Property Inspection Report
Client(s): Eric Desman
Property address: 12940 Wyckland Dr.
Clifton, VA
Inspection date: Monday, July 06, 2009
This report published on 7/7/2009 10:46:07 AM EDT

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Kitchen
Bathrooms
Interior rooms

 
General information Return to table of contents
Report number: 20090706001
Inspector: Joseph Weissglass
Structures inspected: Single Family Detached
Age of building: 8 years
Time started: 7:30
Time finished: 12:30
Inspection Fee: $670
Payment method: Invoiced
Present during inspection: Client(s), Realtor(s)
Occupied: No, but furnishings and stored items are present
Weather conditions: Partly cloudy
Temperature: Warm
Foundation type: Finished basement
The following items are excluded from this inspection: Security system, Irrigation system, Swimming pool, Hot tub, Private well, Playground equipment, Water softener system, Intercom system
1) Safety, Repair/Replace - This property has one or more fuel burning appliances, and no carbon monoxide alarms are visible. This is a safety hazard. Recommend installing one or more carbon monoxide alarms as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
2) Safety, Evaluate - Radon testing indicated levels of 8 pCi/L. The EPA has set an action level at 4 pCi/L. A qualified contractor should install radon mitigation system(s) in order to reduce the radon levels.
3) Comment - Many wall, floor and/or ceiling surfaces were obscured by large amounts of furniture and/or stored items. Many areas couldn't be fully evaluated.

Photo 72  

Photo 73  

Photo 74  

Photo 75  

Photo 76  

Photo 77  

 
Exterior Return to table of contents
Footing material: Not visible
Foundation material: Poured in place concrete
Apparent wall structure: Wood frame
Wall covering: Brick veneer
Driveway material: Asphalt
Sidewalk material: N/A
4) Safety, Repair/Replace, Evaluate - Non-metallic sheathed wiring is routed in one or more areas so it is subject to damage, such as on wall or ceiling surfaces. The insulation can be damaged by objects coming in contact with it and/or it being repeatedly moved. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary. For example, rewire using conduit, or re-routing through wall cavities.

Photo 173  
 

5) Safety, Repair/Replace - The pool gate near the pool equipment does not have a lock installed currently. Repairs should be made to allow the gate to lock.

Photo 32  
 

6) Safety, Repair/Replace - One or more flights of stairs with more than two risers have no handrail installed. This is a safety hazard. A qualified contractor should install graspable handrails that your hand can completely encircle at stairs where missing, and as per standard building practices.

Photo 65  
 

7) Safety, Repair/Replace - A stone on the stairs leading to the pool is loose and should be repaired by a qualified contractor.

Photo 64  
 

8) Repair/Replace - One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.

Photo 7  

Photo 15  

Photo 34  

Photo 38  

Photo 67  
 

9) Maintain - Caulk is missing or deteriorated in some areas and should be replaced and/or applied where necessary. For more information on caulking, visit The Ins and Outs of Caulking.

Photo 6  

Photo 10  

10) Evaluate - One or more light fixtures appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.

Photo 4  

Photo 5  

Photo 15  
 

11) Evaluate - Settlement has occured at some areas surrounding the home. This does not present a structural concern, but may be repaired for aesthetic reasons.

Photo 53  

Photo 54  

12) Comment - Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
 
Roof Return to table of contents
Roof inspection method: Viewed from ground with binoculars
Roof type: Hipped
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: 8 years
Gutter & downspout material: Aluminum
Roof ventilation: Adequate
 
Garage Return to table of contents

13) Safety, Repair/Replace - The garage-house door isn't equipped with an automatic closing device such as sprung hinges. This door should close and latch automatically to prevent vehicle fumes from entering living spaces and/or to slow the spread of fire from the garage to living spaces. A qualified contractor should install automatic closing device(s) as necessary, and as per standard building practices, so this door closes and latches automatically.
14) Comment - Much of the garage, including areas around the interior perimeter and in the center are excluded from this inspection due to lack of access from stored items.

Photo 128  
 

15) Comment - One or more vehicle doors were inaccessible due to stored items and/or debris, and couldn't be operated or fully evaluated.
 
Attic Return to table of contents
Inspection method: Viewed from hatch, Partially traversed
Roof structure type: Trusses
Ceiling structure: Trusses
Insulation material: Mineral wool loose fill
Insulation depth: 14"
Insulation estimated R value: R-30
16) Repair/Replace, Evaluate - A bottom cord on a roof truss is broken at the framing plate. A qualified engineer should evaluate and suggest repairs to be completed by a qualified contractor.

Photo 176  

Photo 177  

 
Electric service Return to table of contents
Primary service type: Underground
Primary service overload protection type: Circuit breakers
Service amperage (amps): 400
Service voltage (volts): 120/240
Location of main disconnect: Breaker at bottom of main service panel
Service entrance conductor material: Aluminum
Main disconnect rating (amps): 200
Solid strand aluminum branch circuit wiring present: No
Smoke detectors present: Yes
 
Water heater Return to table of contents
Estimated age: 8 years
Type: Tank
Energy source: Propane
Capacity (in gallons): 75
Manufacturer: Bradford White
 
Heating and cooling Return to table of contents
Estimated age: 8 years
Primary heating system energy source: Propane gas
Primary heat system type: Forced air
Primary A/C energy source: Electric
Distribution system: Sheet metal ducts, Flexible ducts
Manufacturer: Trane
Filter location: In return air duct below furnace, Behind return air grill
17) Maintain - Air handler filter(s) are dirty and should be replaced now. They should be checked monthly in the future and replaced as necessary.
18) - The furnace fresh air intakes terminate inside the structure of the home. This condition can create a vacuum condition within the home, drawing cold air into the home during heating seasons. These fresh air intakes should be extended outside of the structure to mitigate this condition and to ensure appropriate fresh air supply is available.

Photo 169  

Photo 174  

 
Plumbing and laundry Return to table of contents
Water service: Private
Supply pipe material: Copper, CPVC
19) Repair/Replace, Evaluate - Recommend having the septic tank inspected. Recommend having the tank pumped if it was last pumped more than 3 years ago.

Photo 44  

Photo 45  

Photo 46  
 

20) Minor Defect - The available water pressure was low at the time of the inspection.

Photo 88  
 

21) Comment - The clothes washer had clothing in it and was not operated during this inspection. The inspector was unable to fully evaluate the washer and its drain line.

Photo 127  
 

 
Fireplaces, woodstoves and chimneys Return to table of contents
Fireplace type: Masonry, Metal prefabricated
22) Comment - All solid fuel burning appliances (woodstoves and fireplaces, etc.) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
 
Kitchen Return to table of contents

23) Safety, Repair/Replace, Evaluate - One or more electric receptacles and/or the boxes they are installed in are loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.

Photo 137  

Photo 138  

 
Bathrooms Return to table of contents

24) Repair/Maintain - Caulk is missing and/or deteriorated at one or more bathtubs. For example, where the tub base meets the floor below, where the tub surround meets the tub, and/or around the base of the tub spout. Caulk should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to wall and floor structures.

Photo 96  

Photo 98  

Photo 106  

Photo 107  

Photo 116  

Photo 118  

Photo 119  
 

25) Repair/Maintain - Caulk is missing and/or deteriorated at one or more showers. For example, where the shower base meets the floor below and/or around the shower surround. Caulk should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to wall and floor structures.

Photo 90  

Photo 91  

Photo 92  
 

 
Interior rooms Return to table of contents

26) Safety, Repair/Replace - Lamp holders or light fixtures with fully or partially exposed bulbs are installed in one or more closets. This is a safety hazard due to the risk of fire. Flammable stored items may come into contact with hot bulbs, and hot fragments from broken bulbs may fall on combustible materials. Standard building practices require closet lighting to use fluorescent light fixtures, or to use fully enclosed incandescent fixtures. Installing a compact fluorescent lamp in a lamp holder is not an acceptable practice. A qualified electrician should replace closet lights as necessary and as per standard building practices.

Photo 82  
 

27) Safety, Minor Defect - Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

Photo 129  

Photo 133  

28) Repair/Replace - One or more windows in the kitchen that were built to open, will not open, or open only minimally due to their being painted shut, damaged and/or deteriorated in some way. Repairs should be made as necessary, and by a qualified contractor if necessary so windows open fully, and open and close easily.
29) Repair/Replace - The lockset at the door leading from the family room to the screened porch is loose and should be tightened, repaired and or replaced as necessary.

Photo 135  
 

30) Monitor - Stains were found in the ceiling in the basement bedroom. However, no elevated levels of moisture were found. The stain(s) may be due to past plumbing leaks. Recommend asking the property owner(s) about this, and monitoring the stained area(s) in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, a qualified contractor should evaluate and repair as necessary.

Photo 136  
 

31) Comment - Minor cracks were found in ceilings in one or more areas. They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.

Photo 83  

Photo 115  

Photo 123  

Photo 124  
 

Photo 1  

Photo 8  

Photo 9  

Photo 11  

Photo 12  

Photo 13  

Photo 14  

Photo 16  

Photo 17  

Photo 18  

Photo 19  

Photo 20  

Photo 21  

Photo 22  

Photo 23  

Photo 24  

Photo 25  

Photo 26  

Photo 27  

Photo 28  

Photo 29  

Photo 30  

Photo 31  

Photo 33  

Photo 35  

Photo 36  

Photo 37  

Photo 39  

Photo 40  

Photo 41  

Photo 42  

Photo 43  

Photo 47  

Photo 48  

Photo 49  

Photo 50  

Photo 51  

Photo 52  

Photo 55  

Photo 56  

Photo 57  

Photo 58  

Photo 59  

Photo 60  

Photo 61  

Photo 62  

Photo 63  

Photo 66  

Photo 68  

Photo 69  

Photo 70  

Photo 71  

Photo 78  

Photo 79  

Photo 80  

Photo 81  

Photo 84  

Photo 85  

Photo 86  

Photo 87  

Photo 89  

Photo 93  

Photo 94  

Photo 95  

Photo 97  

Photo 99  

Photo 100  

Photo 101  

Photo 102  

Photo 103  

Photo 104  

Photo 105  

Photo 108  

Photo 109  

Photo 110  

Photo 111  

Photo 112  

Photo 113  

Photo 114  

Photo 117  

Photo 120  

Photo 121  

Photo 122  

Photo 125  

Photo 126  

Photo 130  

Photo 131  

Photo 132  

Photo 134  

Photo 139  

Photo 140  

Photo 141  

Photo 142  

Photo 143  

Photo 144  

Photo 145  

Photo 146  

Photo 147  

Photo 148  

Photo 149  

Photo 150  

Photo 151  

Photo 152  

Photo 153  

Photo 154  

Photo 155  

Photo 156  

Photo 157  

Photo 158  

Photo 159  

Photo 160  

Photo 161  

Photo 162  

Photo 163  