Inspector: John Allison
NYS license #16000067163

   

Property Inspection Report

Client(s):  Karen Client
Property address:  22 Blue Pond Drive
Woodsville, NY
Inspection date:  Friday, December 11, 2015

This report published on Wednesday, January 13, 2016 7:19:09 AM EST

International Association of Certified Home Inspectors
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings


General Information
Return to table of contents

Neighborhood: Rural area
Report number: 2012-12-11-02
Time started: 2:30 pm
Time finished: 4:15 pm
Name of Inspector: John H. Allison
Lic #: License # 16000067163
Present during inspection: Client, Caretaker
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: 41-50 degrees Fahrenheit
Ground condition: Moist
Inspection fee: $388
Payment method: Check
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: C. 2006
House Address Number: No house address number was observed
Not Inspected: Septic System, Generator
Front of building faces: South
Main entrance faces: South
Occupied: Yes, Furniture or stored items were present

1) Some areas and items at this property were obscured by furniture and/or stored items. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
Photo
Photo 1-1
Photo
Photo 1-2

2) When purchasing a new home Hollis Home Inspection recommends changing the locks. Over time, previous owners may have distributed keys to family or friends. A new set of locks would help ensure privacy and security.
Photo
Photo 2-1
Photo
Photo 2-2

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Moderate slope
Condition of driveway: Appeared serviceable
Driveway material: Gravel
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Gravel
Deck Condition: Serviceable
Condition porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Wood

3) This property was accessed by a driveway shared with nearby properties. Shared driveways or access roads are excluded from this inspection. Comments in this report related to them are made as a courtesy only and are not meant to be a substitute for a evaluation by a specialist if repairs are needed. Recommend that the client review the recorded agreements regarding the driveway, the deeds of the property owners involved, and easements permitting access to, use of, and maintenance of the driveway.
Photo
Photo 3-1
Photo
Photo 3-2

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Unfinished basement
Foundation/stem wall material: Poured in place concrete

4) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
Photo
Photo 4-1
Photo
Photo 4-2

5) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 5-1
Photo
Photo 5-2

6) Siding of home observed as bleeding sap. Sap is a natural byproduct of lumber. Oozing or bleeding sap is more common in newer siding and only considered a cosmetic issue. Oozing sap may cease after several seasons of exposure. If removal of sap is desired scraping sap, wiping excess with turpentine, and repainting may help improve appearance.
Photo
Photo 6-1
Photo
Photo 6-2

Basement
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Fiberglass or vinyl
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood
Beam material: Built-up wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Insulation material underneath floor above: None visible

7) Handrails at one or more flights of stairs were missing. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high. Recommend that a qualified contractor install handrails where missing and per standard building practices.
Photo
Photo 7-1
Photo
Photo 7-2

8) Guardrails at one or more locations with drop-offs higher than 30 inches were missing. This poses a fall hazard. Guardrails should be installed where walking surfaces are more than 30 inches above the surrounding grade or surfaces below. Recommend that a qualified contractor install guardrails where missing and per standard building practices.
Photo
Photo 8-1
Photo
Photo 8-2

9) No insulation was installed under the floor above the unheated basement. Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.
Photo
Photo 9-1
Photo
Photo 9-2

10) Small cracks were observed in basement foundation wall. Small cracks do not appear to be a structural concern and may be due to shrinkage during curing process. However, moisture may infiltrate crack, freeze, enter the basement, or clause deterioration. Recommend hiring a qualified contractor to seal crack as necessary.
Photo
Photo 10-1
Photo
Photo 10-2

11) Foundation wall form ties observed without sealant. Steel form ties remain within poured concrete wall after curing and can absorb moisture, rust, and cause deterioration if exposed. Sealing recessed areas from form ties can help promote basement dryness and a longer lasting wall. Recommend hiring a qualified mason to seal form ties.
Photo
Photo 11-1
Photo
Photo 11-2

12) Dehumidifier and dessicant product noted in basement. A dehumidifier may indicate past or ongoing issues with moisture in the basement. Maintaining a dry basement may require use of dehumidifier. Recommend consulting with owner regarding past use and need for basement dehumidification. It is also recommended to monitor basement for signs of moisture accumulation.
Photo
Photo 12-1
Photo
Photo 12-2

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Viewed from ground
Condition of roof surface material: Appeared serviceable
Roof surface material: Metal panel
Roof type: Gable
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: None

13) The majority of the roof did not have gutters installed. Without gutters installed rainwater may be deposited close to the house and foundation. This may cause damage to exterior surfaces, add moisture to the basement, or create moist conditions which may encourage wood destroying organisms or mold growth. Recommend hiring a qualified contractor to install gutters and downspouts as necessary.
Photo
Photo 13-1
Photo
Photo 13-2

14)   Roof appeared in good condition. Metal panel roof observed intact and without defect. Roof observed in plane, with proper type and frequency of fasteners installed, and coating/paint in good condition. Soffit and ridge vents noted installed for ventilation. No penetration noted in roof. Age of roof is estimate to be 7 years old. Metal panel roof expected useful lifespans can vary between manufacturer and installation. However, it is not uncommon for roof covering to last 50 years or more. Recommend performing maintenance as suggested by manufacturer.
Photo
Photo 14-1
Photo
Photo 14-2
Photo
Photo 14-3
Photo
Photo 14-4

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Condition of roof structure: Not determined (inaccessible or obscured)
Roof structure type: Rafters
Condition of insulation in attic (ceiling, skylight chase, etc.): Not determined (inaccessible or obscured)
Vermiculite insulation present: None visible
Vapor retarder: Not determined (inaccessible or obscured)
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Ridge vent(s), Enclosed soffit vents
Ventilation baffles: Not visible

15) One or more exhaust fan ducts terminated at a soffit vent rather than at a dedicated hood or cap. Soffit vents are designed to allow cool air to be drawn into the attic, and to prevent excess moisture from accumulating in the attic. When such ducts are routed to terminate at soffit vents, the moist exhaust air may flow back into the attic and the soffit venting will be reduced. Recommend that a qualified contractor repair per standard building practices. For example, by installing approved hoods or caps at the roof surface or exterior wall(s), and permanently securing exhaust ducts to them.
Photo
Photo 15-1
Photo
Photo 15-2

16) No accessible attic spaces were found or inspected at this property. The inspector attempted to locate attic access points and evaluate attic spaces where possible. Such access points may not exist. If such access points are found in the future and/or made accessible, Hollis Home Inspection offers to return and fully evaluate those attic spaces and roof structures for no additional charge.
Photo
Photo 16-1
Photo
Photo 16-2

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Not determined, not readily apparent
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Basement
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: Yes
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested

17) One or more circuit breakers in panel(s) #A were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?DBLTAP
Photo
Photo 17-1
Photo
Photo 17-2

18) One or more cover plates for switches, receptacles (outlets) or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 18-1
Photo
Photo 18-2

19) One or more light fixtures were not energized. Recommend that a qualified electrician repair or replace light fixtures as necessary.
Photo
Photo 19-1
Photo
Photo 19-2

20) Grounding system of electrical system of house may need evaluation. Standard building practices require 2 forms of grounding for electric panels. Common forms of grounding are usually a connection to the cold water main or connection to a interior or exterior ground rod. No wire serving as house ground was found. Recommend hiring a qualified electrical contractor to evaluate grounding of electrical system and repair if necessary.
Photo
Photo 20-1
Photo
Photo 20-2

21) Home had a backup generator system installed which was not tested. Gasoline powered generator and lead cord noted in basement storage. Recommend consulting with manufacturer for instruction on proper use, care, and maintenance.
Photo
Photo 21-1
Photo
Photo 21-2

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Private well
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: PEX plastic
Condition of drain pipes: Required repair, replacement and/or evaluation (see comments below)
Drain pipe material: Plastic
Condition of waste lines: Required repair, replacement and/or evaluation (see comments below)
Waste pipe material: Plastic
Vent pipe condition: None noted
Sump pump installed: No
Sewage ejector pump installed: No
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: propane tank, oil tank, in yard, in basement
Location of main fuel shut-off valve: At propane tank, At oil tank

22) One or more leaks were found in waste pipes or fittings. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 22-1
Photo
Photo 22-2

23) One or more leaks were found in water supply valves. A qualified plumber should repair as necessary.
Photo
Photo 23-1
Photo
Photo 23-2

24) No plumbing vent was noted installed on roof. Plumbing vents which are required by standard building practices are important because they allow air into waste system plumbing which promotes proper draining. Plumbing vents also allow any sewer gasses that may be present in waste system plumbing to safely exit home. Without plumbing vent installed home may be more likely to have drain/waste plumbing issues or allow sewer gasses into home which may be harmful the occupants. Recommend having a qualified plumber evaluate and repair as necessary.
Photo
Photo 24-1
Photo
Photo 24-2

25) Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC
Photo
Photo 25-1
Photo
Photo 25-2

26) This property was unoccupied and/or recently de-winterized, and the plumbing system has not been in continuous operation recently. It's possible for plumbing leaks to exist but not be apparent. Leaks can be small and take time to become visible. The inspector normally operates all accessible and operable plumbing fixtures, but this limited inspection may not reveal small leaks that only become visible after constant use of the plumbing system. After taking occupancy, monitor the plumbing system for leaks that may become apparent. Areas below the house should be evaluated after plumbing has been operated to check for leaks. Any problems that are found should be repaired by a qualified plumber.

27) Based on visible equipment or information provided to the inspector, the water supply to this property appeared to be from a private well. Private well water supplies are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. The inspector does not test private well water for contamination or pollutants, determine if the supply and/or flow are adequate, or provide an estimate for remaining life of well pumps, pressure tanks or equipment. Only visible and accessible components are evaluated. Recommend the following:
  • That a qualified well contractor fully evaluate the well, including a pump/flow test
  • That the well water be tested per the client's concerns (coliforms, pH, contaminants, etc.)
  • Research the well's history (how/when constructed, how/when maintained or repaired, past performance, past health issues)
  • Document the current well capacity and water quality for future reference
For more information, visit:
http://www.reporthost.com/?WELL
Photo
Photo 27-1
Photo
Photo 27-2
Photo
Photo 27-3
Photo
Photo 27-4

28) A well flow test was performed by request of the client. Well flow tests are designed to simulate a continuous demand for water over a period of time to ensure that well components may hold up to demands of being occupied. Well flow test produced consistent results of 3 and 3/4 gallons per minute taken at 10 minute intervals within an hour. This well exceeds the 3 gallon per minute standard.
Photo
Photo 28-1
Photo
Photo 28-2

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Estimated age: 3 years
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement

29) Water heater serving upstairs had no safety extension noted on TPR Valve. A safety extension is installed so that in the event of the water heater overheating the scalding overflow is carried safety to the ground. Recommend hiring a qualified plumber to install safety extension on TPR Valve.
Photo
Photo 29-1
Photo
Photo 29-2

30) Water heater operated and provided hot water which was received at one or more fixtures at time of inspection. Electric [!GE!Bradford White!A.O.Smith!Whirlpool!American] brand [!30!40!50] gallon water heater noted in good condition. [!Water supply valve! TPR valve! TPR extension! electric shutoff switch! ground screw securing ground wire] and drain cock noted installed on unit. Age of water heater was referenced from serial number as [!1!2!3!4!5!6!7!8!9!10!11!12] years old (c.[!2001!2002!2003!2004!2005!2006!2007!2008!2009!2010!2011!2012!2013!2014!2015!2016]). This puts water heater at approximately [!less than 1/4!1/4!1/3!1/2!2/3!3/4] of the way through its expected useful lifespan. Recommend performing maintenance as necessary as suggested by manufacturer in order to promote safe, efficient, and continued operation.
Photo
Photo 30-1
Photo
Photo 30-2
Photo
Photo 30-3
Photo
Photo 30-4

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Furnace, Wood-burning fireplace or stove
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Oil
Location of forced air furnace: Basement
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: No dedicated source visible, uses room air
Condition of venting system: Required repair, replacement and/or evaluation (see comments below)
Condition of controls: Appeared serviceable

31) Power vented furnace exhaust may not be adequately venting furnace. Fumes from oil combustion were detected strongly in basement. When working properly venting system should not create odor of burnt oil. In this condition harmful exhaust gasses such as carbon monoxide may enter building which could be harmful to health of occupants. Recommend having a qualified HVAC technician evaluate furnace/power venting system and repair as necessary before use of furnace.
Photo
Photo 31-1
Photo
Photo 31-2

32) Furnace fired and gave heat which was received at one or more registers at time of inspection. Carrier brand oil fired furnace noted with orange flame. Furnace air filter observed in good condition. Recommend checking air filter monthly for necessary replacement. Neither date of manufacturer nor serial number was identified by inspector. Oil tank, oil filter, and shutoff valve all noted installed in basement and in good condition. Furnace exhaust was power vented out side wall of house (See additional Concern). Therefore, age of unit could not be referenced. However, age of unit is not estimated to exceed age of home (7 years, c. 2008). This puts furnace at less than 1/4 of the way through its 25 year expected useful lifespan. Recommend having furnace serviced now and annually by a qualified HVAC technician in order to promote safe, efficient, and continued operation.
Photo
Photo 32-1
Photo
Photo 32-2
Photo
Photo 32-3
Photo
Photo 32-4

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Wood-burning stove type: Freestanding
Condition of chimneys and flues: Required repair, replacement and/or evaluation (see comments below)
Wood-burning chimney type: Metal

33) One or more chimneys for wood-burning devices were too short. Fireplace and/or wood stove chimneys should terminate more than 3 feet above the roof surface and/or more than 2 feet above any object on the roof within 10 feet horizontally. Shorter chimneys can have a drafting problems due to air turbulence around the roof or building structure. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 33-1
Photo
Photo 33-2

34) One or more chimneys for wood-burning devices were less than 15 feet in height above the device. Such chimneys should be at least 15 feet in height for adequate drafting and to prevent exhaust gases from entering living spaces. Recommend that a qualified contractor repair per standard building practices.
Photo
Photo 34-1
Photo
Photo 34-2

35) One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
Photo
Photo 35-1
Photo
Photo 35-2

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: Not tested
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Shut down
Condition of built-in microwave oven: Appeared serviceable

36) An exhaust hood was installed over the cook top or range, but the fan recirculated the exhaust air back into the kitchen. This may be due to no duct being installed, baffles at the front of the hood not being installed, or a problem with the duct. This can be a nuisance for odor and grease accumulation. Where a gas-fired range or cook top is installed, carbon monoxide and excessive levels of moisture can accumulate in living spaces. Recommend that a qualified contractor evaluate and repair as necessary so exhaust air is ducted outdoors.
Photo
Photo 36-1
Photo
Photo 36-2

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, first floor
Location #B: Laundry room/area, first floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows, Spot exhaust fans
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes

37) The sink drain pipe at location(s) #A used an S-trap rather than a P-trap, or no P-trap was visible. Siphons and sudden flows of water in S-Traps can drain all the water out of the trap, leaving it dry. Sewer gases can then enter living areas. Recommend that a qualified plumber repair per standard building practices.
Photo
Photo 37-1
Photo
Photo 37-2

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Fiberglass or vinyl
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Multi-pane, Double-hung
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall, Wood
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Wood or wood products, Concrete
Condition of stairs, handrails and guardrails: Appeared serviceable

Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood-destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood-destroying organisms: No


Photo
Photo X-1
Photo
Photo X-2
Photo
Photo X-3
Photo
Photo X-4
Photo
Photo X-5
Photo
Photo X-6
Photo
Photo X-7
Photo
Photo X-8
Photo
Photo X-9
Photo
Photo X-10
Photo
Photo X-11
Photo
Photo X-12
Photo
Photo X-13
Photo
Photo X-14
Photo
Photo X-15
Photo
Photo X-16
Photo
Photo X-17
Photo
Photo X-18
Photo
Photo X-19
Photo
Photo X-20
Photo
Photo X-21
Photo
Photo X-22
Photo
Photo X-23
Photo
Photo X-24
Photo
Photo X-25
Photo
Photo X-26
Photo
Photo X-27
Photo
Photo X-28
Photo
Photo X-29
Photo
Photo X-30
Photo
Photo X-31
Photo
Photo X-32
Photo
Photo X-33
Photo
Photo X-34
Photo
Photo X-35
Photo
Photo X-36
Photo
Photo X-37
Photo
Photo X-38
Photo
Photo X-39
Photo
Photo X-40
Photo
Photo X-41
Photo
Photo X-42
Photo
Photo X-43
Photo
Photo X-44
Photo
Photo X-45
Photo
Photo X-46
Photo
Photo X-47
Photo
Photo X-48
Photo
Photo X-49
Photo
Photo X-50
Photo
Photo X-51
Photo
Photo X-52
Photo
Photo X-53
Photo
Photo X-54
Photo
Photo X-55
Photo
Photo X-56
Photo
Photo X-57
Photo
Photo X-58
Photo
Photo X-59
Photo
Photo X-60
Photo
Photo X-61
Photo
Photo X-62
Photo
Photo X-63
Photo
Photo X-64
Photo
Photo X-65
Photo
Photo X-66
Photo
Photo X-67
Photo
Photo X-68
Photo
Photo X-69
Photo
Photo X-70
Photo
Photo X-71
Photo
Photo X-72
Photo
Photo X-73
Photo
Photo X-74
Photo
Photo X-75
Photo
Photo X-76
Photo
Photo X-77
Photo
Photo X-78
Photo
Photo X-79
Photo
Photo X-80
Photo
Photo X-81
Photo
Photo X-82
Photo
Photo X-83
Photo
Photo X-84
Photo
Photo X-85
Photo
Photo X-86
Photo
Photo X-87
Photo
Photo X-88
Photo
Photo X-89
Photo
Photo X-90
Photo
Photo X-91
Photo
Photo X-92
Photo
Photo X-93
Photo
Photo X-94
Photo
Photo X-95
Photo
Photo X-96
Photo
Photo X-97
Photo
Photo X-98
Photo
Photo X-99
Photo
Photo X-100
Photo
Photo X-101
 

Thank you for hiring Hollis Home Inspection LLC. It is our honor to be a part of your home buying process. Our goal is to communicate our findings clearly and concisely. We encourage our clients to contact us with any questions or concerns. Please call/text us: (518) 421-6069 of emails us: john@hohospec.com. We look forward to hearing from you.