InspectPro Profesional Home Inspection


1067 Rosegold St 
Franklin Square NY 11010-2618
Inspector: Gianpaolo Daniello
16000069767

   

Property Inspection Report

Client(s):  Rida Khan
Property address:  29 Beechhurst Ave,
Floral Park, NY 11001
Inspection date:  Thursday, March 09, 2017

This report published on Sunday, March 12, 2017 12:24:03 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeServiceableItem or component is in servicable condition
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings
Crawl Space

View summary


General Information
Return to table of contents

Report number: 1007
Time started: 3pm
Time finished: 4:30pm
Present during inspection: Client, Property owner, 3 Realtors, 1 Broker
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Freezing
Inspection fee: 375.00
Payment method: Cash
Type of building: Single family
Buildings inspected: One house, One detached garage
Number of residential units inspected: 1
Age of main building: Built in 1952
Source for main building age: Municipal records or property listing
Front of building faces: West
Main entrance faces: West

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Near, at or beyond service life
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Masonry

1) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 1-1
Photo
Photo 1-2

2) Cracks, holes, settlement, heaving and/or deterioration were found in the driveway. Recommend that qualified contractor repair as necessary.
Photo
Photo 2-1
Photo
Photo 2-2
Photo
Photo 2-3
Photo
Photo 2-4

3) Missing bricks and mortar for both the front and rear exterior stairs should be monitored and eventually replaced.
Photo
Photo 3-1
Photo
Photo 3-2
Missing brick
Photo
Photo 3-3
Missing mortar
Photo
Photo 3-4

4) The soil or grading sloped down towards building perimeters in one or more areas. This can result in water accumulating around building foundations or underneath buildings. At a minimum, monitor these areas, and areas under the structure in the future for accumulated water. If water does accumulate, recommend grading soil so it slopes down and away from buildings with a slope of at least 1 inch per horizontal foot for at least 6 feet out from buildings.
Photo
Photo 4-1
Slopes left to right
Photo
Photo 4-2
Sloping towards the foundation

5) Missing bricks and mortar on the basement window wells. Monitor and replace when necessary. Other options are available for replacement.
Photo
Photo 5-1
Photo
Photo 5-2
Photo
Photo 5-3
 

6) Worn, cracking sealant found where driveway and foundation meet. It is recommeneded that this be resealed to avoid water intrusion.
Photo
Photo 6-1
Photo
Photo 6-2

7) At the time of inspection it was found that soil was in contact with bricks in the front flower beds, it is recommended that the soil be lowered to prevent deterioration to the bricks.
Photo
Photo 7-1
Soil in contact with bricks
Photo
Photo 7-2

8) The driveway sloped down towards the garage or house. This can result in water accumulating in the garage, around building foundations or underneath buildings, and is a conducive condition for wood-destroying organisms. Monitor these areas in the future, especially during and after periods of rain. If significant amounts of water are found to accumulate, then recommend that a qualified contractor evaluate and repair as necessary. For example, by installing drain(s) or removing and installing new pavement.
Photo
Photo 8-1
 

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Solid brick (not veneer)
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Unfinished basement
Foundation/stem wall material: Concrete block

9) A small area around the oil fill pipe was found to be missing mortar at the time of inspection. It is important to seal and holes and cracks on the exterior of your home in order to prevent water and animal intrusion.
Photo
Photo 9-1
Photo
Photo 9-2

10) Caulk was deteriorated in some areas. For example, around exterior windows. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
http://www.reporthost.com/?CAULK
Photo
Photo 10-1
Photo
Photo 10-2

11) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
Photo
Photo 11-1
 

Basement
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Steel
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed

12) There was a mix of new and old windows in the basement. One of the new windows was found to have a crack on one of the panes. It is recommended to replace the old single pane windows with newer double pane windows for better efficiency.
Photo
Photo 12-1
Old window
Photo
Photo 12-2
New window

13) Evidence of past water intrusion found on basement walls. It is important to note that there where no active leaks only stains from the past. This could be caused by grading being pitched towards the foundation.
Photo
Photo 13-1
 

14) Multiple views of support posts and beams which all looked well at the time of inspection.
Photo
Photo 14-1
Photo
Photo 14-2
Photo
Photo 14-3
Photo
Photo 14-4
Photo
Photo 14-5
Photo
Photo 14-6
Photo
Photo 14-7
Photo
Photo 14-8

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from eaves on ladder
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of gutters, downspouts and extensions: Appeared serviceable

15) Multiple views of the roof, gutters and flashing.
Photo
Photo 15-1
Photo
Photo 15-2
Photo
Photo 15-3
Photo
Photo 15-4
Photo
Photo 15-5
Photo
Photo 15-6
Photo
Photo 15-7
Photo
Photo 15-8
Photo
Photo 15-9
 

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Not inspected because access was blocked, Only able to reach arm in and snap a 2 pictures
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Not determined (inaccessible or obscured)
Condition of insulation in attic (ceiling, skylight chase, etc.): Not determined (inaccessible or obscured)
Ceiling insulation material: Not determined (inaccessible or obscured)
Approximate attic insulation R value (may vary in areas): Not determined (inaccessible or obscured)
Vermiculite insulation present: Not determined

16)   Very limited view of attic.
Photo
Photo 16-1
Photo
Photo 16-2
Photo
Photo 16-3
 

17)   Attic access which had insulation laying across the top of the hatch was very difficult to open. The inspector was only able to reach his hand through to take pictures.
Photo
Photo 17-1
 

Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Detached
Condition of garage vehicle door(s): Required repair, replacement and/or evaluation (see comments below)
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable

18) At the time of inspection the garage did not have any gutters or downspouts. This has led to water intrusion on the fascia and is causing damage.
Photo
Photo 18-1
Photo
Photo 18-2
Photo
Photo 18-3
 

19) One or more garage vehicle doors were difficult or unable to open or close. Vehicle doors should open and close smoothly and easily. A qualified person should evaluate and repair as necessary. This may require lubrication or repair to hardware such as rollers or brackets.

20)   Limited access due to stored items.
Photo
Photo 20-1
Photo
Photo 20-2

21)   The wood frame that the garage door tracks are attached to where found cracked at the time of inspection. This could be the reason why the door is so difficult to open.
Photo
Photo 21-1
Wood frame cracked
 

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Required repair, replacement and/or evaluation (see comments below)
Primary service type: Overhead
Number of service conductors: 2
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 100
System ground: Cold water supply pipes
Condition of main service panel: Near, at or beyond service life
Location of main service panel #A: Basement
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed, (BX) Armor clad flexible, Copper and Romex
Smoke alarms installed: Yes, but not tested

22) One or more electric receptacles at the kitchen and/or bathroom(s)and laundry room had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
Photo
Photo 22-1
No GFCI
 

23) Extension cords were being used as permanent wiring at one or more locations. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate and needs updating. Extension cords may be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend that a qualified electrician repair per standard building practices and eliminate extension cords for permanently installed equipment.
Photo
Photo 23-1
 

24) A significant amount of rust was found in the electric panel. Any water near electrical components is a severe safety hazard. It is noted that at the time of inspection the electric panel cover was found removed and placed on the floor and was also very rusty. It is recommended that licensed electrician evaluate how water is reaching the panel and replace the electric panel and all other components affiliated to the problem.
Photo
Photo 24-1
Photo
Photo 24-2
Photo
Photo 24-3
 

25) A light switch in the second floor bedroom was found pulling away from the wall. This could be a shock hazard and should be repaired.
Photo
Photo 25-1
 

26) No drip loop on overhead service cables. This a safety concern and does not meet standard building practices. It is recommended that a licensed electrician evaluate.
Photo
Photo 26-1
 

27) The electric meter pan and conduit where found to be rusted and dated. It is recommended that a licensed electrician evaluate and make necessary repairs.
Photo
Photo 27-1
Photo
Photo 27-2

28) The functionality of, power source for and placement of smoke alarms is not determined as part of this inspection. Smoke alarms should be installed in each bedroom, in hallways leading to bedrooms, on each level and in attached garages. They have a limited lifespan and should be replaced every 10 years. For home buyers, batteries in smoke alarms should be changed when taking occupancy. Batteries should be replaced annually in the future. Carbon monoxide alarms should be installed in the vicinity of sleeping areas and on each level. For more information, visit:
http://www.reporthost.com/?SMKALRM
http://www.reporthost.com/?COALRM

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper, PEX plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic, Galvanized steel
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic, Galvanized steel, Cast iron
Vent pipe condition: Appeared serviceable
Vent pipe material: Cast iron
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: in basement
Location of main fuel shut-off valve: At gas meter, At oil tank

29) Vent pipe was cracked at the time of inspection. Replacement is not necessary but it is recommended to have the crack sealed so the situation does not get worse.
Photo
Photo 29-1
 

30)   Views of gas meter, main gas shut off, oil tank and water main.
Photo
Photo 30-1
Gas meter
Photo
Photo 30-2
Gas shut off
Photo
Photo 30-3
Oil tank
Photo
Photo 30-4
Water main

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Integral with heating system
Energy source: Oil
Capacity (in gallons): Not applicable
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 101.8

31)   Water temperature measured at bathroom sink with a laser thermometer.
Photo
Photo 31-1
 

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Furnace
General heating distribution type(s): Pipes and radiators
Condition of hydronic or steam heat system: Appeared serviceable
Type of hydronic or steam heat: Hydronic (hot water)
Hydronic or steam heat fuel type: Oil
Type of combustion air supply: No dedicated source visible, uses room air
Condition of venting system: Appeared serviceable
Condition of controls: Appeared serviceable

32) View of Beckett oil burner based on serial # 12031403147 the burner was manufactured in 2012. It is recommended to service the unit annually.
Photo
Photo 32-1
Oil burner
 

33) Surface rust found on the bottom of boiler at the time of inspection should be monitored. No leaks found at time of the inspection.
Photo
Photo 33-1
 

34) View of Peerless oil fired boiler. Based on serial # 681122-201210 this boiler was produced in October 2012. Based on research of model # wbv 03 wpctl these boilers typically last 20-30 years. It is recommended to have your boiler serviced annually.
Photo
Photo 34-1
Boiler information found on boiler
Photo
Photo 34-2
Boiler

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of chimneys and flues: Appeared serviceable

35)   View of chimney cap(exterior) and exhaust flue(interior). Inspector where not able to inspect crown due to wet roof.
Photo
Photo 35-1
Photo
Photo 35-2

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Natural gas
Condition of refrigerator: Appeared serviceable

36) A 2" hole was found on the kitchen floor. It appears they may have previously been a radiator in this location.
Photo
Photo 36-1
 

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Location #B: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable

37) It appears that the dryer vent may be leaking due to the lint found in the are where it terminates to the exterior. It is recommended to replace the vent duct and maintain it periodically.
Photo
Photo 37-1
 

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall or plaster
Ceiling type or covering: Drywall or plaster
Condition of flooring: Appeared serviceable
Flooring type or covering: Vinyl, linoleum or marmoleum, Wood or wood products

38) One or more windows that were designed to open and close were difficult to open and close. Recommend that a qualified person repair windows as necessary so they open and close easily.

39)   Some slight weathering found on some widow sills is common due to condensation. Monitor to see if condition gets worse. Replacement is not necessary but a little paint and caulking wound improve its appearance.
Photo
Photo 39-1
Photo
Photo 39-2

Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: Yes
Visible evidence of damage by wood-destroying insects: Yes

40) Evidence of past termite activity was found in the garage located at the jams of the garage door. It is recommended that a exterminator evaluate the current condition and see if further action is necessary.
Photo
Photo 40-1
Screwdriver pushed through jam and dry mud tubes
Photo
Photo 40-2

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Viewed from hatch(es)
Condition of floor substructure above: Appeared serviceable
Condition of insulation underneath floor above: Not applicable, none installed
Vapor barrier present: None visible
Condition of crawl space ventilation: Not determined (inaccessible or obscured)
Ventilation type: Unconditioned space

41)   Views of crawlspace
Photo
Photo 41-1
Photo
Photo 41-2
Photo
Photo 41-3
 

Your default report footer here...