 | Safety | Poses a risk of injury or death |
 | Major defect | Correction likely involves a significant expense |
 | Repair/Replace | Recommend repairing or replacing |
 | Repair/Maintain | Recommend repair and/or maintenance |
 | Minor defect | Correction likely involves only a minor expense |
 | Maintain | Recommend ongoing maintenance |
 | Evaluate | Recommend evaluation by a specialist |
 | Monitor | Recommend monitoring in the future |
 | Serviceable | Item or component is in serviceable condition |
 | Comment | For your information |
Concern items are sorted by the types listed above.
  |
3) Flashing is missing from above one or more deck ledger boards. This can cause moisture to accumulate between the ledger board(s) and the structure. Rot may result in this area and cause the ledger board fasteners to fail. The deck may separate from the structure in this event and poses a significant safety hazard. A qualified contractor should install flashing above ledger board(s) where necessary. For more information on installing deck ledger boards visit: http://www.hometime.com/Howto/projects/decks/deck_4.htm
And for more information on building safe decks in general, visit: http://www.thisoldhouse.com/toh/knowhow/exteriors/article/0,16417,212625,00.html
|
  |
4) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.
Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079
|
  |
5) Soffit boards are damaged or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary.
|
 |
6) The perimeter grading slopes towards the structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure with a slope of at least 5% (10% or better is optimal) for at least 6 feet.
|
 |
7) One or more minor cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks including: Hydraulic cement. Requires chiseling a channel in the crack to apply. See http://www.quickrete.com/catalog/HydraulicWater-StopCement.html for an example. Resilient caulks (easy to apply). See http://www.quickrete.com/catalog/GrayConcreteRepair.html for an example. Epoxy sealants (both a waterproof and structural repair). See http://www.mountaingrout.com/ for examples of these products.
|
 |
8) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
|
 |
9) Window glazing putty at one or more windows is missing and/or deteriorated. Putty should be replaced and/or installed where necessary. For more information on replacing window putty, visit: http://www.oldhouseweb.com/stories/Detailed/12216.shtml
|
 |
10) Recommend cleaning deck(s) and treating with a preservative claiming to waterproof, block ultraviolet light, and stop mildew. Consumer Reports recommends these products:
Cabot Decking Stain and PTW Stain Olympic Water Repellent Deck Stain Thompson's House and Deck Stain Wolman PTW Deck Stain Akzo Sikkens Cetol DEK Benjamin Moore Moorwood Clear Wood Finish DAP Woodlife Premium Olympic Natural Look Protector Plus
|
  |
11) This asphalt or fiberglass composition roof surface has two or more layers of roofing materials. When this roof is replaced, recommend a complete "tear off", where all existing layers of roofing are removed before installing new roofing materials. For 20-year rated composition shingles, additional layers of material reduce the new roof material's lifespan as follows:
16-20 years - First roof 12-16 years - Second layer on existing roof
Removing existing roofing materials will significantly increase the cost of the next roof.
|
  |
12) One or more composition shingles have raised, most likely due to nails that have loosened. Leaks may occur as a result. A qualified roofing contractor should evaluate and make repairs as necessary, such as reseating nails.
|
 |
13) Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.
|
  |
17) Ventilation is substandard in the attic. Inadequate attic ventilation may result in high attic and roof surface temperatures, reduce the life of the roof covering materials and increase cooling costs. High levels of moisture are also likely, and can be a conducive condition for wood destroying insects and organisms. Standard building practices require one square foot of vent area for 150 to 200 square feet of attic space. Vents should be evenly distributed between soffits, ridges and at corners to promote air circulation. A qualified contractor should evaluate and install vents as per standard building practices.
|
 |
18) Ceiling insulation is uneven in some areas. This is likely due to someone having walked on or through the insulation. Recommend installing additional insulation where necessary to restore the original R rating.
|
 |
19) One or more attic vents are blocked by insulation and/or debris. This can reduce air flow through the attic, reduce the life of the roof surface because of high temperatures, and/or increase moisture levels in the attic. Repairs should be made as necessary, such as moving insulation or debris, so vents are unobstructed.
|
 |
20) No insulation is installed over the attic access hatch. Recommend installing insulation above hatch for better energy efficiency.
|
   |
27) The furnace or boiler flame(s) are noisy (roaring) and/or "dancing" over the burner(s). This may be caused by an improper gas-air mixture flow velocity and may result in Carbon Monoxide due to incomplete combustion. A qualified heating and cooling contractor should evaluate and repair as necessary.
|
  |
28) Significant amounts of debris, dirt and/or dust are visible in one or more sections of supply and/or return air ducts. This can be a health hazard, especially for those with allergies or respiratory problems. The Environmental Protection Association (EPA) recommends considering having ducts professionally cleaned when "ducts are clogged with excessive amounts of dust and debris and/or particles are actually released into the home from your supply registers". At a minimum, the visible debris should be thoroughly cleaned. Recommend having a qualified contractor clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit: http://www.epa.gov/iaq/pubs/airduct.html
|
  |
29) The estimated useful life for air conditioning compressors is 8 to 15 years. This unit appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
|
 |
30) One or more rooms' interior doors have no gap below, or have a gap less than 3/4". As a result, return air flow out of the room is restricted with closed door(s) and the heating/cooling system on. This may result in the heating and/or cooling system having a reduced efficiency and higher energy costs. To allow adequate return air flow, recommend either trimming the bases of doors as necessary to maintain a 3/4" gap below, or leaving doors open while the heating or cooling system is in operation.
|
  |
31) The last service date of this system appears to be more than two years ago. A qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed every few years in the future, or as per the contractor's recommendations.
|
 |
32) The cooling fins on the air handler's evaporator coils are dirty. This may result in reduced efficiency and higher energy costs. Some sources claim that energy efficiency is degraded by about five percent each year as the coils get dirtier due to accumulated dust and grime. A qualified heating and cooling contractor should clean the evaporator coils as necessary.
|
  |
33) The clothes dryer is equipped with a vinyl or foil, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, see http://www.cpsc.gov/CPSCPUB/PUBS/5022.html
|
  |
34) Some, most, or all of the water supply pipes in this structure are made of galvanized steel. Based on the age of this structure, these pipes may be nearing or may have exceeded their estimated useful life of 40 to 60 years. Internal corrosion and rust can reduce the inside diameter of these pipes over time, resulting in reduced flow and eventually, leaks. The inspector performed a "functional flow test" during the inspection where multiple fixtures were run simultaneously, and found the flow to be adequate. For example, the shower flow didn't decrease substantially when the toilet was flushed. Despite this, and because of their apparent age, these pipes may need replacing at any time.
|
 |
35) The laundry sink is not anchored to the wall or floor. A qualified contractor should securely anchor the sink to the wall and/or floor to prevent damage to and leaks in the water supply and/or drain pipes due to the sink being moved.
|
 |
36) The clothes washer had clothing in it and was not operated during this inspection. The inspector was unable to fully evaluate the washer and its drain line.
|
  |
37) The masonry chimney crown is deteriorated (cracked or broken) and needs repairs or replacement. The crown is meant to keep water off of the chimney structure. The chimney can be damaged by wet masonry going through freeze-thaw cycles. A properly constructed chimney crown should:
Be constructed using either pre-cast concrete slabs, cast-in-place steel reinforced concrete, solid stone, or metal Be sloped down from the flue a minimum of 3 inches of fall per foot of run Extend a minimum of 2-1/2 inches beyond the face of the chimney on all sides Not directly contact the flue liner (if installed), and this gap should be filled with flexible caulk Have flashing installed between the bottom of the crown and the top of the brick chimney
A qualified chimney service contractor or mason should evaluate and repair or replace the crown as necessary.
|
 |
38) The chimney flue does not have a rainproof cover installed. It prevent the following:
Rainwater entering flues and mixing with combustion deposits, creating caustic chemicals which can corrode flues Rainwater entering flues and causing damage to terracotta flue tiles from freeze-thaw cycles
A qualified chimney service contractor should install a rainproof cover where missing.
|
 |
39) The glass on one or more gas fireplaces and/or stoves has a hazy film. This is typically a mineral residue left from water vapor as the gas burns. It may be possible to clean this fogging by removing the glass from the fireplace and using a gas appliance ceramic glass cleaner, available through gas fireplace and stove distributors and installers. Ammonia-based products, such as common glass cleaners should not be used since they may cause damage or etching to the glass, or make the haze permanent.
It may be possible for a homeowner to remove the glass for cleaning, depending on if the instructions or manual for the fireplace are available, and if the homeowner is experienced in such repairs. Recommend consulting with a gas fireplace installation contractor for more information, or to have them do the cleaning.
|
   |
40) Some wiring is loose, unsupported, or inadequately supported. Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.
|
   |
41) Stairs are unsafe due to a non-standard configuration, such as too-high riser heights and/or too-narrow tread depths. Standard building practices call for riser heights not to exceed eight inches and tread depths to be at least nine inches but preferably 11 inches. Riser heights should not vary more than 3/8 inch on a flight of stairs. At a minimum, the client(s) should be aware of this hazard, especially when guests who are not familiar with the stairs are present. Ideally a qualified contractor should repair or replace stairs so they conform to standard building practices.
|
   |
42) Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains and/or efflorescence on the foundation or floor, water stains at bases of support posts, etc. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. The client(s) should review any disclosure statements available and ask the property owner(s) about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:
Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines) Improving perimeter grading Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.
|
   |
43) Substandard wiring was found for the under-sink food disposal. Unprotected solid-strand, non-metallic sheathed (Romex) wiring is used. The insulation can be damaged by objects coming in contact with it and/or it being repeatedly moved. This is a safety hazard due to the risk of shock and fire. Armored (BX) cable, or a flexible appliance cord with a plug end and electric outlet should be used. A qualified electrician should evaluate and repair as necessary.
|
   |
44) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
|
  |
45) The dishwasher drain line is not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The clients should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.
Also, no "air gap" is installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client(s) should consult with a qualified contractor to determine if an air gap should be installed.
|
  |
46) Ice maker is not connected to water supply.
|
   |
47) One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested with the inspector's test instrument. These devices should trip when tested with a test instrument in addition to tripping via the test buttons on the receptacles. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.
|
  |
48) Floor tiles installed in "wet" areas have gaps between them. The wooden subfloor beneath may be damaged by water intrusion. A qualified contractor should evaluate, make repairs if necessary, and replace flooring with a waterproof floor such as sheet vinyl in wet areas.
|
 |
49) One or more bathrooms with a shower do not have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
|
 |
50) Caulk is missing and/or deteriorated at one or more showers. For example, where the shower base meets the floor below and/or around the shower surround. Caulk should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to wall and floor structures.
|
 |
51) Recommend cleaning and sealing grout in countertops now and in the future as necessary to prevent staining and to improve waterproofing.
|
   |
52) Few electric receptacles and two-pronged receptacles rather than three-pronged, grounded receptacles are installed in one or more interior rooms. This can result in "octopus" wiring with extension cords. Two-prong receptacles are considered unsafe by today's standards, and limit the ability to use appliances that require a ground in these rooms. This is a safety hazard for both fire and shock. Examples of appliances that require grounded receptacles include:
Computer hardware Refrigerators Freezers Air conditioners Clothes washers Clothes dryers Dishwashers Kitchen food waste disposers Information technology equipment Sump pumps Electrical aquarium equipment Hand-held motor-operated tools Stationary and fixed motor-operated tools Light industrial motor-operated tools Hedge clippers Lawn mowers
This list is not exhaustive. A qualified electrian should evaluate and install additional receptacles and grounded receptacles as per the client(s)' needs and standard building practices.
|
  |
53) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit this article: NFPA urges replacing home smoke alarms after 10 years.
|
   |
54) Some ceiling areas in this structure have "popcorn" textured surfaces possibly installed prior to 1979. This material may contain asbestos, which is a known carcinogen and poses a health hazard. Laws were passed in the United States in 1978 prohibiting use of asbestos in residential structures, but stocks of existing materials have been known to be used for some time thereafter. The client(s) may wish to have this ceiling material tested by a qualified lab to determine if it does contain asbestos.
In most cases, when the material is intact and in good condition, keeping it encapsulated with paint and not disturbing it may reduce or effectively eliminate the health hazard. If the client wishes to remove the material, or plans to disturb it through remodeling, they should have it tested by a qualified lab and/or consult with a qualified industrial hygenist or asbestos abatement specialist. For more information, visit: http://www.cpsc.gov/CPSCPUB/PUBS/453.html
|
  |
55) The sash spring mechanism(s) in one or more windows are broken or loose. A qualified contractor or service technician should evaluate and make repairs as necessary so the window(s) operate as intended (open easily, stay open without support, close easily, etc.).
|
 |
56) Many of the windows "weep holes" were plugged. Weep holes are located at the bottom edge of a window between the window and the exterior storm. It is important these are kept open to allow airflow and prevent moisture build-up and possible wet rot.
|