Summary

Client(s):  Mr & Mrs Jefferson
Property address:  1234 Island Ave
John's Creek, GA 30097
Inspection date:  Wednesday, August 28, 2013

This report published on Thursday, October 11, 2018 10:54:26 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)


Grounds
2) Handrails at one or more flights of stairs were not graspable and posed a fall hazard. Handrails should be 1 1/4 - 2 inches in diameter if round, or 2 5/8 inches or less in width if flat. Recommend that a qualified person install graspable handrails or modify existing handrails per standard building practices.
Photo
Photo 2-1 
3) Handrails at one or more flights of stairs were loose, wobbly. This is a safety hazard. Recommend that a qualified person repair as necessary.
Photo
Photo 3-1 
4) Guardrails above retaining walls higher than 30 inches were missing. This is a safety hazard due to the risk of falling. At a minimum, the client should be aware of this hazard, especially when children are present. Recommend that a qualified contractor install or repair guardrails per standard building practices (e.g. minimum 3 feet high, no gaps wider than 4 inches, not climbable). Dense shrubbery or vegetation may be acceptable as a barrier, but only when mature enough to be effective.
Photo
Photo 4-1 
5) One or more deck or porch beams were not positively secured to the support posts below. Deck or porch beams are commonly connected to support posts by "toenailing," which is inadequate. Decks and porches are subject to movement under live loads and require a positive connection between their support posts and beams. Recommend that a qualified contractor repair per standard building practices. For example, by installing metal plates, plywood gussets or dimensional lumber to connect posts and beams.

Examples at the following link; http://www.strongtie.com/deckcenter/index.html
Photo
Photo 5-1 
6) Conducive conditionsSoil was in contact with or too close to wooden deck or porch substructure components. This is a conducive condition for wood-destroying organisms. Clearances to soil should be as follows:
  • 12 inches below beams
  • 18 inches below joists
  • 6 inches below support post bases and other wood components
Pressure treated wood is typically rated for 25 year contact with soil, but the cut ends hidden below grade may not have been treated and can rot quickly. Support posts should be elevated above grade on concrete piers or footings, and be separated from the concrete by metal brackets or an impermeable membrane such as shingle scraps. For other components, soil should be graded and/or removed to maintain these clearances if possible. Otherwise, replacing non-treated wood with treated wood, or installing borate-based products such as Impel rods may help to prevent infestation and damage. For more information, visit:
http://www.reporthost.com/?IMPEL
Photo
Photo 6-1 

Exterior and Foundation
8) One or more hornet, bee, and/or wasp nest were found. These can pose a safety hazard. Nest should be removed as necessary.
Photo
Photo 8-1 
9) Some sections of siding and/or trim were damaged. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 9-1 
Photo
Photo 9-2 
10) One or more exhaust duct end caps were loose. Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and can pose a fire hazard. Recommend that a qualified person repair or replace caps as necessary.
Photo
Photo 10-1 
11) Conducive conditionsSoil was in contact with or less than 6 inches from siding or trim. Regardless of what material is used for siding, it should not be in contact with the soil. If made of wood, siding or trim will eventually rot. For other materials, ground or surface water can infiltrate siding or trim and cause damage to the wall structure. Wood-destroying insects are likely to infest and damage the wall structure. This is a conducive condition for wood-destroying organisms. Recommend grading or removing soil as necessary to maintain a 6-inch clearance. Note that damage from fungal rot and/or insects may be found when soil is removed, and repairs may be necessary.
Photo
Photo 11-1 
12) One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo
Photo 12-1 
13) Conducive conditionsVegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 13-1 
Photo
Photo 13-2 
14) Conducive conditionsThe paint finish, and/or caulk in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or re-stain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 14-1 
Photo
Photo 14-2 
Photo
Photo 14-3 

Basement
16) Conducive conditionsEvidence of prior water intrusion was found in one or more sections of the basement. For example, water stains or rust at support post bases, efflorescence on the foundation, etc. Accumulated water is a conducive condition for wood-destroying organisms and should not be present in the basement. Recommend reviewing any disclosure statements available and ask the property owner about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typical repairs for preventing water from accumulating in basements include:
  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter basements, but if water must be controlled after it enters the basement, then typical repairs include installing a sump pump.
Photo
Photo 16-1 
Photo
Photo 16-2 

Attic and Roof Structure
21) The pull-down attic stairs were not insulated. Typically, such stairs that are not insulated also do not have any weatherstripping installed. Recommend that a qualified person install insulation and weatherstripping per standard building practices for better energy efficiency. For more information, visit:
http://www.reporthost.com/?INSATTSTRS
Photo
Photo 21-1 
Photo
Photo 21-2 
22) Some areas of the ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.
Photo
Photo 22-1 
23) Attic insulation at one or more skylight chases or attic walls has fallen down or come loose from the interior wall surface. Heating and cooling costs will likely be higher due to reduced energy efficiency. Recommend that a qualified person repair, re-secure or install insulation as necessary and per standard building practices.
Photo
Photo 23-1 
Photo
Photo 23-2 
Photo
Photo 23-3 
Photo
Photo 23-4 
Photo
Photo 23-5 
24) The ceiling insulation in one or more areas of the attic was compacted or uneven. Heating and cooling costs may be higher due to reduced energy efficiency. Recommend that a qualified person repair, replace or install insulation as necessary and per standard building practices (typically R-38).
Photo
Photo 24-1 
Photo
Photo 24-2 

Garage or Carport
27) The door between the garage and the house didn't self-latch when closed via the self-closing device because of damage or deterioration to the . House to garage doors prevent fire and fumes from spreading from the garage to the house. Self-closing devices keep the door closed for this purpose. Recommend that a qualified person repair as necessary.
Photo
Photo 27-1 
28) One or more garage vehicle doors had an automatic opener installed, and the manual lock mechanism on the door hadn't been permanently disabled. The automatic opener can be damaged, or injury can occur if the automatic door opener is operated with the manual lock engaged. A qualified person should disable or remove the lock mechanism per standard building practices.
Photo
Photo 28-1 
29) Significant gaps were found below or around one or more garage vehicle doors. Vermin and insects can enter the garage as a result. Recommend that a qualified person repair as necessary to eliminate or minimize gaps.
Photo
Photo 29-1 

Electric
32) Substandard wiring was found at the building exterior. For example, extension or lamp cord used as permanent wiring. This is a safety hazard. Recommend that a qualified electrician evaluate and repair as necessary and per standard building practices.
Photo
Photo 32-1 
33) Smoke alarms were missing from one or more bedrooms. Additional smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM
Photo
Photo 33-1 

Heating, Ventilation and Air Condition (HVAC)
41) The air handler's primary condensate drain line appears to be leaking. Condensate drain water may accumulate, leak and cause water damage to surrounding areas. Recommend that a qualified HVAC contractor repair as necessary.
Photo
Photo 41-1 
Photo
Photo 41-2 
42) The covers for one or more heating and/or cooling system air filters were loose. Unfiltered air can enter the return air supply and reduce indoor air quality. Recommend that a qualified person repair as necessary.
Photo
Photo 42-1 
43) Insulation on the heat pump or air conditioning condensing unit's refrigerant lines was deteriorated or missing in some areas. This may result in reduced efficiency and increased energy costs. Recommend that a qualified person replace or install insulation as necessary.
Photo
Photo 43-1 
44) Recommend replacing or washing HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or washing them as necessary. How frequently they need replacing or washing depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo
Photo 44-1 
Photo
Photo 44-2 

Kitchen
48) An exhaust hood was installed over the cook top or range, but the fan recirculated the exhaust air back into the kitchen. This may be due to no duct being installed, baffles at the front of the hood not being installed, or a problem with the duct. This can be a nuisance for odor and grease accumulation. Where a gas-fired range or cook top is installed, carbon monoxide and excessive levels of moisture can accumulate in living spaces. Recommend that a qualified contractor evaluate and repair as necessary so exhaust air is ducted outdoors.
Photo
Photo 48-1 
49) The oven door handle was loose or damaged. Consult with the property owner. If necessary, a qualified person should repair by tightening or replacing the handle.
Photo
Photo 49-1 
Photo
Photo 49-2 
Photo
Photo 49-3 
50) Cabinet molding was loose, missing or damaged on one or more cabinets. Recommend that a qualified person repair as necessary.
Photo
Photo 50-1 

Bathrooms, Laundry and Sinks
57) Conducive conditionsThe toilet at the master bathroom was loose where it attached to the floor. Leaks can occur. Flooring, the sub-floor or areas below may get damaged. Sewer gases can enter living spaces. Recommend that a qualified contractor remove the toilet(s) for further evaluation and repair if necessary. A new wax ring should be installed and toilet(s) should be securely anchored to the floor to prevent movement and leaking.
Photo
Photo 57-1 
58) Conducive conditionsGaps, no caulk, or substandard caulking were found between the bathtub and the walls at location(s) #. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo
Photo 58-1 
Photo
Photo 58-2 

Interior, Doors and Windows
61) The inspector was unable to verify that the glass used in one or more windows was approved safety glass where required. Window glazing that is not approved safety glass, located in areas subject to human impact, is a safety hazard. Standard building practices generally require that approved safety glass be used in but not limited to the following conditions:
  • Windows with a pane larger than 9 square feet, with a bottom edge closer than 18 inches to the floor and a top edge higher than 36 inches above the floor and within 36 inches, horizontally, of a walking surface
  • Windows that are both within a 24-inch arc of a door and within 60 inches of the floor
  • Glazing in walls enclosing stairway landings or within 5 feet of the bottom and top of stairways, where the bottom edge of the glass is less than 60 inches above the floor
Note that "art glass" (leaded, faceted, carved or decorative) may be an acceptable alternative for safety glass due to its visibility. Also, a 1 1/2-inch-wide protective bar on the accessible side of the glass, placed 34-38 inches above the floor, can serve as an acceptable substitute for safety glass. Recommend that a qualified contractor evaluate further to determine if glazing is approved safety glass, and replace glass if necessary, and per standard building practices.
Photo
Photo 61-1 
62) Trim is damaged and/or missing in one or more areas. Recommend having a qualified contractor replace or repair trim as necessary.
Photo
Photo 62-1 
63) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product:
http://www.reporthost.com/?ECC
Photo
Photo 63-1