Owens / Silver Leaf Inspection |
| Client(s): |
Mike & Sandra Owens |
| Property address: |
451 Siver Leaf Drive Oroville, Ca. 95966 |
| Inspection date: |
Tuesday, August 26, 2008 |
This report published on 8/26/2008 7:13:12 PM PDT
View summary page
NOTE:
The findings and recommendations contained in this report are based on the newest and most up to date construction and safety standards in the industry. Some deficiencies may not have been recognized as such at the time the structure was built or remodeled. Other deficiencies are aimed at energy efficiency or air quality, and are not required building restrictions or practices. Look First Inspections is not a specialist in code compliance or zoning restrictions, and no part of the report should be considered as required repair and/or replacement.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types: | Safety | Poses a risk of injury or death |
 | Repair/Replace | Recommend repairing or replacing |
 | Repair/Maintain | Recommend repair and/or maintenance |
 | Minor Defect | Correction likely involves only a minor expense |
 | Maintain | Recommend ongoing maintenance |
 | Evaluate | Recommend evaluation by a specialist |
 | Monitor | Recommend monitoring in the future |
 | Serviceable | Item or component is in servicable condition |
 | Comment | For your information |
Structural Pest Inspection Concerns
Items of concern relating to the structural pest inspection are shown as follows:
 | WDO/WDI Infestation | Evidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) |
 | WDO/WDI Damage | Damage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) |
 | WDO/WDI Conducive conditions | Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) |
Click here for a glossary of building construction terms.
Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp
Table of Contents
General Information
Grounds
Exterior / Foundation
Roof / Attic
Garage / Carport
Electric
Plumbing / Fuel Systems
Water Heater #1 - Main
Water Heater #2 - Subsidiary
Heating
Cooling / Heat Pump
Fireplaces / Stoves / Chimneys
Kitchen
Bathrooms / Laundry / Sinks
Interior Rooms / Areas
Report number: 1147
Time started: 10:00 am
Time finished: 12:45 pm
Client present for discussion at end of inspection: No
Weather conditions: Clear
Temperature: Warm
Ground condition: Dry
Type of building: Manufactured home
Age of building(s): 28 years
Source for building age: Realtor
Front of building faces: West
Occupied: No
1)

Evidence of rodent infestation was found in the form of feces, urine stains, poison in one or more areas including the interior rooms, (kitchen). Recommend consulting with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.cdc.gov/rodents/prevent_rodents/seal_up.htm
http://www.cdc.gov/rodents/prevent_rodents/trap_up.htm
http://www.cdc.gov/rodents/prevent_rodents/clean_up.htm

Photo 60
Kitchen, below sink
|
|
Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
Condition of retaining walls: Appeared serviceable
Retaining wall material: Rock
Site profile: Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared serviceable
Condition of guardrails: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood
Condition of exterior stairs: Appeared serviceable
Condition of handrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Wood
2)

Handrails at one or more flights of stairs were loose. This is a safety hazard. A qualified person should repair or replace as necessary and as per standard building practices.

Photo 19
Front deck stairs
|
|
3)

Guardrails in some areas with drop-offs higher than 30 inches were missing, with gaps over 4. This is a safety hazard. Standard building practices require that they:
Be installed at drop-offs higher than 30 inches
Be securely and permanently attached
Be at least 36 inches in height
Not be climbable by children
Not have gaps or voids that allow passage of a sphere equal to or greater than four inches in diameter
A qualified contractor should evaluate and repair, replace or install guardrails as necessary, and as per standard building practices.

Photo 10
Master bedroom deck
|

Photo 22
NW corner of front deck
|
4)

One or more retaining walls higher than three feet were found on this property and guardrails or barriers were missing. This is a safety hazard due to the risk of falling. At a minimum, the client should be aware of this hazard, especially when children are present. Ideally a qualified contractor should install adequate guardrails or make modifications to existing barriers as necessary above retaining walls higher than 3 feet to eliminate fall hazards. Dense shrubbery or vegetation may be acceptable as a barrier, but only when mature enough to be effective.

Photo 34
West side
|
|
5)
One or more wood spacers in the East side patio/walkway were rotten or damaged by unspecified wood destroying insects. These spacers typically fill expansion joints that are meant to prevent the concrete slabs from breaking. Recommend replacing wood spacers as necessary with a rot and insect resistant material that compresses and expands, such as treated wood.

Photo 35
East side
|
|
6)
Soil was in contact with or too close to wooden support posts. This is a conducive condition for wood destroying insects and organisms. Standard building practices require the following clearances to soil below:
12 inches between beams and the soil below
18 inches between joists and the soil below
6 inches between support post bases and the soil below
Not in contact with any wood
Efforts should be made, such as grading and/or removing soil, to maintain these clearances. If this is not practical, then installing borate based Impel rods may help to prevent infestation and damage. For more information, visit:
http://www.ewoodcare.com/products/borates_preserve/impel_rods.html

Photo 36
Under front deck
|
|
7)
Trees were in contact with or were close to the building in one or more areas. Damage may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.

Photo 11
NW corner
|

Photo 26
Shed/shop
|
8)
Minor cracks, settlement, heaving and/or deterioration were found in the driveway and sidewalks. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of wall covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Wood fiber, Vinyl
Condition of foundation and footings: Appeared serviceable
Foundation type: Crawlspace
Foundation material: Steel frame on concrete block piers
Footing material: None
Tie downs for seismic reinforcement installed: Yes (but not evaluated, the inspector is not a licensed engineer)
Condition of floor substructure: Appeared serviceable
Pier or support post material: Masonry, Steel
Beam material: Steel
Floor structure: Not determined
Condition of crawl space: Required repair and/or evaluation (see comments below)
Crawl space inspection method: Traversed
Insulation material underneath floor above: Fiberglass roll or batt
Ventilation: Appears serviceable
Vapor barrier present: No
9)
Caulk was missing around doors. A qualified person should repair or replace as necessary. For more information, visit:
http://www.reporthost.com/_docs/FPL_Caulking_Ins_Outs.pdf

Photo 28
Master bedroom slider
|

Photo 29
Master bedroom slider
|
10)

Some sections of siding and/or trim were deteriorated. A qualified person should evaluate and repair, replace or install as necessary.

Photo 15
West side
|
|
11)
Soil was in contact with or less than six inches from siding and/or trim. This is a conducive condition for wood destroying insects and organisms. Soil should be graded and/or removed as necessary so there are at least six inches of space between the siding and trim and the soil below.

Photo 38
Under front deck
|

Photo 39
Under front deck
|
12)
Flashing in one or more areas was missing, loose. Leaks may occur as a result. A qualified person should evaluate and repair, replace or install as necessary, and as per standard building practices.

Photo 7
NE corner
|

Photo 27
NW corner outside master bedroom
|

Photo 77
North side of front entry door
|
|
13)
Scrap wood was found in the crawl space. All cellulose-based debris or stored items should be removed to avoid attracting wood destroying insects.
NOTE: Under front deck

Photo 40
Under front deck
|
|
14)
One or more exhaust fan ducts in the crawl space were loose, damaged. This is a conducive condition for wood destroying insects and organisms due to increased moisture levels in the attic from the exhaust air. A qualified person should evaluate and make permanent repairs as necessary and as per standard building practices, so all exhaust air is vented outside.

Photo 74
|

Photo 75
|
15)
One or more exhaust duct end caps were deteriorated. Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and may pose a fire hazard. A qualified person should evaluate and repair as necessary.

Photo 8
East side
|
|
16)
The crawl space access hatch was missing. A qualified person should repair, replace or install as necessary to prevent water and vermin intrusion.
NOTE: Under front deck

Photo 76
NW corner of front deck
|
|
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
Condition of roof structure: Required repair, replacement and/or evaluation (see comments below)
Roof type: Gable
Roof inspection method: Traversed
Condition of metal and/or tile roof surface materials: Required repair, replacement and/or evaluation (see comments below)
Metal, tile or panel roof surface material: Metal
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
Gutter and downspout material: Metal, Plastic
Gutter and downspout installation: Full
Roof structure type: Not determined
Ceiling insulation material: Not determined
Roof ventilation: Appears serviceable
17)

The roof structure needed repair in one or more areas due to the following conditions: damage. A qualified contractor should evaluate and repair as necessary, and as per standard building practices.

Photo 46
Above water heater enclosure (roof surface)
|

Photo 48
Above water heater enclosure (interior)
|
18)
One or more sections of metal roofing had a failing paint/sealant finish. For example, peeling and/or missing paint. A qualified contractor should repaint/reseal metal panels where necessary.

Photo 42
Above kitchen
|
|
19)

Some gutters, downspouts were loose, damaged. Water may accumulate around the building foundation as a result. A qualified person should evaluate and repair as necessary.

Photo 13
West
|

Photo 14
NW corner of front deck
|

Photo 18
SW corner
|

Photo 23
SW corner
|
20)
Extensions such as splashblocks or drain pipes for some downspouts were damaged. Water may accumulate around the building foundation as a result. A qualified person should evaluate and repair, replace or install as necessary

Photo 16
SW corner
|
|
21)

One or more roof surface sections were designed so as to be much more likely to accumulate debris and snow. This includes the following: two slopes converge. Leaks may occur as a result. The client should monitor such areas for accumulated debris in the future and clean as necessary.

Photo 44
Master bedroom addition
|
|
22)
Debris had accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the building exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

Photo 45
|

Photo 47
Front deck cover
|
23)
Debris such as leaves, needles, seeds, etc. had accumulated on the roof. This is a conducive condition for wood destroying insects and organisms since water may not flow easily off the roof, and may enter gaps in the roof surface. Leaks may occur as a result. Debris should be cleaned from the roof now and as necessary in the future.

Photo 43
Carport
|
|
24)
Trees were overhanging roof and were within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.

Photo 41
East side
|
|
25)
No accessible attic spaces were found or inspected at this property.
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages varies between municipalities.
Type: Attached carport
Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120/240
Service amperage (amps): 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Unable to determine
Main disconnect rating (amps): 200
System ground: Cold water supply pipes
Condition of main service panel: Appeared serviceable
Condition of sub: Appeared serviceable
Location of main service panel #A: Building exterior, East side
Location of sub panel #B: East bedroom closet
Location of sub panel #C: Master bedroom
Location of other panels: Front deck (for hot tub/spa), by A/C unit, by furnace.
Location of main disconnect: At main disconnect panel outside
Branch circuit wiring type: Nonmetallic sheathed
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Solid strand aluminum branch circuit wiring present: None visible
Condition of smoke detectors: Required repair, replacement and/or evaluation (see comments below)
Smoke detectors present: Yes
Carbon monoxide detectors present: No
Smoke detector power source: Not determined
26)

One or more clamps that secure the electric service's grounding electrode conductor(s) to a water pipe were loose. Grounding may be substandard as a result and may be a safety hazard for shock. A qualified electrician should evaluate and repair as necessary.

Photo 56
East side by electric meter
|
|
27)

Wire splices were exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

Photo 24
Shed/shop
|

Photo 25
Shed/shop
|
28)

Some receptacle boxes were loose. This is a potential safety hazard for shock or fire. A qualified person should evaluate and repair as necessary.

Photo 20
Front deck by front entry door
|

Photo 33
Water heater enclosure
|
29)

Some electric receptacles had reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

Photo 20
Front deck by front entry door
|
|
30)

Smoke detectors were missing from bedrooms. Additional smoke detectors should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, in each bedroom, and one each level of the building. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
31)

This property had one or more fuel burning appliances and/or an attached garage, and no carbon monoxide detectors were visible. This is a safety hazard. Recommend installing one or more carbon monoxide detectors as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
32)

One or more electric receptacles at the following "wet" locations appeared to have no ground fault circuit interrupter (GFCI) protection: kitchen, wet bar. This is a safety hazard due to the risk of shock. A recommended upgrade would be to have a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf

Photo 53
Wet bar
|

Photo 54
Kitchen
|

Photo 55
Kitchen
|
|
33)
One or more lamp covers were missing and should be replaced as necessary.

Photo 57
Kitchen, above sink
|
|
34)
Some light fixtures were inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner. Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.

Photo 52
China cabinet
|
|
Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Location of main water meter: At street
Location of main water shut: East side
Service pipe material: Galvanized steel
Condition of supply lines: Required repair, replacement and/or evaluation (see comments below)
Supply pipe material: Galvanized steel, CPVC
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
35)

One or more outside faucets were missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the building. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.
Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079
36)
Water supply lines were routed outside and are subject to freezing. Pipe wrap or foam sleeves are inexpensive and easily installed. Recommend insulating pipes as necessary to prevent pipes from freezing and bursting.

Photo 2
South side
|

Photo 3
East side
|

Photo 6
North side
|

Photo 17
SW corner
|

Photo 37
Under front deck
|
|
37)

Minor flow restriction was found at one or more sinks, bathtubs, showers when multiple fixtures were operated at the same time. A qualified plumber should evaluate and repair if necessary.
38)
Recommend having the septic tank inspected. Recommend having the tank pumped if it was last pumped more than 3 years ago.
Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Required repair, replacement and/or evaluation (see comments below)
Type: Tank
Estimated age: 2 years
Energy source: Electricity
Capacity (in gallons): 40
Manufacturer: Whirlpool
Model: EE2H40RD045V, ser# 0624127093
Location of water heater: NE corner in closet w/ exterior access
39)

The water heater did not have seismic straps or struts installed. This is a potential safety hazard. Leaks may also occur in water supply pipes. A qualified person should install seismic straps or struts as necessary and as per standard building practices.

Photo 31
Main water heater
|
|
40)

No drain line was installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.

Photo 30
Main water heater
|
|
41)
The water heater enclosure door or hardware was deteriorated. Recommend that a qualified person evaluate and repair or replace as necessary.

Photo 32
|
|
Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Required repair, replacement and/or evaluation (see comments below)
Type: Tank
Estimated age: 7 years
Energy source: Electricity
Capacity (in gallons): 6
Manufacturer: General Electric
Model: GE6P6A, ser# 0701228938
Location of water heater: Under kitchen sink
42)

The water heater did not have seismic straps or struts installed. This is a potential safety hazard. Leaks may also occur in water supply pipes. A qualified person should install seismic straps or struts as necessary and as per standard building practices.
43)

No drain line was installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.

Photo 61
Subsidiary water heater, under kitchen sink
|
|
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
Condition of heating system: Appeared serviceable
Location of heating system: Closet, North side, exterior access
Heating type: Forced air
Fuel type: Electric
Model: F2FPO48NO6B, ser# XBMS040040
Condition of distribution system: Appeared serviceable
Distribution system: Ducts and registers
Condition of controls: Appeared serviceable
Condition of air filters: Appeared serviceable
Location of air filters: At base of air handler
44)

One or more air supply registers were damaged and should be replaced where necessary.
NOTE: These registers appear to be abandoned. However, they pose a possible trip hazard.

Photo 49
East bedroom
|

Photo 51
Living room in front of china cabinet
|
45)
Filters should be checked monthly and maintained as necessary in the future.
Limitations: The following items are not included in this inspection: evaporative coolers, humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Required repair, replacement and/or evaluation (see comments below)
Type: Heat pump
Estimated age: 5 years
Manufacturer: Coleman
Condition of controls: Appeared serviceable
46)
Insulation for the outside condensing unit's refrigerant lines was loose, deteriorated in areas. This may result in reduced efficiency and increased energy costs. A qualified person should replace insulation as necessary.

Photo 4
By A/C unit
|

Photo 5
By A/C unit
|
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, nor determine if prefabricated or zero clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit.
Condition of fireplaces, stoves: Appeared serviceable
Location #A: Family Room
Stove type: Freestanding
Fuel type: Pellets
Condition of chimneys: Required repair, replacement and/or evaluation (see comments below)
Chimney type: Metal
47)


The solid fuel burning appliance chimney at location # A terminated improperly and may result in drafting problems. Standard building practices require the following clearances for chimney terminations:
At least 3 feet above the roof surface below
At least 2 feet above all roof surfaces within 10 feet from the chimney
At least 2 additional feet beyond the requirement in the second rule above if the roof ridge is more than 10 feet from the chimney
A qualified contractor should evaluate and make repairs or modifications as necessary.

Photo 12
Pellet stove chimney
|
|
48)
All solid fuel burning appliances (woodstoves and fireplaces, etc.) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
Condition of counters: Appeared serviceable
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Appeared serviceable
Condition of garbage disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop: Appeared serviceable
Range, cooktop type: Electric
Condition of refrigerator: Appeared serviceable
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
49)
Some cabinet surfaces, drawers, dividers and/or doors showed minor wear, damage.

Photo 58
Kitchen
|

Photo 59
Kitchen, NW corner
|
50)
Stains were found in the shelving or cabinet components below one or more sinks. Plumbing leaks may have occurred in the past. Recommend consulting with the property owner about this, and if necessary, having a qualified person evaluate and repair.
51)
The following appliances were not fully evaluated because of the following condition(s): electricity supply turned off. Appliances not fully evaluated: trash compactor.
52)
Some counters showed minor wear.
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Off utility room
Location #B: Off master bedroom
Condition of counters: Required repair, replacement and/or evaluation (see comments below)
Condition of cabinets: Required repair, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Condition of laundry facilities: Required repair, replacement and/or evaluation (see comments below)
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes
53)

The clothes dryer was equipped with a vinyl, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, visit:
http://www.cpsc.gov/CPSCPUB/PUBS/5022.html

Photo 50
|
|
54)

The clothes dryer exhaust duct was too long, or had too many bends. This may reduce the air flow through the duct, resulting in overheating, reduced efficiency and/or difficulty in cleaning the duct. Standard building practices limit clothes dryer exhaust ducts to 25 feet, and less when bends are present (2.5 feet for each 45-degree bend and 5 feet for each 90-degree bend). A qualified contractor should evaluate and repair as necessary, and as per standard building practices.

Photo 73
|
|
55)
Caulk was deteriorated at location #A, B. A qualified person should repair as necessary.

Photo 62
Guest bathroom
|

Photo 63
Master bathroom
|
56)

The sink at location #B drained slowly. A qualified person should evaluate and repair as necessary.
57)
Drawers were damaged in one or more cabinets at location #B. A qualified person should evaluate and repair as necessary.

Photo 64
Master bathroom
|
|
58)
Cabinet surfaces, drawers and/or doors showed minor wear at location #A, B.
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
Exterior door material: Fiberglass or vinyl, Sliding glass
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Condition of interior doors: Required repair, replacement and/or evaluation (see comments below)
Type of windows: Aluminum
Condition of windows: Appeared serviceable
Wall type or covering: Drywall, Paneling, Wallpaper
Condition of walls: Appeared serviceable
Ceiling type or covering: Drywall, Ceiling tiles
Condition of ceilings: Appeared serviceable
Flooring type or covering: Carpet, Vinyl, Tile
Condition of flooring: Required repairs, replacement and/or evaluation (see comments below)
59)


Thresholds at one or more exterior doors are non standard, and pose a possible trip hazard . At a minimum, the client should be aware of this hazard, especially when guests who are not familiar with this condition are present. Ideally a qualified contractor should evaluate and repair as necessary, and as per standard building practices.

Photo 66
Master bedroom slider threshold
|
|
60)

Vinyl flooring in one or more "wet" areas was damaged or deteriorated, had gaps between tiles. As a result, the wooden subfloor beneath may become damaged by water intrusion. A qualified contractor should repair or replace flooring as necessary.

Photo 71
kitchen floor
|

Photo 72
kitchen floor
|
61)
Trim or jambs around one or more interior doors was missing. A qualified person should repair, replace or install as necessary.

Photo 65
Master bathroom door jamb
|
|
62)
Screens in one or more exterior doors were damaged. A qualified person should replace screens where necessary.

Photo 9
Carport entry door
|
|
63)
The lock mechanisms on one or more sliding glass doors were difficult to operate. A qualified person should repair or replace as necessary.

Photo 69
Master bedroom slider
|
|
64)
The front door's doorbell appeared to be inoperable. A qualified person should evaluate and repair as necessary.

Photo 21
|
|
65)
Some interior doors wouldn't latch, were difficult to latch. A qualified person should evaluate and repair as necessary.

Photo 67
Master bedroom door
|

Photo 68
Master bathroom door
|
66)
Minor cracks and/or holes were found in walls and ceilings in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
67)
Carpeting in areas was damaged. A qualified contractor should replace as necessary

Photo 70
By kitchen
|
|
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.Look First Inspections requires an inspection agreement to be signed by Client prior to performing an inspection. If you were not present at the inspection and did not sign the Inspection Agreement you, by accepting, paying for, and/or using the inspection report you acknowledge and agree to be bound by the terms and conditions of the inspection agreement and further agree that the Inspection Agreement will form part of the inspection report.