Integris Home Inspections, LLC

Website: http://www.integrisres.com
Email: bill@integrisres.com
Phone: (616) 502-6751
210 Barber St 
Spring Lake MI 49456
Inspector: Bill Sibilla

     

Pre Purchase Property Inspection Report

Client(s):  John and Mary Smith
Property address:  1313 Woodfield Blvd.
Anytown USA 00000
Inspection date:  Thursday, June 18, 2015

This report published on Friday, July 10, 2015 12:33:54 PM EDT

Thank you for choosing Integris Home inspections. It is our intention to provide you with the most clear and concise information on your Inspection Report to air in your decision making process. If at any point, you have additional questions, please feel free to contact us and we will do our best to provide the answers you need. This report is the exclusive property of Integris Home Inspections, LLC and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeServiceableItem or component is in servicable condition
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings


General Information
Return to table of contents

Report number: 501
Time started: 5:20
Time finished: 8:15
Present during inspection: Client
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Sunny
Temperature during inspection: Hot
Inspection fee: $289
Payment method: Credit card
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building:
Front of building faces: West
Main entrance faces: West
Occupied: No
Buildings inspected: One detached garage
Age of main building: 20 years
Source for main building age: Client

1) Based on substandard construction observed, modifications to this property may have been made without the owner having attained permits or inspections from the municipality. Work may have been performed by someone other than a qualified contractor or person. Consult with the property owner about this, and if necessary research permits.

At worst case, if substantial work was performed without permits, this knowledge must be disclosed when the building is sold in the future. This can adversely affect future sales. Also, the local municipality could require costly alterations to bring the building into legal compliance or even require that the additions or modifications be removed.

Wiring connection made outside of an approved box for downstairs bathroom fixture. This is in the utility area in the Southeast corner of the basement and should be easily fixed by a qualified electrician.
Photo
Photo 1-1
Photo
Photo 1-2

2) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC

3) Microbial growths were found at one or more locations. It is beyond the scope of this inspection to identify what substance or organism this staining is. However such staining is normally caused by excessively moist conditions, which in turn can be caused by plumbing or building envelope leaks and/or substandard ventilation. These conducive conditions should be corrected before making any attempts to remove or correct the staining. Normally affected materials such as drywall are removed, enclosed affected spaces are allowed to dry thoroughly, a mildewcide may be applied, and only then is drywall reinstalled. For evaluation and possible mitigation, consult with a qualified industrial hygienist or mold/moisture mitigation specialist. For more information, visit:
http://www.reporthost.com/?MOLDCDC
http://www.reporthost.com/?MOLDEPA

A small mold stain was found in the Southeast corner of the basement family room along the baseboard. See accompanying photo below.
Photo
Photo 3-1
Mold staining in fower fevel family room
 

4) Evidence of rodent infestation was found in the form of Holes and Den entrances in the Yard near the foundation. These appear to be Chipmunk dens and chipmunks were observed nearby during the inspection. There were no observed ingress points in the structure. Consult with the property owner about this. A qualified person should make repairs to the grounds and seal any discovered openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.reporthost.com/?SEALUP
http://www.reporthost.com/?TRAPUP
http://www.reporthost.com/?CLEANUP
Photo
Photo 4-1
Rodent Hole on Northeast corner
 

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete, Asphalt, Gravel
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete, Wood, Pavers
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open, Covered, Lower level walkout covered by main floor deck
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Appeared serviceable, Missing railing on one side
Exterior stair material: Wood, Plastic fiber

5) Flashing appeared to be missing from above one or more deck or porch ledger boards, or could not be verified. Missing flashing at this location can cause moisture to accumulate between the ledger boards and the building. Fungal rot may occur in this area and cause the ledger board fasteners to fail. The deck may separate from the building in this event. This is a potential safety hazard. Recommend that a qualified contractor install flashing above ledger boards per standard building practices. For more information, visit:
http://www.reporthost.com/?LB
http://www.reporthost.com/?SD
Photo
Photo 5-1
Lower deck attached to cement patio outside center bedroom
Photo
Photo 5-2
Photo
Photo 5-3
Outside main level french door.
Photo
Photo 5-4
Main level outside of dining room.

6) Handrails at one or more flights of stairs were missing. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high. Recommend that a qualified contractor install handrails where missing and per standard building practices.
Photo
Photo 6-1
Photo
Photo 6-2

7) The plastic composite decking boards needed cleaning. Dirt, moss, lichen, algae or debris will deteriorate such decking, and most manufacturers recommend periodic cleaning. Recommend cleaning per the manufacturer's specifications. For more information, visit:
http://www.reporthost.com/?COMPDECKMT

8) Significant amounts of standing water or evidence of past accumulated water were found at one or more locations in the yard or landscaped areas, and no drain was visible. If evidence of past water was found (e.g. silt accumulation or staining), monitor these areas in the future during periods of heavy rain. If standing water exists, recommend that a qualified person repair as necessary. For example, installing one or more drains, or grading soil.

Ground was excessively soggy in North and Northeast lower yard between patio and garden area.

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Vinyl, Stone or faux stone veneer
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Finished basement
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Not determined (inaccessible or obscured)

9) Some sections of siding and/or trim were deteriorated. Recommend that a qualified person repair, replace or install siding or trim as necessary.

Trim between double bay window on East side of lower level had apparent rot. This needs to be addressed to prevent any further ingress of moisture.

There are apparent water stains likely from heavy iron content in water around hose bibs and on shaded corner of siding in Northwest corner

Cracked siding right of the garage door. The previous owner left extra siding peices in the garage.
Photo
Photo 9-1
Photo
Photo 9-2
Photo
Photo 9-3
Photo
Photo 9-4
Photo
Photo 9-5
 

10) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 10-1
 

11) Trees were in contact with or were close to the building at one or more locations. Damage to the building can occur, especially during high winds, or may have already occurred (see other comments in this report). Recommend that a qualified tree service contractor or certified arborist remove trees as necessary to prevent damage to the building exterior.

Tree in Northeast Corner close to and contacting siding and roof.

Basement
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from eaves on ladder, Viewed from ground
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)

12) Substandard repairs were found at one or more locations on the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair per standard building practices.

Chicken wire has been installed in some locations as a makeshift gutter shield and is buckling first course of shingles. I recommend removing these and replacing with manufactured products more suited to this application. Gutter shielding would be very prudent for this house due to the high number of large oak trees present and high eves to reduce the periodic maintenance required to keep gutters clear.

There is one layer of composition shingles on roof but no evidence of an ice and or water barrier at the eves.
Photo
Photo 12-1
Photo
Photo 12-2

13) Significant amounts of debris have accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. This is a conducive condition for wood-destroying organisms. Recommend cleaning gutters and downspouts now and as necessary in the future.

14) Moss was growing on the roof. As a result, shingles can lift or be damaged. Leaks can result and/or the roof surface can fail prematurely. Efforts should be made to kill the moss during its growing season (wet months). Typically, zinc or phosphate-based chemicals are used for this and must be applied periodically. For information on various moss treatment products and their pros and cons, visit:
http://www.reporthost.com/?MOSS

15) Stains were found at the front of one or more gutters and indicate that the gutters have overflowed. If they have overflowed, it's usually due to debris clogging gutters or downspouts. The inspector was unable to verify that the gutters and downspouts drained adequately due to lack of recent, significant rainfall. Monitor the roof drainage system in the future while it's raining to determine if problems exist. Then if necessary, recommend that a qualified person clean, repair or replace gutters, downspouts and/or extensions.

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): R-30
Vapor retarder: None in some areas
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Ridge vent(s), Gable end vents

16) There was evidence apparently of rodents in the attic above the garage in the form of feces and poison left behind by the previous owner.
Photo
Photo 16-1
 

Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Metal
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Roll
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Condition of garage floor: Appeared serviceable

17) No threshold was installed at the base of the door between the garage and the house. House to garage doors prevent fire and fumes from spreading from the garage to the house. Thresholds prevent fire and fumes from spreading underneath the door. This is a potential safety hazard. Recommend that a qualified person install a threshold per standard building practices.

18) The auto-reverse mechanism on one or more automatic openers for garage vehicle doors . This is a potential safety hazard. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
http://www.reporthost.com/?NRGD

Not opperational

19) The Threshold on the service entrance to the garage from outside has deteriorated and could be prone to leaking as well as a potential location for rodent and/or insect ingress.
Photo
Photo 19-1
 

20) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.

There has been some deterioration of the floor on the West side parking position and some epoxy patching was visible.
Photo
Photo 20-1
Photo
Photo 20-2

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Condition of branch circuit wiring: Serviceable
Ground fault circuit interrupter (GFCI) protection present: Yes
GFCI Notation: We test the operation of GFCI receptacles as part of our evaluation. We also recommend the installation of GFCI receptacles near plumbing fixtures. It is current building code since 2008 to use GFCI receptacles in these locations but they weren’t always required.A “ground-fault” is an unintentional flow of electricity between a source of electrical current and a grounded surface. Without protection, electrical shock can occur if a person comes into contact with an energized part. For example, if a person is holding a damaged electrical cord from a hair dryer and touches a plumbing fixture, they could be electrocuted. A GFCI receptacle constantly monitors an electrical circuit. If it detects even a slight flow of electricity to a grounded item, it immediately shuts off the flow of electricity. This protects people from electrocution. It is particularly important to protect people where they could come in contact with exposed grounded items such as plumbing fixtures. GFCI receptacles were required in residential construction beginning in 1971. Originally they were only required at the exterior of the house and near swimming pool equipment. As time went on, GFCI receptacles have been required in more locations such as garages, bathrooms, kitchens, etc. In an older home there may be no requirement for GFCI’s to be installed. The seller is not required to upgrade the receptacles unless the electrical system has been modified. So if the kitchen in a house has been remodeled, and receptacles have been added or moved, they must be upgraded to GFCI receptacles if they are within 6 feet of a plumbing fixture. This applies to bathrooms too. So when your home inspector suggests upgrading certain receptacles to GFCI receptacles, please know that he has your safety in mind. The seller may not be required to upgrade these receptacles, but you should do it for your family’s safety.

21) One or more ground fault circuit interrupter (GFCI) receptacles at the . This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.

All GFCI receptacles were tested and all tripped and reset with the exception of the one on the main floor rear deck. This receptacle was also loose.

22) One or more receptacles were broken or damaged. This is a potential shock or fire hazard. Recommend that a qualified electrician replace such receptacles as necessary.

One receptacle on the North wall in the Master bedroom was loose. Several in the basement family room were either crooked or mounted in a fashion not flush with the wall.

23) Only two of the many smoke alarms in this house were operational. The house appears to be wired for linked alarms such as those offered by Kidde and others. It is recommended that all of these be replaced as a precaution since they appear to have outlived their service life.

24) One or more wall switches were broken or damaged. Recommend that a qualified electrician replace wall switches as necessary.


The light switch for the lights outside the garage located in the laundry room appears to be intermittent in operation. Several light switches throughout the house had a "light" feel to them which is to say that they felt worn.

25) Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.

Several bulbs were missing and or apparently burned out. Several exterior fixtures were damaged and in need of minor repairs or replacement outside of the garage and rear deck.
Photo
Photo 25-1
Photo
Photo 25-2
Photo
Photo 25-3
 

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Private well
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper

26) Water was discolored when bathtubs or sinks were filled, or when showers were operated. This can be caused by water stagnating in water supply pipes, rust accumulating in pipes or in the water heater, or sediment being present in the water supply. Recommend flushing the water supply piping and the water heater. If that fails to resolve the issue, then have a qualified plumber evaluate and repair as necessary.

27) Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC

28) Based on visible equipment or information provided to the inspector, the water supply to this property appeared to be from a private well. Private well water supplies are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. The inspector does not test private well water for contamination or pollutants, determine if the supply and/or flow are adequate, or provide an estimate for remaining life of well pumps, pressure tanks or equipment. Only visible and accessible components are evaluated. Recommend the following:
  • That a qualified well contractor fully evaluate the well, including a pump/flow test
  • That the well water be tested per the client's concerns (coliforms, pH, contaminants, etc.)
  • Research the well's history (how/when constructed, how/when maintained or repaired, past performance, past health issues)
  • Document the current well capacity and water quality for future reference
For more information, visit:
http://www.reporthost.com/?WELL

29) A water softener system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Water softeners typically work by removing unwanted minerals (e.g. calcium, magnesium) from the water supply. They prevent build-up of scale inside water supply pipes, improve lathering while washing, and prevent spots on dishes. Recommend consulting with the property owner about this system to determine its condition, required maintenance, age, expected remaining life, etc. For more information, visit:
http://www.reporthost.com/?WTRSFT
http://www.reporthost.com/?HRDWTR

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 19 Years. Manufacture date of 1996
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Utility room, Basement
Hot water temperature tested: Yes, Temperature was tested at faucets with skin test to confirm that it is working.
Condition of venting system: Appeared serviceable

30) The outer flame shield for the water heater combustion chamber was missing. This is a potential fire hazard. Recommend that a qualified person replace any missing flame shields.

Flame shield was removed and lying next to water heater.
Photo
Photo 30-1
 

31) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be at and/or beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace, Wood-burning fireplace or stove
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: Furnace appears to be less than one year old with a manufacture date of 2014.
Source for last service date of primary heat source: Label
Condition of forced air heating/(cooling) system: Appeared serviceable
Location of forced air furnace: Utility room, Basement
Forced air system capacity in BTUs or kilowatts: 80,000 BTUs
Condition of furnace filters: Appeared serviceable
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location: Condenser located in Southeast corner outside of garage.
Type: Split system
Condition of controls: Appeared serviceable

32) Recommend replacing or washing HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or washing them as necessary. How frequently they need replacing or washing depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo
Photo 32-1
Photo
Photo 32-2
Photo
Photo 32-3
 

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Masonry with metal liner
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: with wood enclosure, with metal liner

33) One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA

34)   Ice maker in the refrigerator is not working

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Required repair, replacement and/or evaluation (see comments below), Ice maker not working
Condition of built-in microwave oven: Appeared serviceable
Condition of refrigerator: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below), Ice-maker not operational

35) One or more sink water shut-off valve handles were damaged. Recommend that a qualified person replace or repair as necessary.

Drinking water faucet to the right of main faucet not working.

36) One outlet East wall was not accessible for test due to a rod installed by the owner. See picture.
Photo
Photo 36-1
 

37)   Pot lights in the ceiling are wired in a curious manner. In order to light all of them involves three separate switches. I suspect an upgrade was done at some point and this may have been a homeowner completed project.

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Laundry room/area, first floor
Location #B: Full bath, First floor, South, Full Bath
Location #C: Master bath, first floor, Master bath
Location #D: 3/4 bath, basement
Condition of counters: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: No
Condition of cabinets: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable, Jacuzzi tub in master bathroom was not evaluated for operation due to rusty water.
Bathroom and laundry ventilation type: Spot exhaust fans, with individual ducts

38) The toilet at location(s) #B was loose where it attached to the floor. Leaks can occur. Flooring, the sub-floor or areas below may get damaged. Sewer gases can enter living spaces. Recommend that a qualified contractor remove the toilet(s) for further evaluation and repair if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.

Evidence of a leaking wax seal was found on the floor tile behind the toilet in the bathroom closest to the kitchen.
Photo
Photo 38-1
 

39) The toilet at location(s) #B ran water continuously or didn't shut off after being flushed, and water leaked from the tank into the bowl. Significant amounts of water can be lost through such leaks. If this system uses a septic system, the septic system can be overloaded and cause significant and potentially expensive damage. A qualified person should repair or replace components as necessary.

Toilet runs in b

40) One or more cabinets, drawers and/or cabinet doors at location(s) #A and #C were damaged or deteriorated. Recommend that a qualified person repair or replace as necessary.

#A. Doors in the laundry room cabinet were mounted backwards. It appears they were removed for painting and returned to the wrong locations as the original holes are clearly visible at the hing points. This is a simple repair.

#C. Lower shelves in both Master bath closets are bent from heavy loading

41) Vinyl flooring at location(s) #A was deteriorated. Water can damage the the sub-floor as a result. Recommend that a qualified contractor replace or repair flooring as necessary.

Cracks in the floor tiles in the laundry area.
Photo
Photo 41-1
 

42) The toilet at location(s) #B ran water continuously or didn't shut off after being flushed, and water leaked from the tank into the bowl. Significant amounts of water can be lost through such leaks. If this system uses a septic system, the septic system can be overloaded and cause significant and potentially expensive damage. A qualified person should repair or replace components as necessary.

The toilet runs due to interference with the flapper chain in he bathroom closest to the kitchen.

43) Tile and/or grout in the shower enclosure at location(s) #C were deteriorated (e.g. loose or cracked tiles, missing grout) or substandard. Water can damage the wall structure as a result. Recommend that a qualified contractor repair as necessary.
Photo
Photo 43-1
 

44) One or more leaks were found at water for the sink at location(s) #D. A qualified plumber should repair as necessary.

Apparent evidence of past leaking in the basement vanity. There was a bucket that was dry but stained under the trap.
Photo
Photo 44-1
 

45) Jacuzzi tub not tested due to brown water

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal, Glass panel
Condition of interior doors: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable

46) Some exterior door hardware, including locksets were deteriorated. Recommend that a qualified person repair or replace as necessary.

The door into house from garage closes loosely. The lockset is worn.

The French door in the living room has a loos hinge on the top left that appears to impact proper locking of the door. This should be looked at and repaired as needed for security.

47) Some interior door hardware (Ball Catch on top of door) were missing. Recommend that a qualified person repair or replace as necessary.

In the lavender bedroom and in the Center and South bedrooms of the basement, some of the ball catch hardware is missing.

48) One or more sliding glass doors were difficult to open or close. Recommend that a qualified person maintain, repair or replace door(s) as necessary. Often, cleaning the track and applying a lubricant will help.

49)   Stairs to basement were creaking indicating a potential need for additional support. These are easily accessed in the North utility room.

50)   The bathroom door stop in the master bedroom is missing.

51)   The door to the South two bedrooms in the lower level is not latching.

52)   There is a damaged patch of carpet in the Center bedroom of the lower level.

Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: Yes
Visible evidence of active wood decay fungi: Yes
Visible evidence of conditions conducive to wood-destroying organisms: Yes
Location #C: Ants in attic
Location #A: Garage attic
Location #B: Outside east wall of corner of garage

53) Evidence of active infestation of carpenter ants was found at location(s) #A and B in the form of active ants and large nest outside with no visible wood damage. Recommend the following:
  • Correct any conducive conditions for wood-destroying organisms mentioned in this report.
  • Consult with the property owner about any history of infestation.
  • Have a state-licensed pest control operator evaluate further and treat as necessary.
Photo
Photo 53-1
Photo
Photo 53-2
Active Ants
Photo
Photo 53-3
The large nest was covered by a piece of plywood that appeared to be placed so as to conceal its presence.
 

Thanks again for selecting Integris Home Inspection, LLC for your Pre-purchase inspection. It is advisable that you have licensed specialists provide a more detailed analysis on any areas of concern mentioned in our report. If you have any additional concerns, please feel free to call us at 616-502-6751