Property Inspection Report
Client(s): Andy Goodbuyer
Property address: 123 Any Street
Our Town, USA
Inspection date: Monday, July 02, 2007
This report published on 1/23/2010 8:26:28 AM EST

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Kitchen
Bathrooms
Interior rooms; energy audit info
 
General information Return to table of contents
Report number: G07-0702
Type of building: Single family
Age of building: 15 years
Present during inspection: Client(s), Realtor(s)
Occupied: No
Weather conditions: Clear
Temperature: Warm
Ground condition: Dry
Front of structure faces: South
Main entrance faces: South
Foundation type: Slab on grade
The following items are excluded from this inspection: Irrigation system, Playground equipment, Water softener system
 
Exterior Return to table of contents
Footing material: Poured in place concrete
Foundation material: Poured in place concrete
Apparent wall structure: Concrete block
Wall covering: Stucco
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Glass panel
1) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
 
Roof Return to table of contents
Roof inspection method: Traversed
Roof type: Gable
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: 15 years
Roof ventilation: Adequate
2) One or more composition shingles are damaged, deteriorated and/or missing, and should be replaced. Leaks may occur as a result. A qualified roofing contractor should evaluate and make repairs as necessary.

Photo 7  
Missing tab on rear plane of roof.
 
 
Attic Return to table of contents
Inspection method: Traversed
Roof structure type: Trusses
Ceiling structure: Trusses
Insulation material: Cellulose loose fill
Insulation depth: 6 inches
Insulation estimated R value: R 18
3) One or more exhaust fan ducts terminate in attic because no vent cap is installed at the roof or exterior wall surfaces. This is a conducive condition for wood destroying insects and organisms due to increased moisture levels in the attic from the exhaust air. A qualified contractor should evaluate and install vent caps where missing and as per standard building practices, so all exhaust air is vented outside.

Photo 3  
Exhaust fan from guest bathroom not vented to the exterior.
 
 
Electric service Return to table of contents
Primary service type: Underground
Primary service overload protection type: Fuses
Service amperage (amps): 200
Service voltage (volts): 120/240
Location of main disconnect: Breaker at top of main service panel
Service entrance conductor material: Aluminum
System ground: Ground rod(s) in soil
Main disconnect rating (amps): 200
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: No
Smoke detectors present: Yes
4) Scorched receptacle outlet due to arcing. Outlet should be repaired by qualified licensed contractor.

Photo 6  
Scorching due to arcing. Family room rear wall.
 
 
Water heater Return to table of contents
Estimated age: 5 years
Type: Tank
Energy source: Electricity
Capacity (in gallons): 50
Manufacturer: American
Model: XYZ123
 
Heating and cooling Return to table of contents
Estimated age: 15 years
Primary heating system energy source: Electric
Primary heat system type: Forced air
Primary A/C energy source: Electric
Primary Air conditioning type: Split system
Distribution system: Flexible ducts
Manufacturer: Amana
Model: 123XYZ
Filter location: Behind return air grill
Last service date: 06/06
5) Signs of moisture accumulation seen at the base of the air handler.
recommend repair by licensed qualified contractor.

Photo 1  
Signs of puddling at base of air handler
 
 
Plumbing and laundry Return to table of contents
Water pressure (psi): 55 psi
Location of main water shut-off valve: Front left yard near mailbox.
Location of main water meter: Same
6) The clothes dryer is equipped with a vinyl or foil, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, see http://www.cpsc.gov/CPSCPUB/PUBS/5022.html
7) The clothes dryer exhaust duct is broken or disconnected in one or more places. Clothes dryers produce large amounts of moisture which should not enter structure interiors. Damage to building components may result. A qualified contractor should evaluate and make permanent repairs as necessary. For more information, visit http://www.cpsc.gov/CPSCPUB/PUBS/5022.html
 
Kitchen Return to table of contents

8) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
9) One or more sink drains have an active leak. For example, at pipe fittings and/or junctions between pipe and sink. A qualified plumber should evaluate and repair as necessary.

Photo 5  
Drain line under kitchen sink shows signs of leaking.
 
 
Bathrooms Return to table of contents

10) One or more toilets "run" after being flushed, where water leaks from the tank into the bowl. Significant amounts of water can be lost through such leaks. A qualified plumber should evaluate and repair or replace components as necessary.
 
Interior rooms; energy audit info Return to table of contents

11) Insulation is missing or out of place.

Missing insulation batt in guest bedroom wall

Photo 4  
Thermal image of missing insulation batt in guest bedroom wall.

Photo 9  
Void in attic blown-in insulation

Photo 10  
Missing batt.
Note thermal bridging at furring strips under sheetrock

Photo 11  
Missing batts

Photo 12  
Attic hatchway door not insulated
 

12)   AC supply air leaking from air handler into garage.

Photo 8  
 

13)   Thermal bridging at metal window frames allowing heat loss from interior of house.

Photo 13  

Photo 14  

 
If repairs are made to a property based on the results of an inspection, the work should be performed by qualified contractors, not the seller. By qualified, we mean licensed, bonded, state certified where applicable and with a reasonable amount of experience. Contractors providing repairs should provide legible documentation in the form of work orders and/or receipts. If repairs are made in this way there's generally no need for a follow -up inspection.