Summary Page
| Property Inspection Report (SAMPLE ONLY) | |
| Client(s): | John & Jane Doe |
| Property address: | 123 Main Street Anywhere, GA 30000 |
| Inspection date: | Friday, January 1 2010 |
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
Please Note:
The concerns listed below on the summary page are numbered consistently with their corresponding numbers on the report page. Therefore, you may notice that some concerns are not mentioned on the summary page. This is because the concern was not a major priority to warrant it to be listed on the summary page.

Concerns are shown and sorted according to these types:
| Safety | Poses a risk of injury or death | |
| Repair/Replace | Recommend repairing or replacing | |
| Repair/Maintain | Recommend repair and/or maintenance | |
| Maintain | Recommend ongoing maintenance | |
| Evaluate | Recommend evaluation by a specialist | |
| Comment | For your information |
| Infestation | Evidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) | |
| Damage | Damage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) | |
| Conducive conditions | Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) |
General information
1)
![]()
- This property has one or more fuel burning appliances, and no carbon monoxide alarms are visible. This is a safety hazard. Recommend installing one or more carbon monoxide alarms as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
Exterior
2)
![]()
![]()
- One or more electric receptacles and/or the boxes they are installed in are loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.
3)
![]()
- Rot was found in one or more areas on door trim. A qualified contractor should evaluate and make repairs as necessary, replacing all rotten wood.
4)
![]()
- One or more light fixtures are damaged and/or deteriorated. A qualified electrician should evaluate and repair or replace light fixtures where necessary.
5)
- One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.
6)
- Caulk is missing or deteriorated in some areas and should be replaced and/or applied where necessary. For more information on caulking, visit The Ins and Outs of Caulking.
Garage
11)
![]()
![]()
- The infrared "photo eye" devices that trigger the vehicle door opener's auto-reverse feature were inoperable during the inspection. This is a safety hazard, especially for small children. A qualified contractor should evaluate and make repairs or replace components as necessary. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
12)
![]()
- The vehicle door has an electric opener installed, and the manual lock mechanism on the door hasn't been disabled. Damage or injury may occur if the vehicle door opener is operated with the manual lock engaged. A qualified contractor should disable or remove the lock mechanism. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
13)
- Small area of sheetrock damage on garage wall.
Attic
14)
- Pull-down stairs are installed for the attic access. No insulation is installed above the stairs and no weatherstripping is installed around the hatch perimeter. To reduce air leakage, recommend installing weatherstripping and an insulated hatch cover. An example of one can be seen at http://www.batticdoor.com/
Interior air leaking into the attic results in heating and cooling losses, increased energy costs, and a possible increase in moisture levels in the attic due condensation forming on the underside of the roof sheathing during cold weather.
Heating and cooling
18)
- Air handler filter(s) are dirty and should be replaced now. They should be checked monthly in the future and replaced as necessary.
Kitchen
23)
![]()
- Trip hazard at kitchen and family room from lack of threshold being installed.
24)
- The sink sprayer at the kitchen sink is inoperable or defective. It should be replaced, and by a qualified plumber if necessary.
Bathrooms
27)
- One or more bathtub drains are clogged or drain slowly. Drain(s) should be cleared as necessary, and by a qualified plumber if necessary.
28)
- One or more shower drains are clogged or drain slowly. Drain(s) should be cleared as necessary, and by a qualified plumber if necessary.
29)
- Caulk is missing and/or deteriorated where countertops meet backsplashes in wet areas, such as around sinks. Caulk should be replaced where deteriorated and/or applied where missing to prevent water damage.
Interior rooms
33)
![]()
- Wood flooring in one or more areas is worn, damaged and/or cupping. Recommend having a qualified contractor evaluate and refinish wood flooring as necessary. Possible water entering around rear door.
34)
- Glass in one or more windows is broken. A qualified contractor should replace glass where necessary.