to ensure free movement in case of an emergency.
    Laundry Summary: It is noted that in an occupied home when the dryer hookup is obstructed by the appliances, the hookup cannot be tested. Client is advised that if a new electric dryer is installed and the existing receptacle is a three pronged 220 receptacle, it will be required to be replaced with a four pronged 220 receptacle. If plastic vent lines are used, they will also be required to be replaced with either solid metal or metal flex vents when the dryer is installed.
    Water pressure (psi): 75 psi
    Water service: Public
    Service pipe material: Copper
    Supply pipe material: Copper, Galvanized steel
    Vent pipe material: Galvanized steel
    Drain pipe material: Plastic, Galvanized steel
    Waste pipe material: Cast iron
    33) The clothes dryer is equipped with a vinyl or foil, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, see http://www.cpsc.gov/CPSCPUB/PUBS/5022.html

    Photo 1  
     
    34) Some, most, or all of the water supply pipes in this structure are made of galvanized steel. Based on the age of this structure, these pipes may be nearing or may have exceeded their estimated useful life of 40 to 60 years. Internal corrosion and rust can reduce the inside diameter of these pipes over time, resulting in reduced flow and eventually, leaks. The inspector performed a "functional flow test" during the inspection where multiple fixtures were run simultaneously, and found the flow to be adequate. For example, the shower flow didn't decrease substantially when the toilet was flushed. Despite this, and because of their apparent age, these pipes may need replacing at any time.
    35) The laundry sink is not anchored to the wall or floor. A qualified contractor should securely anchor the sink to the wall and/or floor to prevent damage to and leaks in the water supply and/or drain pipes due to the sink being moved.
    36) The clothes washer had clothing in it and was not operated during this inspection. The inspector was unable to fully evaluate the washer and its drain line.
     


    Fireplaces, woodstoves and chimneys Return to table of contents  
    Chimney type: Masonry
    37) The masonry chimney crown is deteriorated (cracked or broken) and needs repairs or replacement. The crown is meant to keep water off of the chimney structure. The chimney can be damaged by wet masonry going through freeze-thaw cycles. A properly constructed chimney crown should:

  • Be constructed using either pre-cast concrete slabs, cast-in-place steel reinforced concrete, solid stone, or metal
  • Be sloped down from the flue a minimum of 3 inches of fall per foot of run
  • Extend a minimum of 2-1/2 inches beyond the face of the chimney on all sides
  • Not directly contact the flue liner (if installed), and this gap should be filled with flexible caulk
  • Have flashing installed between the bottom of the crown and the top of the brick chimney

    A qualified chimney service contractor or mason should evaluate and repair or replace the crown as necessary.
  • 38) The chimney flue does not have a rainproof cover installed. It prevent the following:

  • Rainwater entering flues and mixing with combustion deposits, creating caustic chemicals which can corrode flues
  • Rainwater entering flues and causing damage to terracotta flue tiles from freeze-thaw cycles

    A qualified chimney service contractor should install a rainproof cover where missing.

    Photo 13  
     
  • 39) The glass on one or more gas fireplaces and/or stoves has a hazy film. This is typically a mineral residue left from water vapor as the gas burns. It may be possible to clean this fogging by removing the glass from the fireplace and using a gas appliance ceramic glass cleaner, available through gas fireplace and stove distributors and installers. Ammonia-based products, such as common glass cleaners should not be used since they may cause damage or etching to the glass, or make the haze permanent.

    It may be possible for a homeowner to remove the glass for cleaning, depending on if the instructions or manual for the fireplace are available, and if the homeowner is experienced in such repairs. Recommend consulting with a gas fireplace installation contractor for more information, or to have them do the cleaning.

    Photo 2  
     
     


    Basement Return to table of contents  
    Basement Summary: Basements are checked for evidence of water penetrations and unusual cracks. Client is advised that hairline cracks are very common in basement areas and are not usually readily visible. Therefore hairline cracks are not typically noted in the report unless and obvious problem, such as leaking, is noted during the inspection. Virtually all basements are vulnerable to water seepage due to their location below grade. Based on a one-time review, we obviously cannot predict whether a basement will leak in the future. Changing soil conditions and unusual weather can cause leakage even in previously dry basements. Regular monitoring of the basement walls is considered to be part of routine home maintenance as water seepage can occur at any time. There are, however many maintenance procedures that can be performed that will help prevent the potential for water penetration. Some of these procedures are located in the Home Inspection Manual you will receive with your report. Whenever a basement is finished, I am unable to view the foundation walls in these areas. I am unable to view any areas that are obstructed by owner’s belongings and I am not allowed to move any of the owner’s belongings. Client is advised that no obstructed areas are inspected.
    Beam material: Solid wood
    Pier or support post material: Wood
    Floor structure above: Solid wood joists
    40) Some wiring is loose, unsupported, or inadequately supported. Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.

    Photo 4  
     
    41) Stairs are unsafe due to a non-standard configuration, such as too-high riser heights and/or too-narrow tread depths. Standard building practices call for riser heights not to exceed eight inches and tread depths to be at least nine inches but preferably 11 inches. Riser heights should not vary more than 3/8 inch on a flight of stairs. At a minimum, the client(s) should be aware of this hazard, especially when guests who are not familiar with the stairs are present. Ideally a qualified contractor should repair or replace stairs so they conform to standard building practices.
    42) Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains and/or efflorescence on the foundation or floor, water stains at bases of support posts, etc. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. The client(s) should review any disclosure statements available and ask the property owner(s) about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.
  •  


    Kitchen Return to table of contents  
    Kitchen Summary: The kitchen inspection is a combination of visual and functional. Appliances are operated, if power is supplied. Calibrations to cooking systems are not evaluated nor life expectancies given to dishwashers. Note: Dishwashers can fail at any time due to their complexity. My review is to determine if the system is free of leaks and excessive corrosion. Refrigerators, trash compactors and other portable type appliances are not within the scope of this review. Self cleaning devices on ovens are not within the scope of this inspection and are not tested. I suggest client verify its operation prior to closing.
    43) Substandard wiring was found for the under-sink food disposal. Unprotected solid-strand, non-metallic sheathed (Romex) wiring is used. The insulation can be damaged by objects coming in contact with it and/or it being repeatedly moved. This is a safety hazard due to the risk of shock and fire. Armored (BX) cable, or a flexible appliance cord with a plug end and electric outlet should be used. A qualified electrician should evaluate and repair as necessary.

    Photo 17  
     
    44) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
    45) The dishwasher drain line is not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The clients should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.

    Also, no "air gap" is installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client(s) should consult with a qualified contractor to determine if an air gap should be installed.
    46) Ice maker is not connected to water supply.
     


    Bathrooms Return to table of contents  
    Bathroom Summary: My focus in bathrooms is directed at identifying visible water damage and/or problems. I recommend keeping the area around the faucets sealed at all times to prevent water penetration. Tub/Shower enclosures will leak if sprayed directly. While resealing may be required, this condition is not unusual and directing the shower head away from the enclosure is recommended. I may not always mention common faults such as stuck stoppers or dripping faucets. If considered important, you should check these items independently. It is beyond the scope of this inspection to determine whether the glass in this home is safety glass as the identifying sticker may have been removed.
    47) One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested with the inspector's test instrument. These devices should trip when tested with a test instrument in addition to tripping via the test buttons on the receptacles. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.
    48) Floor tiles installed in "wet" areas have gaps between them. The wooden subfloor beneath may be damaged by water intrusion. A qualified contractor should evaluate, make repairs if necessary, and replace flooring with a waterproof floor such as sheet vinyl in wet areas.
    49) One or more bathrooms with a shower do not have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
    50) Caulk is missing and/or deteriorated at one or more showers. For example, where the shower base meets the floor below and/or around the shower surround. Caulk should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to wall and floor structures.

    Photo 18  
     
    51) Recommend cleaning and sealing grout in countertops now and in the future as necessary to prevent staining and to improve waterproofing.
     


    Interior rooms Return to table of contents  
    Interior Rooms Summary: My interior view is visual and evaluated with similar aged homes in mind. Cosmetic considerations and minor flaws such as a torn screen or an occasional cracked window can be overlooked, thus I suggest you double check these items, if concerned. Minor adjustments needed to the hardware on doors and windows are not commonly listed individually in this report. A heat source is provided in every room unless otherwise noted. The inspector will test all of the receptacles that are accessible at the time of the inspection. No item will be unplugged to allow a receptacle to be tested.
    52) Few electric receptacles and two-pronged receptacles rather than three-pronged, grounded receptacles are installed in one or more interior rooms. This can result in "octopus" wiring with extension cords. Two-prong receptacles are considered unsafe by today's standards, and limit the ability to use appliances that require a ground in these rooms. This is a safety hazard for both fire and shock. Examples of appliances that require grounded receptacles include:

  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

    This list is not exhaustive. A qualified electrian should evaluate and install additional receptacles and grounded receptacles as per the client(s)' needs and standard building practices.
  • 53) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit this article: NFPA urges replacing home smoke alarms after 10 years.
    54) Some ceiling areas in this structure have "popcorn" textured surfaces possibly installed prior to 1979. This material may contain asbestos, which is a known carcinogen and poses a health hazard. Laws were passed in the United States in 1978 prohibiting use of asbestos in residential structures, but stocks of existing materials have been known to be used for some time thereafter. The client(s) may wish to have this ceiling material tested by a qualified lab to determine if it does contain asbestos.

    In most cases, when the material is intact and in good condition, keeping it encapsulated with paint and not disturbing it may reduce or effectively eliminate the health hazard. If the client wishes to remove the material, or plans to disturb it through remodeling, they should have it tested by a qualified lab and/or consult with a qualified industrial hygenist or asbestos abatement specialist. For more information, visit: http://www.cpsc.gov/CPSCPUB/PUBS/453.html
    55) The sash spring mechanism(s) in one or more windows are broken or loose. A qualified contractor or service technician should evaluate and make repairs as necessary so the window(s) operate as intended (open easily, stay open without support, close easily, etc.).

    Photo 19  
     
    56) Many of the windows "weep holes" were plugged. Weep holes are located at the bottom edge of a window between the window and the exterior storm. It is important these are kept open to allow airflow and prevent moisture build-up and possible wet rot.
     
    Thank you for choosing Minneapolis Home Inspections, LLC. Please do not hesitate to call or email with any questions or comments regarding the information in this report.