Home Inspection Report |
| Client(s): |
John & Mary Brown |
| Property address: |
Autumn Glory Huntsville, AL |
| Inspection date: |
8/4/2011 |
This report published on Tuesday, October 18, 2011 8:54:14 AM CDT
View summary page
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.This inspection is a limited visual report of the general condition of the home and its major components at the time of the inspection. Please review the pre-inspection agreement that you have been provided for an explanation of the scope and restrictions of this report.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types: | Safety | Poses a risk of injury or death |
 | Repair/Replace | Recommend repairing or replacing |
 | Repair/Maintain | Recommend repair and/or maintenance |
 | Evaluate | Recommend evaluation by a specialist |
 | Monitor | Recommend monitoring in the future |
 | Comment | For your information |
Click here for a glossary of building construction terms.
Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp
Report number: 080411
Type of building: Single family
Age of building: Approximately 3 years
Time started: 9:00 am
Time finished: 1:30 pm
Present during inspection: Client(s)
Occupied: No
Weather conditions: Rain
Temperature: Warm
Ground condition: Wet
Front of structure faces: West
Foundation type: Crawlspace
The following items are excluded from this inspection: Private sewage disposal system, Security system, Irrigation system, Central vacuum system
1)
Cosmetic issues and concerns are the responsibility or the buyers.
Footing material: Not visible
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Wood clapboard, Cement-based clapboard, Brick veneer, Stone veneer
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core wood
2)


The vent stack for the vented gas log fireplace is too short and too close to the upper structure. The concern is that if an accidental combustion occurred flames would exit at a point close to combustible materials. This should be evaluated by a certified technician other than the installer who obviously approved this location.

Photo 44
|
|
3)

Brick pavers installed for patios and porches have not been filled with a surface sand material to prevent movement. There are separations where pavers meet structure. One area at front porch has algae growing. The stepped down area at rear porch has settled and causes a trip / fall hazard.

Photo 15
|

Photo 16
|

Photo 33
|
|
4)

Hand rails are required where stairs have 3 or more risers. Hand rails are not present at side steps.

Photo 5
|
|
5)

The plumbing clean out pipe protrudes from ground in rear yard and is a trip / fall and mowing hazard.

Photo 12
|
|
6)

Yard has several bare areas and there is a hole at SE yard posing a trip / fall hazard.

Photo 7
|

Photo 18
|

Photo 19
|
|
7)

Gas valve is not secured to structure.

Photo 24
|
|
8)

The rear steps have uneven riser heights which pose a trip / fall hazard.

Photo 20
|
|
9)
Gas line connection on rear/side porch is too short for use. It must be extended and cut off valve installed. Brick is also missing from this area.

Photo 6
|
|
10)
Areas where mechanical lines or fixtures are attached or penetrate structure are not sealed.

Photo 17
|

Photo 29
|

Photo 39
|

Photo 40
|
11)
Trim pieces at rear fireplace below shingles are deformed and there is a hole at right side.

Photo 21
|

Photo 22
|

Photo 23
|
|
12)
Where half columns are installed the gaps next to brick greatly vary in size and the seals are broken in some areas.

Photo 25
|

Photo 26
|
13)
There is a piece of siding at front gable above garage that is loose.

Photo 31
|
|
14)
A large gap at front porch between frieze and the stone veneer is present.

Photo 34
|

Photo 35
|

Photo 36
|
|
15)
Door bell buttons are loose and or broken.

Photo 27
|

Photo 37
|
16)
The 2 disconnects for the HVAC compressors do not have inner cover plates leaving exposed wires when outer cover is open.

Photo 10
|

Photo 11
|
17)
Font porch column bases are not sealed.

Photo 38
|
|
18)
Weather stripping at garage pedestrian door is deformed.

Photo 28
|
|
19)
Window screens are not present.
20)
Crawl space door is not painted or sealed.

Photo 79
|
|
21)
There are several separations in the brick steps which allow water penetration and in winter may freeze causing further damage.

Photo 13
|

Photo 14
|

Photo 32
|

Photo 41
|
22)
Door from breakfast room has been trimmed but not painted.

Photo 47
|
|
23)

Could not determine termination point of downspout extensions.
24)
Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.

Photo 30
|
|
25)
Septic system is private, 2 maintenance covers are present in rear yard.

Photo 3
|
|
26)
Propane tank is buried at side yard.

Photo 4
|
|
Roof inspection method: Viewed from ground with binoculars, Viewed from windows, partially traversed
Roof type: Cross gable, Hipped
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: 3 years
Gutter & downspout material: Aluminum
Roof ventilation: Adequate
27)
Exposed nails on roof are not sealed.

Photo 42
|

Photo 67
|

Photo 43
|
|
28)
Gutters are clogged.

Photo 65
|

Photo 66
|

Photo 68
|
|
29)
Two areas on roof present awkward junctions left and right of main front dormer. These areas have a low slope which means the shingles will hold water longer than at steeper slopes. Ideally there should be metal flashings under these areas. Could not determine if metal flashings are present.

Photo 69
|

Photo 70
|
30)


The auto-reverse mechanism on the vehicle door opener is inoperable or requires too much force to activate. This is a safety hazard, especially for small children. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
http://www.cpsc.gov/cpscpub/pubs/523.html
http://www.ohdstl.com/safety.html
This applies to double door only.
31)
Overhead door switch button is loose.

Photo 45
|
|
32)
Switch must be is "on " position for door openers to operate.

Photo 45
|
|
Inspection method: Partially traversed
Roof structure type: Rafters
Ceiling structure: Ceiling beams
Insulation material: Fiberglass loose fill
Insulation depth: 10" - 12" where visible.
33)
Insulation has been trampled down in some areas from foot traffic.
34)
Repair to roof from tree damage has left small holes above and below the repair and felt can be seen.
Primary service type: Overhead
Primary service overload protection type: Circuit breakers
Service amperage (amps): 2- 200 amp
Service voltage (volts): 120/240
Location of main service switch: Meter Base
Location of sub panels: Garage
Location of main disconnect: Meter base
Service entrance conductor material: Aluminum
System ground: Not visible
Main disconnect rating (amps): 200 2
Branch circuit wiring type: Non-metallic sheathed
Smoke detectors present: YesConnected to security system (no test button)
35)

Most exterior receptacles are not GFCI protected.
36)
Two electrical wires are stretched across a concrete block pier. This poses an abrasive possibility which is a fire hazard. These wires should be rerouted. This is under kitchen area.

Photo 80
|
|
37)

Could not operate front porch or back porch lights.
38)

Some bulbs did not turn on.
39)
Could not get eave lights to operate.
40)
Could not determine purpose for some switches.
41)
Main disconnects are located outside of structure and can easily be turned off by pedestrian traffic. This should be locked by homeowner.
Type: Tank, Instantaneous
Energy source: Electricity, Propane
Capacity (in gallons): 50
Manufacturer: Rheem
42)
Water heater in crawl space pressure relief valve drain line dumps in crawl space. This line must exit structure and point downward terminating no more than 6" from the ground.

Photo 72
|

Photo 73
|

Photo 74
|

Photo 75
|
43)
Rinnai was not operating so most of the lower level had no hot water.
44)
Rinnai water heater control is in master bedroom closet.

Photo 60
|
|
Primary heating system energy source: Electric
Primary heat system type: Forced air, Heat pump
Primary A/C energy source: Electric
Primary Air conditioning type: Split system
Filter location: Behind return air grill
45)
Lower unit was operated in cooling mode and a temperature differential between in going and out going was approximately 15 degrees. For a unit of this age a larger temperature differential is expected.
Upper unit was operated in cooling mode and a temperature differential between in going and out going was approximately 9 degrees. For a unit of this age a larger temperature differential is expected.
These units should be evaluated by a certified technician.
46)
There is an air handler located in the crawl space. It does not have an auxiliary drain pan.
In hot months this unit will cool and condensation will drip off of it onto the crawl space floor. An auxiliary pan should be installed with a separate drain line which terminates outside of structure.

Photo 81
|
|
Water pressure (psi): 85
Location of main water shut-off valve: Street
Location of main water meter: Street
Water service: Public
Service pipe material: Not visible
Supply pipe material: Polyethelene
Vent pipe material: Plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
47)
Tank less water heater was not operating and most of lower level fixtures did not have water.
Fireplace type: Metal prefabricated
48)

3 fireplaces are vented gas logs. Gas was not turned on and fireplaces were not evaluated. An unsuccessful attempt to operate one fireplace was made after company rep turned on the gas. These units have probably never had their start up performed and may need lines bled and started. Reinspect after repaired by a certified technician.
Inspection method: Traversed
Insulation material underneath floor above: None visible
Pier or support post material: Masonry
Floor structure above: Engineered wood joists
Vapor barrier present: Yes
49)

There is a separation in foundation wall next to crawl space access door. These blocks should have been interwoven during construction (there are also other techniques for tying these walls together). The movement is excessive for new construction and should be evaluated.

Photo 82
|

Photo 83
|
50)
Dryer vent duct has bends and joints which will create resistance to exhausted lint and result in build up.

Photo 78
|
|
51)

The foundation walls are wet at NW corner.

Photo 77
|
|
52)
An unused electrical conduit is present at SW corner.

Photo 76
|
|
53)
There is a concern about the small raised area in the kitchen floor. This area is obscured by the HVAC duct work. The floor system is an engineered substructure. It is recommended that a copy of the designed floor system is acquired from the designer/supplier for your records and in the event of further movement.
54)

Disposer at kitchen sink appears to have no switch other than the breaker at the service panel.
55)
No receptacles present at cook top wall.
56)

Could not access ice maker valve behind refrigerator for presence of water.
57)
The floor is slightly raised in front of the sink and it extends to the breakfast room. This may be caused by a girder under the floor.

Photo 49
|
|
58)


Master bath jetted tub plunger would not close completely and tub would not hold water for evaluation. Repair and reinspect for operation and GFCI protection..
59)

GFCI at lower level hall bath does not trip when tested.
60)

No shower doors or rods present in bathrooms.

Photo 57
|
|
61)
There is no HVAC register at lower level hall bath.
62)
HVAC register in master bath is clogged with paper.

Photo 61
|
|
63)
Tub fill spouts are not secured at upper level bath tubs.
64)
Upper level toilet closest to bonus room would not shut off when tank is full.
65)
Small box in lower hall bath below vanity is unfinished. This box probably covers a plumbing drain mistake.

Photo 56
|
|
66)
A void is present in grout next to tub in upper level bathroom next to upper level landing area.

Photo 64
|
|
67)
No hot water present at lower level baths. See above.
68)

The dimmer switch that controls the breakfast room light gets extremely hot when in "on" position.
69)

The receptacle for ironing board in master closet has open ground.
70)

An unusual clunking sound is made when laundry sink faucet is moved from the hot side to the cold side.
71)

Stress cracks are present above and right of fireplace in front of kitchen. The concern is that one of these cracks is diagonal which indicates movement.

Photo 48
|
|
72)

When entering laundry room from garage a loud squeak is present at wood floor and floor feels spongy.
73)

The baseboard at living room front walls has open joints at both ends. This may be a result of movement or shrinkage.

Photo 51
|

Photo 52
|
74)

Trim pieces at top of formal stairway skirt board has separations. This appears to be lateral movement. It is unusual that both sides have significant separations.

Photo 62
|

Photo 63
|
75)
Laundry room door will not latch.
76)
Closet under stairway does not have finished floor.

Photo 53
|
|
77)
Pocket door hardware is not installed correctly and causes binding when in "open" position (check all 3 doors).

Photo 55
|
|
78)
Window hardware is not installed at master bath above jetted tub.

Photo 58
|

Photo 59
|
79)
Motion detector in great room is hidden above cabinet and is ineffective.

Photo 54
|
|
80)
Pocket door leading to upper level bonus room is not painted.

Photo 71
|
|
81)
There is slight cupping of wood floors in kitchen which is an indication of moisture. No water was found under crawl space under this area.

Photo 50
|
|