Property Inspection Report

Client(s):  Happy Home Buyer
Property address:  Somewhere Vista
Anywhere, UT 84777

Real Estate Agent
Best One Ever
801-555-7777
Inspection date:  Wednesday, June 10, 2015

This report published on Sunday, March 27, 2016 9:41:14 AM MDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Garage
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows


General Information
Return to table of contents

Report number: 062015HappyHomeBuyer
Time started: 8:00 AM
Time finished: 12:15 PM
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Warm
Inspection fee: $390 with Radon
Payment method: Check
Buildings inspected: One house
Age of main building: 27 years
Source for main building age: Municipal records or property listing
Front of building faces: North
Main entrance faces: North
Occupied: Yes, Furniture or stored items were present

1) Some areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Photo
Photo 1-1
Photo
Photo 1-2

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level, Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood, Concrete
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Wood, Concrete

2) Cracks and deterioration resulting in trip hazards were found in the sidewalks. For safety reasons, recommend repairs as necessary to eliminate trip hazards.
Photo
Photo 2-1
 

3) One or more deck or porch beams were not positively secured to the support posts below. Deck or porch beams are commonly connected to support posts by "toenailing," which is inadequate. Decks and porches are subject to movement under live loads and require a positive connection between their support posts and beams. Recommend that a qualified contractor repair per standard building practices. For example, by installing metal plates, plywood gussets or dimensional lumber to connect posts and beams.

4) The patio slab outside the basement door appeared to have settled. Recommend sealing the crack between the house and slab and in the step to prevent further damage from thaw and freeze cycles.
Photo
Photo 4-1
Photo
Photo 4-2

5) Vegetation was overgrown around equipment for one or more utilities such as gas or electric meters. Vegetation should be pruned or removed as necessary to allow unobstructed access.
Photo
Photo 5-1
 

6) Wooden deck or porch surfaces were overdue for normal maintenance. Recommend that a qualified person clean and preserve as necessary. Where decks have been coated with a finish such as opaque stains or paint, it may be too difficult to strip the finish and apply anything but paint or opaque stain. Where transparent stain or penetrating oil has been applied in the past, recommend that a penetrating oil be used. For more information, visit:
http://www.google.com/search?q=penetrating+oil+decks
http://www.google.com/search?q=deck+maintenance
Photo
Photo 6-1
Photo
Photo 6-2

7) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway.
Photo
Photo 7-1
 

8)   The gate on the west side of the house was difficult to open and close.
Photo
Photo 8-1
Photo
Photo 8-2

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Stucco, Vinyl, Stone or faux stone veneer, Metal
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Finished basement
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Not visible

9) The rock wall behind the BBQ grill was smoke damaged.
Photo
Photo 9-1
 

10) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 10-1
 

11) Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.
Photo
Photo 11-1
 

12) The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture. Recommend that a qualified person prep (e.g. clean, scrape, sand, prime, caulk) and repaint or re-stain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 12-1
 

Basement
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal, Glass panel
Condition of floor substructure above the basement.: Appeared serviceable
Pier or support post material: Bearing wall
Beam material: Built-up wood
Floor structure: Solid wood joists
Condition of insulation underneath floor above: Appeared serviceable
Insulation material underneath floor above: Fiberglass roll or batt

13)   The shrinkage cracks were found in the basement floor. Recommend sealing with an epoxy grout
Photo
Photo 13-1
 

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Partially traversed, Viewed from ground with binoculars
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable

14) Some composition shingles had minor damage. Areas shown in the photos are visible from the master bedroom SW window.
Photo
Photo 14-1
Photo
Photo 14-2

15) Debris had accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. Recommend cleaning gutters and downspouts now and as necessary in the future.
Photo
Photo 15-1
 

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch.
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): R-19, Estimated
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Box vents (roof jacks), Open soffit vents, Mechanical vents with powered fan

Garage
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached, Garage
Condition of garage: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Type of door between garage and house: Metal
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Roll
Number of vehicle doors: 1
Condition of automatic opener(s): Serviceable, required repairs, replacement and/or evaluation (see comments below)
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Window only

16) The auto-reverse mechanism on the automatic opener for the garage vehicle door required excessive force. This is a potential safety hazard. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
http://www.cpsc.gov/cpscpub/pubs/523.html
Photo
Photo 16-1
 

17) The door between the garage and the house did not have self closing hinges. This is a potential safety hazard. Such doors should close automatically to provide limited fire resistance and prevent fire from spreading from the garage to the house. Recommend installing self-closing hinges.

18) Gaps were found below or around one or more garage vehicle doors. Weather strip was missing or damaged. Vermin and insects can enter the garage as a result. Recommend that a qualified person repair as necessary to eliminate or minimize gaps.
Photo
Photo 18-1
Photo
Photo 18-2

19) The man door for the garage dead bolt was keyed inside. Just a reminder to ask the sellers for keys when closing.

20) A section of the ceiling sheetrock had previously been cut out and re-installed. This area may provide access to repair plumbing leaks in the master bathroom.
Photo
Photo 20-1
 

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide detectors is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide detectors should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 125
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 125
System ground: Undetermined, not visible
Condition of main service panel: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of sub: Appeared serviceable
Location of main service panel #A: Building exterior
Location of sub-panel #B: Basement stairway
Location of sub-panel #C: Shop
Location of main disconnect: At main disconnect panel outside
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Smoke alarms installed: Yes, Responded to testing
Carbon monoxide alarms installed: No, recommend install

21) One or more electric receptacles (outlets) at the garage and/or exterior had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/099.pdf
Photo
Photo 21-1
Photo
Photo 21-2

22) Some of the electric receptacles (outlets) in the garage were incorrectly wired with "false grounds" where the receptacle's ground screw is connected to the neutral or white wire or the ground wire is not attached. Such receptacles may appear to be grounded when they aren't. This is a shock hazard, and can damage equipment plugged into such receptacles. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.google.com/search?q=false+ground
Photo
Photo 22-1
 

23) The inside cover was missing at the outside breaker box.
Photo
Photo 23-1
 

24) One or more knockouts were missing from the outside panel. Holes in panels are a potential fire hazard if a malfunction ever occurs inside the panel. Wasps had entered the panel through holes. Recommend that a qualified person install knockout covers where missing and per standard building practices.
Photo
Photo 24-1
Photo
Photo 24-2

25) No carbon monoxide alarms were visible. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

26) One or more cover plates for switches, receptacles (outlets) or junction boxes in the shop were missing. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 26-1
Photo
Photo 26-2

27) The service light in the attic needed to be replaced or re-secured to the box above.
Photo
Photo 27-1
 

28) The ground fault circuit interrupter (GFCI) receptacle (outlet) was energized when tripped in the upstairs hallway bathroom . This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.
Photo
Photo 28-1
 

29) The legend for circuit breakers or fuses in panels B and C was missing, incomplete, illegible or confusing. This is a potential shock or fire hazard in the event of an emergency when power needs to be turned off. Recommend correcting the legend so it's accurate, complete and legible. Evaluation by a qualified electrician may be necessary.
Photo
Photo 29-1
 

30)   Breaker boxes appeared serviceable.
Photo
Photo 30-1
Photo
Photo 30-2
Photo
Photo 30-3
Photo
Photo 30-4

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, sprinklers, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Location of main water shut-off: Basement, Laundry room
Water service: Public
Water pressure (psi): 58 PSI
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, PEX plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic, Brass
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Condition of fuel system: Appeared serviceable
Location of main fuel shut-off valve: At gas meter

31) The main water shut off was in the basement kitchen and laundry area.
Photo
Photo 31-1
 

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Type: Tank
Energy source: Natural gas
Estimated age: 4 years
Capacity (in gallons): 40
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 140
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable

32) The water heater did not have earthquake straps or struts installed. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines breaking if it's gas-fired, or electric wiring being damaged if powered by electricity. Leaks can also occur in water-supply pipes. Recommend that a qualified person install earthquake straps or struts as necessary and per standard building practices.
Photo
Photo 32-1
 

33) No drain line was installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. Recommend that a qualified plumber install a drain line per standard building practices.
Photo
Photo 33-1
 

34) The hot water temperature was greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. If the water heater is powered by electricity, a qualified person should perform the adjustment, since covers that expose energized equipment normally need to be removed. For more information on scalding dangers, visit:
http://www.cpsc.gov/CPSCPUB/PUBS/5098.pdf

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: 6/22/2007
Source for last service date of primary heat source: Label
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 8 years
Location of forced air furnace: Basement
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location: Furnace and exterior
Type: Split system
Condition of controls: Appeared serviceable

35) Because of the age and/or condition of the forced air furnace, recommend that a qualified HVAC contractor inspect the heat exchanger and perform a carbon monoxide test when it's serviced. Note that these tests are beyond the scope of a standard home inspection.
Photo
Photo 35-1
 

36) A rust spot was present under the connection for the condensate line at the base of the furnace. It did not appear to be leaking at the time of the inspection. Recommend monitoring this area in the future and making repairs if needed.
Photo
Photo 36-1
 

37) The whole house fan was controlled by a thermostat. Because of the ambient temperature at the time of the inspection and/or the thermostat controls, the inspector was unable to evaluate the whole house fan. It is excluded from this inspection.

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Masonry
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Masonry, with metal liner

38) One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.csia.org/

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop: Appeared serviceable
Range, cooktop type: Natural gas, Electric
Condition of refrigerator: Appeared serviceable
Condition of built in microwave.: Appeared serviceable

39) Knobs were missing from the washer/dryer area's cover in the basement. Recommend installing.
Photo
Photo 39-1
 

40) The ice maker was in the off position. Property owners said it worked but they don't use it.
Photo
Photo 40-1
 

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Condition of counters: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Required repair, replacement and/or evaluation (see comments below)
Gas supply for laundry equipment present: Yes, upstairs
240 volt receptacle for laundry equipment present: Yes, Downstairs

41) The toilet in themain floor bathroom was loose where it attached to the floor. Leaks can occur. Flooring, the subfloor or areas below may get damaged. Sewer gases can enter living spaces. Recommend that a qualified contractor remove the toilet(s) for further evaluation and repair if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
Photo
Photo 41-1
 

42) The bathtub surround at Master bathroom was deteriorated, damaged or substandard. Water can damage the wall structure as a result. Recommend that a qualified contractor replace or repair the surround as necessary.
Photo
Photo 42-1
Photo
Photo 42-2

43) The shower enclosure at the main floor bathroom was deteriorated, damaged or substandard. Water can damage the wall structure as a result. Recommend that a qualified contractor repair or replace the surround as necessary.
Photo
Photo 43-1
 

44) None of the bathrooms had an exhaust fan installed. Moisture can accumulate and result in mold, bacteria or fungal growth. Even if the bathroom has a window that opens, it may not provide adequate ventilation, especially during cold weather when windows are closed or when wind blows air into the bathroom. Recommend that a qualified contractor install exhaust fans per standard building practices where missing in bathrooms with showers or bathtubs.
Photo
Photo 44-1
Photo
Photo 44-2

45) Elevated levels of moisture were found in the ceiling area of the main floor bathroom. Tub in the master above may be leaking at the drain.
Photo
Photo 45-1
Photo
Photo 45-2

46) The dryer vent for the main floor laundry should be extended to vent outside the garage. The basement dryer vent exits the basement on the west side of the house.
Photo
Photo 46-1
Photo
Photo 46-2

47) The sink in the main floor bathroom drained slowly. Recommend clearing drain and/or having a qualified plumber repair if necessary.
Photo
Photo 47-1
 

48) Damage and elevated moisture levels were found between the shower enclosure and the walls in the downstairs bathroom. Recommend that a qualified person repair wall after the cause of the moisture is eliminated.
Photo
Photo 48-1
Photo
Photo 48-2

49) Gaps, no caulk, or substandard caulking were found between the bathtub and the walls in the upstairs hallway bathroom. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo
Photo 49-1
 

50) The basement bathroom door binds in the jamb.
Photo
Photo 50-1
 

51) Recommend cleaning and sealing the grout at countertops in the upstairs hallway bathroom now and in the future as necessary to prevent staining and to improve waterproofing.
Photo
Photo 51-1
Photo
Photo 51-2

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood, Metal, Glass panel
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Multi-pane, Sliding, Single-hung, Casement, Fixed
Condition of walls and ceilings: Appeared serviceable, Required repairs, replacement and/or evaluation (see comments below)
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Wood or wood products, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable

52) Door stops were missing from some interior doors. Walls could be damaged as a result.
Photo
Photo 52-1
 

53) The front exterior door was difficult to open or close. Weather strip was missing. Recommend that a qualified person repair as necessary.
Photo
Photo 53-1
Photo
Photo 53-2

54) One or more windows that were designed to open and close were stuck shut. ( crank handles missing, lock mechanism that would not release). Recommend that a qualified person repair windows as necessary so they open and close easily.
Photo
Photo 54-1
Photo
Photo 54-2

55) One or more window screens were damaged or missing. These window(s) may not provide ventilation during months when insects are active. Recommend replacing window screens as necessary.
Photo
Photo 55-1
Photo
Photo 55-2

56) One or more walls were damaged and wallpaper was peeling off. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 56-1
Photo
Photo 56-2
Photo
Photo 56-3
Photo
Photo 56-4

57) Carpeting in one or more areas was damaged or deteriorated. Recommend that a qualified contractor replace as necessary.
Photo
Photo 57-1
Photo
Photo 57-2

58) Staining was found in the window seal at the north end of the master bedroom.
Photo
Photo 58-1
 

59) Recommend caulking aroun the inside of windows where cracks are present.
Photo
Photo 59-1
Photo
Photo 59-2

60) Minor damage was found on one or more exterior doors.
Photo
Photo 60-1
Photo
Photo 60-2

61) Carpeting in one or more areas was soiled. Recommend having carpeting professionally cleaned.

62) Floors were squeaky in some areas.
Photo
Photo 62-1
 