Frisbie Home Inspection


PO Box 894 
Beaverton OR 97075-0894
Inspector: Stan Frisbie
CCB 156506
OCHI 152

 

Property Inspection Report

Client(s):  Shen Yang
Property address:  24152 Pete's Mountain Rd
West Linn OR
Inspection date:  Friday, September 11, 2015

This report published on Sunday, September 13, 2015 12:11:58 PM PDT

Thank you for choosing Frisbie Home Inspection to perform your home inspection. Every effort was made to provide a complete and thorough inspection, and I hope that the information provided in this report is valuable in your consideration of this property. If you have any questions at all regarding this report, please do not hesitate to contact me.

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information
Concern typeDamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior / Foundation
Roof / Attic
Garage / Carport
Electric
Electric 2
Electric 3
Plumbing / Fuel Systems
Water Heater
Water Heater 2
Water Heater 3
Heating
Heating 2
Heating 3
Heating 4
Cooling / Heat Pump
Cooling / Heat Pump 2
Cooling / Heat Pump 3
Cooling / Heat Pump 4
Cooling / Heat Pump 5
Fireplaces / Stoves / Chimneys
Fireplaces / Stoves / Chimneys 2
Kitchen
Bathrooms / Laundry / Sinks
Bathrooms / Laundry / Sinks 2
Interior Rooms / Areas
Private Well
Structural Pest Findings


General Information
Return to table of contents

Time started: 12:00 Pm
Time finished: 4:30 Pm
Inspector: Stan Frisbie
Present during inspection: Client, Realtor
Client present for discussion at end of inspection: No
Weather conditions: Clear
Temperature: Hot
Ground condition: Dry
Inspection fee: 1520.00
Payment method: Invoiced
Type of building: Single family
Buildings inspected: House / attached garage
Number of residential units inspected: 1
Age of building(s): 1995 / 14000'
Source for building age: Property listing
Front of building faces: West
Main entrance faces: West
Occupied: Yes
Discosure Reviewed:: No

1) Evidence of rodent infestation was found in the form of feces in the garage and traps at exterior. Recommend consulting with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary.
Photo
Photo 1-1
Photo
Photo 1-2
Photo
Photo 1-3
 

Grounds
Return to table of contents

Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
Condition of fences and gates: Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Wrought iron
Condition of retaining walls: Appeared serviceable
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of decks, porches and/or balconies: Appeared serviceable
Condition of guardrails: Appeared serviceable
Deck, porch and/or balcony material: Concrete
Condition of exterior stairs: Appeared serviceable
Exterior stair material: Concrete

2) Stucco at guardrails in one or more areas was deteriorated. Recommend repair as necessary by qualified contractor (see exterior comments).
Photo
Photo 2-1
 

3) Conducive conditions Trees were in contact with or were close to the building in one or more areas. Damage may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.
Photo
Photo 3-1
Photo
Photo 3-2
Photo
Photo 3-3
 

Exterior / Foundation
Return to table of contents

Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of wall covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Expanded insulation foam system (EIFS)
Condition of foundation and footings: Appeared serviceable
Foundation type: Crawlspace
Foundation material: Poured in place concrete
Footing material: Poured in place concrete
Condition of floor substructure: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure: Solid wood joists
Condition of crawl space: Appeared serviceable
Crawl space inspection method: Traversed
Insulation material underneath floor above: Fiberglass roll or batt
Ventilation: Appears serviceable
Vapor barrier present: Yes

4) Damage Rot / water damage was found at front door window sill, exposed beam at garage, and left side garage door. A qualified person should evaluate and repair as necessary. All rotten wood should be replaced.
Photo
Photo 4-1
Photo
Photo 4-2
Photo
Photo 4-3
 

5) Conducive conditions Cracks, deterioration and/or damage was found in multiple areas of the expanded foam insulation system (EIFS) siding. For example, garage posts, rear of house, and window sill at rear. Some of the cracking is cosmetic, client may wish to repair for aesthetic reasons. There are several holes in siding at rear. A qualified contractor who specializes in this material should evaluate and make repairs and repair siding as necessary.
Photo
Photo 5-1
Photo
Photo 5-2
Photo
Photo 5-3
Photo
Photo 5-4
Photo
Photo 5-5
Photo
Photo 5-6

6) Conducive conditions Multiple crawl space vent wells were needed where landscape materials are covering vents. This can lead to water entering and accumulating in the crawl space, and is a conducive condition for wood destroying insects and organisms. A qualified contractor should install wells where necessary.
Photo
Photo 6-1
Photo
Photo 6-2

Roof / Attic
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
Condition of roof structure: Appeared serviceable
Roof type: Gable, Hipped
Age of roof surface(s): Original
Source for building age: Inspector's estimate
Roof inspection method: Viewed from ground with binoculars, Viewed from windows
Condition of metal and/or tile roof surface materials: Required repair, replacement and/or evaluation (see comments below)
Metal, tile or panel roof surface material: Concrete tile
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
Gutter and downspout installation: Full
Condition of attic: Appeared serviceable
Attic inspection method: Viewed from hatch(es)
Roof structure type: Rafters
Ceiling structure: Ceiling beams
Ceiling insulation material: Fiberglass loose fill
Ceiling insulation depth: 12/14"
Roof ventilation: Appears serviceable

7) Conducive conditions Roof repairs were needed because some concrete tiles were cracked and/or loose at rear. A qualified contractor should evaluate entire roof and repair as necessary.
Photo
Photo 7-1
 

8) Conducive conditions Debris had accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the building exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

9) Because of the roof covering type, the inspector was unable to traverse the roof and wasn't able to fully evaluate the entire roof.

Garage / Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages varies between municipalities.
Type: Attached
Condition of garage: Appeared serviceable
Type of garage: Solid core, Wood
Condition of garage vehicle door(s): Required repair, replacement and/or evaluation (see comments below)
Garage vehicle door type: Sectional
Number of vehicle doors: 6
Condition of automatic opener(s): Required repair, replacement and/or evaluation (see comments below)
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable

10) Right side vehicle door was damaged at bottom, and weatherstrip is loose. A qualified contractor should evaluate and repair or replace the door(s) as necessary.
Photo
Photo 10-1
Photo
Photo 10-2

11) Number four door opener couldn't be fully evaluated because it was disconnected. Recommend repair if necessary, and verify proper operation of opener.

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120
Service amperage (amps): 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Aluminum
Main disconnect rating (amps): Not applicable, no single main disconnect
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Upstairs hall closet
Location of sub-panel #B: Pool room
Branch circuit wiring type: Non-metallic sheathed
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Condition of smoke detectors: Appeared serviceable
Smoke detectors present: Yes
Carbon monoxide detectors present: No
Smoke detector power source: Hard wired

12) This property had one or more fuel burning appliances and/or an attached garage, and no carbon monoxide detectors were visible at right side hall upstairs. Recommend installing one or more carbon monoxide detectors as necessary and as per the manufacturer's instructions, and mandated guidelines.

13) Some switch cover plates were missing. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. A qualified person should repair as necessary.
Photo
Photo 13-1
 

14) Two wires in left side of crawlspace were on ground and not terminated properly. These wires should be terminated in a junction box. Recommend repair by qualified electrician.
Photo
Photo 14-1
Photo
Photo 14-2

Electric 2
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120
Service amperage (amps): 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Aluminum
Main disconnect rating (amps): 200

15)   Panel Garage
Photo
Photo 15-1
 

16)   Panel upstairs closet
Photo
Photo 16-1
 

Electric 3
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120
Service amperage (amps): 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Aluminum
Main disconnect rating (amps): 200
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of sub-panel #B: Next to main pane
Location of sub-panel #D: Garage
Location of main disconnect: Garage 

17)   Panel garage
Photo
Photo 17-1
 

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Private
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: ABS
Condition of fuel system: Appeared serviceable
Location of main fuel shut: Crawlspace / meter

18) This property has a septic system that is outside the scope of this inspection. Recommend having a qualified plumber inspect the system to determine if it needs repair or maintenance.

Water Heater
Return to table of contents

Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Appeared serviceable
Type: Tank
Estimated age: 2003
Energy source: Natural gas
Capacity (in gallons): 34
Manufacturer: Lennox
Location of water heater: Upstairs closet
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable

19) A circulating pump was installed for the hot water supply. It is intended to make hot water immediately available when faucets are turned on. Timers are typically integrated with these pumps, and should be configured so water circulates only at desired times for better energy efficiency. The client should familiarize themselves with the timer's operation and configure it as needed.
Photo
Photo 19-1
 

Water Heater 2
Return to table of contents

Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Appeared serviceable
Type: Tank
Estimated age: 2005
Energy source: Natural gas
Capacity (in gallons): 74
Manufacturer: A.O. Smith
Location of water heater: Garage
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable

Water Heater 3
Return to table of contents

Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Appeared serviceable
Type: Tank
Estimated age: 2009
Energy source: Natural gas
Capacity (in gallons): 74
Manufacturer: A.O. Smith
Location of water heater: Garage
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable

Heating
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
Condition of heating system: Required repair, replacement and/or evaluation (see comments below)
Location of heating system: Closet, Upstairs 
Heating type: Forced air, Hot water
Fuel type: Natural gas
Manufacturer: Lennox
Last service date: Unknown
Condition of distribution system: Appeared serviceable
Distribution system: Ducts and registers
Condition of controls: Appeared serviceable
Condition of air filters: Appeared serviceable
Location of air filters: At base of air handler, Electronic 

20) The last service date of this system appeared to be more than two years ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than two years ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed every few years in the future, or as per the contractor's recommendations.
Photo
Photo 20-1
 

Heating 2
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
Condition of heating system: Required repair, replacement and/or evaluation (see comments below)
Location of heating system: Closet, Upstairs 
Heating type: Forced air, Hot water
Fuel type: Natural gas
Manufacturer: Lennox
Last service date: Unknown
Condition of distribution system: Appeared serviceable
Distribution system: Ducts and registers
Condition of controls: Appeared serviceable
Condition of air filters: Appeared serviceable
Location of air filters: At base of air handler

21) The last service date of this system appeared to be more than two years ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than two years ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed every few years in the future, or as per the contractor's recommendations.

Heating 3
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
Condition of heating system: Appeared serviceable
Location of heating system: Garage
Heating type: Forced air
Fuel type: Natural gas
Manufacturer: Lennox
Last service date: 2/14/2013
Model: 1995
Source for last service date: Label on heater
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Condition of distribution system: Appeared serviceable
Distribution system: Ducts and registers
Condition of controls: Appeared serviceable
Condition of air filters: Appeared serviceable
Location of air filters: At top of air handler, Electronic 

Heating 4
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
Condition of heating system: Appeared serviceable
Location of heating system: Garage
Heating type: Forced air
Fuel type: Natural gas
Manufacturer: Trane
Last service date: 2/14/12
Source for last service date: Label on heater
Condition of burners: Not determined
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Condition of distribution system: Appeared serviceable
Distribution system: Ducts and registers
Condition of controls: Appeared serviceable
Condition of air filters: Appeared serviceable
Location of air filters: At top of air handler

Cooling / Heat Pump
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Appeared serviceable
Location: Right side
Type: Split system
Estimated age: 2014
Manufacturer: Carrier
Condition of controls: Appeared serviceable

Cooling / Heat Pump 2
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Required repair, replacement and/or evaluation (see comments below)
Location: Right side
Type: Split system
Estimated age: 1996
Manufacturer: Lennox
Condition of controls: Appeared serviceable

22) The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified contractor should service this system and make repairs if necessary. This servicing should be performed annually in the future.

Cooling / Heat Pump 3
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Not determined
Location: Rear
Type: Split system
Estimated age: 1995
Manufacturer: Lennox
Condition of controls: Appeared serviceable

23) The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified contractor should service this system and make repairs if necessary. This servicing should be performed annually in the future.

Cooling / Heat Pump 4
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Appeared serviceable
Location: Rear
Type: Split system
Estimated age: 2015
Manufacturer: American Standard
Condition of controls: Appeared serviceable

Cooling / Heat Pump 5
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Appeared serviceable
Location: Rear
Type: Split system
Estimated age: 2006
Manufacturer: Trane
Condition of distribution system: Appeared serviceable
Condition of controls: Appeared serviceable

24) The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified contractor should service this system and make repairs if necessary. This servicing should be performed annually in the future.

Fireplaces / Stoves / Chimneys
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, nor determine if prefabricated or zero clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit.
Condition of fireplaces, stoves: Appeared serviceable
Location #A: Master bedroom
Location #B: Office / masonry
Location #C: Living room / masonry
Location #D: Family room
Fireplace type: Masonry, Prefabricated
Fuel type: Natural gas
Condition of chimneys: Appeared serviceable
Chimney type: Masonry, Metal, with wood enclosure

25) The gas fireplaces were not fully evaluated because they are manually lit units . As per the Oregon Standards of Practice and both the National Association of Certified Home Inspectors (NACHI) and the American Society of Home Inspectors (ASHI) the inspector does not operate gas shut off valves or light pilot lights during inspections.

Fireplaces / Stoves / Chimneys 2
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, nor determine if prefabricated or zero clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit.
Condition of fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Location #A: Media room
Fireplace type: Prefabricated
Stove type: Insert
Fuel type: Natural gas
Condition of chimneys: Appeared serviceable
Chimney type: Metal

26) The glass at the gas fireplace at location #A, (media) had a hazy film. This is typically a mineral residue left from water vapor as the gas burns. It may be possible to clean this fogging by removing the glass from the fireplace and using a gas appliance ceramic glass cleaner, available through gas fireplace and stove distributors and installers. Ammonia-based products, such as common glass cleaners, should not be used since they may cause damage or etching to the glass, or make the haze permanent.

It may be possible for a homeowner to remove the glass for cleaning, depending on if the instructions or manual for the fireplace are available, and if the homeowner is experienced in such repairs. Recommend consulting with a gas fireplace installation contractor for more information, or to have them do the cleaning.
Photo
Photo 26-1
 

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of garbage disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable. Run through complete cycle at time of inspection.
Condition of range, cooktop: Required repair, replacement and/or evaluation (see comments below)
Range, cooktop type: Natural gas, Electric
Condition of refrigerator: Appeared serviceable

27) Three cooktop burner(s) were inoperable. A qualified person should evaluate and repair as necessary.

28) Main sink faucet handle was difficult to close, and small sink faucet is loose. A qualified person should repair or replace as necessary.

Photo
Photo 28-1
Photo
Photo 28-2

Bathrooms / Laundry / Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Master
Location #B: Right rear bedroom
Location #C: Front bedroom
Location #D: Left front bedroom
Location #E: Left  bedroom
Location #F: Left rear bedroom
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Appeared serviceable
Condition of laundry facilities: Appeared serviceable, Upstairs 
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes

29) The bathtub drain stopper mechanism at location #A was inoperable. A qualified person should repair or replace as necessary.

30) Conducive conditions The grout around the shower pan at location #B was Cracking. A qualified person should repair as necessary.
Photo
Photo 30-1
 

31) The jetted tub at location #A was inoperable. A qualified contractor should evaluate and repair or replace as necessary.

32) The toilet at location #F had no water supply and could not be fully evaluated. The shut-off valve(s) may be turned off, or repairs may be necessary. The client should ask the property owner about this, and have a qualified plumber evaluate and repair if necessary.

Bathrooms / Laundry / Sinks 2
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Right side bedroom
Location #B: 1/2 bath at entry
Location #C: 1/2 bath at garage entry
Location #D: Media room
Location #E: Gym
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable

Interior Rooms / Areas
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
Exterior door material: Wood, Metal
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Condition of interior doors: Appeared serviceable
Type of windows: Wood, Multi, Fixed, Hinged 
Condition of windows: Required repair, replacement and/or evaluation (see comments below)
Wall type or covering: Drywall
Condition of walls: Appeared serviceable
Ceiling type or covering: Drywall
Condition of ceilings: Appeared serviceable
Flooring type or covering: Carpet, Wood, Tile
Condition of flooring: Appeared serviceable

33) The seal between multi-pane glass in pool room door appeared to have failed based on condensation or stains between the panes of glass. A qualified contractor should evaluate and replace glass where necessary.

The client should be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Glass doors or windows other than those that the inspector identified may also have failed seals and need glass replaced too.
Photo
Photo 33-1
 

34) One rear living room windows was damaged at trim. A qualified person should evaluate and repair or replace as necessary.
Photo
Photo 34-1
 

35) The weatherstrip around left side exterior door (next to garage) was deteriorated. A qualified person should repair or replace as necessary.
Photo
Photo 35-1
 

Private Well
Return to table of contents

Limitations: The inspector does not test private well water for contamination or pollutants, determine if the supply and/or flow are adequate, or provide an estimate for remaining life of well pumps, pressure tanks or equipment. Only visible components are evaluated. The client should have qualified lab test the well water for bacterial contaminants. A qualified well specialist should evaluate the well and perform a yield test.

36) The well was not observed or evaluated during the inspection.

Structural Pest Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than five feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood destroying organisms may infest, reinfest or become active at anytime. No warranty is provided as part of this inspection.
Visible evidence of active wood destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood destroying insects: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood destroying organisms: Yes

This inspection was performed in accordance with the Oregon Home Inspection standards of practice, set forth in Division 8 of OAR chapter 812. A copy of these standards were provided to you at the time of the inspection. Home inspections are essentially visible in nature, and do not include the dismantling of equipment, or defacing of the property to inspect. The purpose of this inspection is to identify any defects that would require evaluation by a specialist. No ancillary inspections were performed, such as testing air quality, radon testing, mold, etc.