Summary Page

Cox / Myrtle Inspection
Client(s): Dan Cox
Property address: 54 Myrtle Drive
Oroville, Ca. 95966
Inspection date: Thursday, October 23, 2008

This summary page published on 10/23/2008 11:41:32 PM PDT

Return to report

Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
ServiceableItem or component is in servicable condition 
CommentFor your information 
 
WDO/WDI InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
WDO/WDI DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
WDO/WDI Conducive
conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

1) General Information:   - Structures built prior to 1980 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.epa.gov
http://www.cpsc.gov
http://www.cdc.gov

2) Grounds:   - One or more deck, patio and/or porch covers were unstable due to substandard bracing, lack of diagonal bracing, or lack of attachment to the main building. This is a safety hazard since severe movement may cause the cover to collapse. A qualified contractor should evaluate and repair as necessary.

3) Grounds:   - Stairs were unsafe due to the following non standard configuration: risers too high. Standard building practices require that:

  • Riser heights not vary by more than 3/8 inch on one flight of stairs
  • Risers should not exceed eight inches in height
  • Treads should be at least nine inches deep, but preferably 11 inches deep
  • Minimum stairway width is 36 inches (although 30 inches is common in older homes)
  • Minimum overhead clearance at stairs is six feet eight inches

    At a minimum, the client should be aware of this hazard, especially when guests who are not familiar with the stairs are present. Ideally a qualified contractor should evaluate and repair as necessary, and as per standard building practices.
    4) Grounds: - Soil was in contact with or too close to wooden beams. This is a conducive condition for wood destroying insects and organisms. Standard building practices require the following clearances to soil below:

  • 12 inches between beams and the soil below
  • 18 inches between joists and the soil below
  • 6 inches between support post bases and the soil below
  • Not in contact with any wood

    Efforts should be made, such as grading and/or removing soil, to maintain these clearances. If this is not practical, then installing borate based Impel rods may help to prevent infestation and damage. For more information, visit:
    http://www.ewoodcare.com/products/borates_preserve/impel_rods.html
    8) Exterior / Foundation:   - One or more pier or foundation footings were undermined, where soil has either eroded out from underneath, or has been excavated too close to the footing. Standard building practices typically require undisturbed soil to extend at least a foot horizontally out from the edge of footings, and then slope down no more steeply than 45 degrees. Otherwise soil may collapse from beneath the footing(s). A qualified contractor or engineer should evaluate and determine what repairs if any should be made. A qualified contractor should perform any repairs that may be needed.

    9) Exterior / Foundation: - Soil was in contact with or less than six inches from siding and/or trim. This is a conducive condition for wood destroying insects and organisms. Soil should be graded and/or removed as necessary so there are at least six inches of space between the siding and trim and the soil below.

    10) Exterior / Foundation: - One or more minor cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks including hydraulic cement, resilient caulks and epoxy sealants.

    11) Exterior / Foundation:   - The floor substructure was damaged in one or more areas. A qualified contractor should evaluate and repair as necessary, and as per standard building practices.

    NOTE: Pier block cracked

    12) Exterior / Foundation: - Rot or water damage was found at one or more sections of rafter tails. A qualified person should evaluate and repair as necessary. All rotten wood should be replaced.

    NOTE: Tail was cut off and new piece toe nailed in to cover.

    13) Exterior / Foundation: - Scrap wood, Cardboard was found in the crawl space. All cellulose-based debris or stored items should be removed to avoid attracting wood destroying insects.

    14) Exterior / Foundation:   - Some sections of siding and/or trim were damaged, loose, substandard. A qualified person should evaluate and repair, replace or install as necessary.

    15) Exterior / Foundation:   - Gaps/holes existed at one or more areas around the exterior. Gaps/holes should be sealed as necessary to prevent moisture intrusion, save energy and prevent entry by vermin.

    16) Exterior / Foundation:   - The crawl space access hatch fit poorly. A qualified person should repair, replace or install as necessary to prevent water and vermin intrusion.

    NOTE: No latch

    17) Exterior / Foundation:   - Some crawl space vent screens were missing, damaged. Animals such as vermin or pets may enter the crawl space and nest, die and/or leave feces and urine. A qualified person should replace damaged or deteriorated screens where necessary using screen material such as "hardware cloth" with 1/4 inch minimum gaps.

    18) Exterior / Foundation: - Evidence of prior water intrusion was found in one or more sections of the crawl space. For example, sediment stains on the vapor barrier or foundation, and/or efflorescence on the foundation. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the crawl space. The client should review any disclosure statements available and ask the property owner about past accumulation of water in the crawl space. The crawl space should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in crawl spaces include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter crawl spaces, but if water must be controlled after it enters the crawl space, then typical repairs include installing trenches, gravity drains and/or sump pump(s) in the crawl space.
    23) Roof / Attic:   - The ceiling insulation in some areas of the attic was missing, uneven. This may result in increased heating or cooling costs due to decreased energy efficiency. A qualified person should repair, replace or install insulation as necessary. For more information, visit:
    http://www.eere.energy.gov/consumer/tips/insulation.html

    24) Roof / Attic: - The siding on one or more exterior walls above lower roof sections was in contact with or had less than a one inch gap between it and the roof surface below. A gap of at least one inch is recommended so water isn't wicked up into the siding from the shingles below, and also to provide room for additional layers of roofing materials when the current roof surface fails. Recommend having a qualified contractor make repairs as necessary, such as trimming siding, so at least a one inch gap exists between the siding and the roofing below where necessary.

    25) Roof / Attic: - Rafter and/or barge board tails are exposed. Rain run-off from the roof will likely cause rot to occur in these boards. Recommend that shingles or flashing be installed above them to prevent rot.

    26) Roof / Attic: - One or more gutters were poorly sloped so that significant amounts of water accumulate in them rather than draining through the downspouts. This can cause gutters to overflow, especially when organic debris such as leaves or needles have accumulated in them. A qualified contractor should evaluate and make repairs as necessary, such as correcting the slope in gutters or installing additional downspouts and extensions if necessary.

    27) Roof / Attic: - Extensions such as splashblocks or drain pipes for some, all downspouts were missing. Water may accumulate around the building foundation as a result. A qualified person should evaluate and repair, replace or install as necessary

    28) Roof / Attic: - One or more exhaust fan ducts in the attic were missing. This is a conducive condition for wood destroying insects and organisms due to increased moisture levels in the attic from the exhaust air. A qualified person should evaluate and make permanent repairs as necessary and as per standard building practices, so all exhaust air is vented outside.

    29) Roof / Attic:   - No insulation was installed at the attic access hatch. Recommend installing insulation at hatch for better energy efficiency. For more information, visit:
    http://www.reporthost.com/_docs/atticaccess.pdf

    30) Roof / Attic: - One or more roof surface sections were designed so as to be much more likely to accumulate debris and snow. This includes the following: two slopes converge. Leaks may occur as a result. The client should monitor such areas for accumulated debris in the future and clean as necessary.

    31) Roof / Attic: - Debris had accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the building exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

    32) Roof / Attic: - Trees were overhanging roof and were within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.

    33) Roof / Attic:   - The roof structure may need repair in one or more areas due to the following conditions: cracked or broken rafters. A qualified contractor should evaluate and repair as necessary, and as per standard building practices.

    34) Roof / Attic:   - Stains were visible on the roof structure in one or more areas. These areas were dry at the time of the inspection. The stains may be caused by a past leak. Recommend asking the property owner about past leaks. The client should monitor these areas in the future, especially after heavy rains, to determine if active leaks exist. If leaks are found, a qualified contractor should evaluate and repair as necessary.

    NOTE: Stains may predate new roof

    35) Electric:   - Panel #A was corroded. This is a safety hazard for shock and/or fire. A qualified electrician should evaluate and repair as necessary.

    36) Electric:   - Panel #A used older style, "Edison" base fuses. This type of fuse allows anyone to install incorrectly rated fuses, possibly resulting in damage to wiring. Recommend that a qualified electrician evaluate this panel and the wiring to determine if damage has occurred, and repair or replace components and/or wiring as necessary.

    37) Electric:   - Grounding at panel #A appeared to be substandard. This is a potential hazard for shock. A qualified electrician should evaluate and repair as necessary.

    38) Electric:   - Some wiring was loose, unsupported, or inadequately supported. Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.

    39) Electric:   - One or more sections of wiring that weren't terminated were found. This is a potential safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary. For example, cutting the wire to length and terminating the wire with wire nuts in a securely anchored, covered, properly sized junction box.

    40) Electric:   - One or more screws were missing from the cover to panel #A and should be replaced. Because energized wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws do not come in contact with wiring inside the panel when they are installed. Stock screws from the panel manufacturer should be used, or their equivalent.

    41) Electric:   - Many cover plates on junction boxes were missing. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. A qualified person should repair as necessary.

    42) Electric:   - One or more electric receptacles and/or the boxes they are installed in were loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.

    43) Electric:   - Some electric receptacles had reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

    44) Electric:   - Some open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

    Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.

    45) Electric:   - One or more ground fault circuit interrupter (GFCI) type receptacles were found to have an open ground. GFCI protection will still work with an open ground, but ideally repairs should be made as necessary so grounding is correct with these receptacles. A qualified electrician should evaluate and make repairs as necessary.

    46) Electric:   - One or more ground fault circuit interrupter (GFCI) electric receptacles wouldn't trip, wouldn't trip with test instrument at the following "wet" locations: bathroom(s). This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.

    47) Electric:   - Smoke detectors were missing from bedrooms. Additional smoke detectors should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, in each bedroom, and one each level of the building. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html

    48) Electric:   - This property had one or more fuel burning appliances and/or an attached garage, and no carbon monoxide detectors were visible. This is a safety hazard. Recommend installing one or more carbon monoxide detectors as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

    49) Electric:   - The legend for overcurrent protection devices (breakers or fuses) in panel #A, B was missing. Recommend installing, updating or correcting the legend as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.

    50) Electric:   - One or more electric receptacles appeared to have no power. Recommend asking the property owner about this. Switches may need to be operated to make some receptacles energized. If necessary, a qualified electrician should evaluate and make repairs as necessary.

    55) Plumbing / Fuel Systems:   - One or more outside faucets were missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the building. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

    Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079

    56) Plumbing / Fuel Systems:   - One or more sections of gas supply pipes were loose or had substandard support. Standard building practices require that gas supply piping be supported by clamps as follows:

  • Every six feet for two inch pipe
  • Every eight feet for 3/4 inch pipe
  • Every 10 feet for 1 1/4 inch pipe

    A qualified contractor should evaluate and repair as necessary, and as per standard building practices.
    57) Plumbing / Fuel Systems:   - One or more sections of waste pipes had a substandard slope. Clogging or leaks may occur as a result. Standard building practices typically require a slope of 1/4 inch per foot of length. A qualified plumber should evaluate and repair as necessary, and as per standard building practices.

    58) Plumbing / Fuel Systems:   - One or more sections of copper pipe were found in the gas supply pipes. Some municipalities don't allow this. Standard building practices require that black steel pipe or plastic coated steel pipe be used in most cases. Recommend having a qualified contractor evaluate and replace pipe or make repairs if necessary.

    59) Plumbing / Fuel Systems:   - One or more sections of water supply pipes were loose or had substandard support. A qualified person should evaluate and repair as necessary, and as per standard building practices.

    60) Plumbing / Fuel Systems:   - All water supply pipes in the crawl space were uninsulated. Recommend insulating pipes as per standard building practices for better energy efficiency and to prevent water pipes from freezing.

    61) Plumbing / Fuel Systems:   - Water supply lines were routed outside and are subject to freezing. Pipe wrap or foam sleeves are inexpensive and easily installed. Recommend insulating pipes as necessary to prevent pipes from freezing and bursting.

    62) Plumbing / Fuel Systems:   - The inspector was not able to find the main water shut-off valve. The client should consult with the property owner to determine if a shut-off valve exists, find it themselves, or hire a qualified plumber if necessary to find it. If no shut-off valve is found for the structure, then recommend having a qualified plumber install one to more easily allow the water supply to be turned off in the event of an emergency, such as when a supply pipe bursts.

    63) Plumbing / Fuel Systems:   - Recommend having the septic tank inspected. Recommend having the tank pumped if it was last pumped more than 3 years ago.

    64) Water Heater:   - Combustible materials were too close to the flue pipe. This is a fire hazard. Combustible materials should be moved well away from the flue or repairs made by a qualified contractor as necessary. Standard building practices typically require the following clearances:

  • Minimum one inch from "B" vent for gas-fueled burner
  • Minimum two inches from double wall pipe for oil or gas-fueled burner
  • Minimum 18 inches from single wall pipe with no draft hood for oil or gas-fueled burner
  • Minimum 9 inches from single wall pipe with a draft hood for oil-fueled burner
  • Minimum 6 inches from single wall pipe with a draft hood for gas-fueled burner
    65) Water Heater:   - No drain line was installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.

    66) Water Heater:   - The water heater's seismic straps or struts were substandard. For example, they may allow significant movement or use improper fasteners. This is a potential safety hazard. Leaks may also occur in water supply pipes. A qualified person should evaluate and either repair existing straps or install new straps or struts as necessary and as per standard building practices.

    67) Water Heater:   - No water supply shut-off valve was visible for the water heater. A shut-off valve allows the supply to the water heater to be turned off when the water heater needs repair or replacement, while allowing the remainder of the plumbing system to be operable (toilets, sinks, etc.). Recommend having a qualified, licensed plumbing contractor determine if a water supply shut-off valve exists, and install one if it is missing.

    69) Heating:   - There is no visible heat source in the structure.

    70) Cooling / Heat Pump:   - This cooling or heat pump system was not fully evaluated because the water supply was turned off. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the system is operable. Note that as per the standards of practice for NACHI (http://www.nachi.org) and ASHI (www.ashi.org), the inspector is not required to operate or replace overcurrent protection devices, or operate any controls other than "normal controls".

    71) Kitchen:   - The sink sprayer base was loose. A qualified person should evaluate and repair as necessary.

    72) Kitchen:   - One or more sink faucets were loose. A qualified person should repair as necessary.

    73) Kitchen:   - One or more sink drains used flexible drain pipe. This type of drain pipe is more likely to clog than smooth wall pipe. Recommend having a qualified plumber replace this pipe with standard plumbing components (smooth wall pipe) to prevent clogged drains.

    74) Kitchen:   - No "air gap" was installed for the dishwasher drain line. Air gaps are a device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client should consult with a qualified contractor to determine if an air gap should be installed.

    77) Bathrooms / Laundry / Sinks:   - The flow from the bathtub's hot, cold water supply was low at location #A. A qualified person should evaluate and repair as necessary.

    78) Bathrooms / Laundry / Sinks:   - The bathtub drain stopper mechanism at location #A was inoperable. A qualified person should repair or replace as necessary.

    79) Bathrooms / Laundry / Sinks: - Caulk was missing by the floor, wall at the bathtub at location #A. A qualified person should repair as necessary.

    80) Bathrooms / Laundry / Sinks:   - The sink drain stopper mechanism at location #A was inoperable. A qualified person should repair or replace as necessary.

    84) Interior Rooms / Areas:   - This structure was built prior to 1979 and may contain lead paint. Laws were enacted in 1978 in the US preventing the use of lead paint in residential structures. Lead is a known safety hazard, especially to children but also to adults. The paint found in and around this structure appeared to be intact and may be encapsulated by more recent layers of paint that are not lead-based. Regardless, recommend following precautions as described in the following links to Consumer Products Safety Commission website articles regarding possible lead paint:
    http://www.cpsc.gov/CPSCPUB/PUBS/5054.html
    http://www.cpsc.gov/CPSCPUB/PUBS/5055.html

    85) Interior Rooms / Areas:   - The weatherstrip around one or more exterior doors was substandard. A qualified person should repair or replace as necessary.

    86) Interior Rooms / Areas:   - interior doors were difficult to latch. A qualified person should evaluate and repair as necessary.

    87) Interior Rooms / Areas:   - Some interior door hardware, including locksets, strike plates were missing. A qualified person should repair or replace as necessary.

    88) Interior Rooms / Areas:   - Trim was missing in some areas. A qualified person should repair as necessary.

    89) Interior Rooms / Areas:   - Fixtures such as door stops were missing in one or more areas. A qualified person should install missing fixtures as per standard building practices.