Property Inspection Report
Client(s): Thomas Hession/sample report
Property address: in Florida
Inspection date: 10/10/2010
This report published on Thursday, October 21, 2010 12:40:01 PM EDT

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Crawl space
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Report number: 07282010-1
Inspector's name: Thomas Hession
Type of building: Single family
Age of building: 23
Inspection Fee: $250.00
Present during inspection: Client(s), Realtor(s)
Occupied: No
Time started: 8:30 a.m
Time finished: 1:30 p.m.
Weather conditions: Partly cloudy
Temperature: Hot
Ground condition: Damp
Front of structure faces: N.E
Foundation type: Crawlspace
The following items are excluded from this inspection: Irrigation system , garage door, garage door opener
 
Exterior Return to table of contents
Apparent wall structure: Concrete block
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Footing material: Not visible
Foundation material: Concrete block
Apparent wall structure: Concrete block
Wall covering: Stone veneer
Exterior door material: Solid core steel
1) Guardrails are loose and/or wobbly in one or more areas. This is a safety hazard. A qualified contractor should evaluate and make repairs as necessary, such as installing new fasteners or hardware, installing additional fasteners and/or installing additional railing components as necessary so they are securely attached.

Photo 17  

Photo 18  

2) One or more outdoor electric receptacles appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all outdoor receptacles within six feet six inches of ground level have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
3) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit:
http://edis.ifas.ufl.edu/AE113

Photo 3  
 

4) One or more hornet, bee and/or wasp nests were found. These can pose a safety hazard. Nest(s) should be removed as necessary.

Photo 45  
above entrance door
 

5) One or more downspouts are missing. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. A qualified contractor should install downspout(s) where missing. Also recommend installing extensions such as splashblocks or tie-ins to underground drain lines as necessary to carry rainwater away from the house.

Photo 5  
 

6) One or more crawl space vent screens are damaged and/or deteriorated. Animals such as vermin or pets may enter the crawl space and nest, die and/or leave feces and urine. A qualified contractor should replace damaged or deteriorated screens where necessary using screen material such as "hardware cloth" with 1/4 inch minimum gaps.

Photo 4  
 

7) Gaps exist at one or more openings around the exterior, such as those where outside faucets, refrigerant lines, and/or gas supply pipes penetrate the exterior. Gaps should be sealed as necessary to prevent moisture intrusion and entry by vermin.

Photo 2  
Gap between concrete steps and garage grade
 

8) One or more soffit vent screens are blocked by paint, insulation or debris. This can reduce air flow through the attic, reduce the life of the roof surface because of high temperatures, and/or increase the moisture content in the attic. Repairs should be made as necessary, such as cleaning paint from screens, replacing screens, and/or moving insulation so vents are unobstructed.

Photo 13  
above entrance door
 

9) One or more exhaust duct end caps are damaged and/or deteriorated. Their purpose is to prevent unconditioned air from entering the house, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and may pose a fire hazard. New vent cap(s) should be installed where necessary.

Photo 15  
 

10) One or more soffit vent screens are blocked by paint, insulation or debris. This can reduce air flow through the attic, reduce the life of the roof surface because of high temperatures, and/or increase the moisture content in the attic. Repairs should be made as necessary, such as cleaning paint from screens, replacing screens, and/or moving insulation so vents are unobstructed.
11) One or more minor cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks including:
  • Hydraulic cement. Requires chiseling a channel in the crack to apply.
  • Resilient caulks (easy to apply).
  • Epoxy sealants (both a waterproof and structural repair).
    12) Fences and/or gates are damaged and/or deteriorated in some areas. A qualified contractor should evaluate and make repairs or replace sections as necessary.
    13) Trees and/or shrubs are in contact with or are close to the roof edge(s) in one or more areas. Damage to the roof may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.
    14) The finish on the deck(s) and railing(s) is worn and/or deteriorated. Recommend cleaning and refinishing as necessary.

    Photo 17  

    Photo 18  

    15) Caulk is missing or deteriorated in some areas and should be replaced and/or applied where necessary. For more information on caulking, visit:
    The Ins and Outs of Caulking.

    Photo 7  
     

    16) The exterior finish in some areas is failing. A qualified contractor should prep (pressure wash, scrape, sand, prime caulk, etc.) and repaint or restain areas as needed and as per standard building practices.

    Photo 6  
    Near front entrance
     

    17) Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
    18) One or more light fixtures have missing bulbs and could not be fully evaluated. Bulbs may simply need to be installed, or repairs or replacement may be necessary.
    19) One or more light fixtures have missing bulbs and could not be fully evaluated. Bulbs may simply need to be installed, or repairs or replacement may be necessary.

    Photo 16  
     
     
    Roof Return to table of contents
    Roof inspection method: Traversed
    Roof type: Gable
    Roof covering: Asphalt or fiberglass composition shingles
    Estimated age of roof: 6 yrs
    Gutter & downspout material: Plastic
    Roof ventilation: Adequate
    20) Satellite dishes roof penetrations have no visible sealing. This may cause water penetration in the future

    Photo 22  
     

    21) Two sections of roof surfaces are sloped towards each other. Debris such as leaves or needles are more likely to accumulate in this area than rest of the roof. Leaks may occur as a result. Recommend monitoring such areas for accumulated debris in the future and cleaning as necessary.

    Photo 20  

    Photo 21  

    22) missing sealant around vent pipe

    Photo 23  
     

    23) Debris such as leaves, needles, seeds, etc. have accumulated on the roof. This is a conducive condition for wood destroying insects and organisms since water may not flow easily off the roof, and may enter gaps in the roof surface. Leaks may occur as a result. Debris should be cleaned from the roof now and as necessary in the future.

    Photo 20  

    Photo 21  

    24) Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.
     
    Garage Return to table of contents

    25) The automatic door closing device (sprung hinges, etc.) on the garage-house door needs adjustment, repair or replacing. The door doesn't close and latch easily and/or completely via the force of the automatic closing device. This door is intended to prevent vehicle fumes from entering living spaces and to slow the spread of fire from the garage to living spaces. A qualified contractor should evaluate and make repairs as necessary.
    26) Gaps exist between the garage-house door and the surrounding weatherstrip when the door is closed. Fumes from the garage may enter living spaces as a result. A qualified contractor should evaluate and make repairs as necessary.
    27) The garage-house door poses a fire risk because a pet door has been installed in it, eliminating its fire rating. A qualified contractor should replace this door with a fire-rated door.

    Photo 44  
     

    28) The attic access hatch over the attached garage doesn't have a one-hour fire rating. Wall and ceiling surfaces in an attached garage should be fire rated for one hour to prevent or slow the spread of fire from the garage to interior living spaces. This hatch should be replaced with a material that has a one hour fire rating, such as 5/8 inch Type X sheetrock.
    29) Handrail(s) at some stairs are loose. This is a safety hazard. A qualified contractor should make repairs as necessary. For example, installing new fasteners and/or hardware so handrails are securely attached.
    30) One or more ground fault circuit interrupter protection devices were defective. Because one GFCI device may in turn provide GFCI protection for other electric receptacles on the same circuit, the inspector was unable to determine if all electric receptacles that serve countertop surfaces within six feet of sinks are protected with a GFCI device. If they are not, a safety hazard due to the risk of shock exists. After repairs are made to the defective GFCI device(s), a qualified electrician should evaluate, determine if all receptacles that serve countertop surfaces within six feet of sinks are protected by GFCI devices, and make repairs if necessary.
    31) The garage vehicle door is damaged or deteriorated. A qualified contractor should evaluate and repair or replace the door as necessary.

    Photo 9  

    Photo 10  

    Photo 11  
     

    32) Various wall penetrations are in need of sealing to prevent air intrusion and insect or rodent infestations.

    Photo 33  

    Photo 38  

    33) Because of the condition of the garage door.....it or the automatic garage door opener was not inspected and is excluded from this report.

    Photo 9  

    Photo 10  

    Photo 11  
     
     
    Attic Return to table of contents
    Inspection method: Viewed from hatch
    Roof structure type: Trusses
    Ceiling structure: Trusses
    Insulation material: Fiberglass loose fill
    Insulation depth: less than 6"
    Insulation estimated R value: r-15
    34) One or more hornet, bee and/or wasp nests were found. These can pose a safety hazard. Nest(s) should be removed as necessary.
    35) The ceiling insulation's R rating is significantly less than what's recommended for this area. Recommend having a qualified contractor install additional insulation as per standard building practices for better energy efficiency.
    36) No insulation is installed over the attic access hatch. Recommend installing insulation above hatch for better energy efficiency.
    37) No weatherstrip is installed around the attic access hatch. Weatherstrip should be installed around the hatch to prevent heated interior air from entering attic.
    38) Some attic areas were inaccessible due to lack of permanently installed walkways, the possibility of damage to insulation, low height and/or stored items. These areas are excluded from this inspection.

    Photo 29  

    Photo 30  

    Photo 48  
     
     
    Electric service Return to table of contents
    Primary service type: Underground
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 150
    Service voltage (volts): 120/240
    Location of main service switch: Garage area
    Location of main disconnect: Breaker at top of main service panel
    Service entrance conductor material: Copper-clad aluminum
    System ground: Ground rod(s) in soil
    Main disconnect rating (amps): 150
    Branch circuit wiring type: Copper
    Solid strand aluminum branch circuit wiring present: No
    Smoke detectors present: No
    39) One or more overcurrent protection devices (circuit breakers or fuses) are "double tapped", where 2 or more wires are clamped in a terminal designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. A qualified electrician should evaluate and repair as necessary.

    Photo 24  
     

    40) One or more pointed and/or too-long screws are used to fasten the cover to the main service panel. These types of screws are more likely to come into contact with wiring inside the panel than stock screws from the manufacturer, and can damage wiring insulation. This is a safety hazard due to the risk of shock and/or fire. Long and/or pointed crews should be replaced as necessary with the correct screws, and if necessary by a qualified electrician.

    Photo 27  

    Photo 28  

    41) One or more knockouts have been removed inside the main service panel where no wires and bushings are installed, and no cover(s) have been installed to seal the hole(s). This is a safety hazard due to the risk of fire. A qualified electrician should install knockout covers where missing.

    Photo 25  
     

    42) AFCI protection requirement for some of the circuits in your house has been in place since January 1, 2002 . Have your electrical service evaluated by an licensed electrical contractor .

    Photo 26  
     

    43) The legend for overcurrent protection devices (breakers or fuses) in the main service panel is missing, unreadable or incomplete. Recommend installing, updating or correcting the legend as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.
     
    Water heater Return to table of contents
    Estimated age: 2 yrs
    Type: Tank
    Energy source: Electricity
    Capacity (in gallons): 38 gals
    Manufacturer: Whirlpool
    Model: E2F406D045V
    44) Temperature-pressure relief valve drain line is too short. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should extend the drain line to 6 inches from the floor, or route it so as to drain outside.

    Photo 31  

    Photo 32  

    Photo 34  

    Photo 35  

    Photo 36  
     

    45) It appears an ground wire is attached to the cold water copper inlet. This groundwire is improperly installed and should be evaluated by a licensed electrician to determine it's origin, safety, and function

    Photo 37  
     
     
    Heating and cooling Return to table of contents
    Estimated age: 4.5 Yrs
    Primary heating system energy source: Electric
    Primary heat system type: Heat pump
    Primary A/C energy source: Electric
    Primary Air conditioning type: Split system
    Distribution system: Flexible ducts
    Manufacturer: Nordyne
    Model: JT3BC-030K Serial# JTD050601642
    Filter location: Behind return air grill
    Last service date: Unknown
    46) Insulation for the outside condensing unit's refrigerant lines is damaged, deteriorated and/or missing in one or more areas. This may result in reduced efficiency and increased energy costs. A qualified heating and cooling contractor should replace insulation as necessary.
    47) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.

    Photo 12  

    Photo 19  

    48) The cooling fins on the air handler's evaporator coils are dirty. This may result in reduced efficiency and higher energy costs. Some sources claim that energy efficiency is degraded by about five percent each year as the coils get dirtier due to accumulated dust and grime. A qualified heating and cooling contractor should clean the evaporator coils as necessary.

    Photo 43  
     

    49) The cooling fins on the outdoor condensing unit's evaporator coils are dirty. This may result in reduced efficiency and higher energy costs. A qualified heating and cooling contractor should clean the evaporator coils as necessary.
    50) Air handler filter(s) should be checked monthly in the future and replaced or washed as necessary.
     
    Plumbing and laundry Return to table of contents
    Location of main water shut-off valve: Side of garage
    Location of main water meter: Front yard
    Water service: Public
    Service pipe material: Not visible
    Supply pipe material: Copper
    Vent pipe material: Plastic
    Drain pipe material: Plastic
    Waste pipe material: Plastic
    51) The clothes dryer exhaust duct appears to need cleaning. Significant amounts of lint build up was found. This is a safety hazard due to the risk of fire from decreased air flow. This duct should be cleaned now and annually, or more often if necessary in the future. Some chimney sweeps or heating/cooling duct cleaners perform this service. For more information, visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5022.html
    http://chimneykeepers.com/dryerclean.html

    Photo 15  
     

    52) This appears to be a clean out for the sewer line...Have evaluated by a licensed plumbing contractor to know of it's origin.

    Photo 8  
     

    53) The heat recovery unit has been terminated....and appears to have no value...to be safe it should be evaluated by an licensed HVAC tech and removed.

    Photo 14  
     

    54) Neither the clothes washer nor dryer were operated or evaluated. They are excluded from this inspection.
     
    Crawl space Return to table of contents
    Inspection method: Partially traversed
    Insulation material underneath floor above: Fiberglass roll or batt
    Pier or support post material: Masonry, Steel
    Beam material: Solid wood
    Floor structure above: Solid wood joists
    Vapor barrier present: No
    55) One or more pier or foundation footings are undermined, where soil has either eroded out from underneath, or has been excavated too close to the footing. Structural engineers typically require undisturbed soil to extend at least a foot horizontally out from the edge of footings, and then slope down no more steeply than 45 degrees. Otherwise soil may collapse from beneath the footing(s). A qualified structural engineer should evaluate and determine what repairs if any should be made. If repairs are prescribed, then a qualified contractor should perform them in accordance with the engineer's recommendations.

    Photo 53  
     

    56) Some wiring is loose, unsupported, or inadequately supported. Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.

    Photo 55  
     

    57) Wooden support posts are not securely fastened to beams above. This is a safety hazard since they can separate during a seismic event. A qualified contractor should evaluate and make repairs as necessary, such as installing metal ties, bracing with lumber and/or plywood gussets as per standard building practices.

    Photo 50  

    Photo 54  

    Photo 56  
     

    58) No vapor barrier is installed. This is a conducive condition for wood destroying insects and organisms due to the likelihood of water evaporating into the structure from the soil. A qualified contractor should install a vapor barrier. Standard building practices require the following:

  • The soil below the vapor barrier should be smooth and free from sharp objects.
  • Seams should overlap a minimum of 12 inches.
  • The vapor barrier should lap up onto the foundation side walls.

    Better building practices require that:

  • Seams and protrusions should be sealed with a pressure sensitive tape.
  • The vapor barrier should be caulked and attached tightly to the foundation side walls. For example, with furring strips and masonry nails.
    59) Insulation under the floor in the crawlspace is damaged, deteriorated, or has fallen down. A qualified contractor should make repairs as necessary to restore the insulation to its original rating.
    60) Entrance to crawl space and other pictures of support members . There appears to have been some repair work done. Have evaluated by a structural engineer.

    Photo 49  

    Photo 50  

    Photo 51  

    Photo 52  

    Photo 57  

    Photo 58  

    Photo 59  
     

    61) Some crawl space areas were inaccessible due to low height (less than 18 inches), ductwork or pipes blocking, standing water, and/or stored items. These areas are excluded from this inspection.
     
    Kitchen Return to table of contents

    62) One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.
    63) One or more ground fault circuit interrupter protection devices were defective. Because one GFCI device may in turn provide GFCI protection for other electric receptacles on the same circuit, the inspector was unable to determine if all electric receptacles that serve countertop surfaces within six feet of sinks are protected with a GFCI device. If they are not, a safety hazard due to the risk of shock exists. After repairs are made to the defective GFCI device(s), a qualified electrician should evaluate, determine if all receptacles that serve countertop surfaces within six feet of sinks are protected by GFCI devices, and make repairs if necessary.
    64) The dishwasher drain line is not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The clients should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.

    Also, no "air gap" is installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client(s) should consult with a qualified contractor to determine if an air gap should be installed.

    Photo 40  
     

    65) The refrigerator appears to be inoperable. The client(s) should ask the property owner(s) about this, and if necessary, the refrigerator should be replaced, or a qualified appliance technician should evaluate and repair.
    66) The under-sink food disposal is inoperable. A qualified plumber or contractor should evaluate and repair or replace the food disposal as necessary.

    Photo 39  
     

    67) One or more faucets leak by handle(s) or at their base when turned on. A qualified plumber should evaluate and repair as necessary.
    68) The refrigerator ice maker is in the "off" position. The inspector was unable to evaluate this component.
     
    Bathrooms Return to table of contents

    69) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    Photo 42  

    Photo 47  

    70) One or more sink drains have an active leak. For example, at pipe fittings and/or junctions between pipe and sink. A qualified plumber should evaluate and repair as necessary.
    71) Floor tiles installed in "wet" areas have gaps between them. The wooden subfloor beneath may be damaged by water intrusion. A qualified contractor should evaluate, make repairs if necessary, and replace flooring with a waterproof floor such as sheet vinyl in wet areas.

    Photo 41  
     

    72) One or more bathrooms with a shower do not have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
    73) One or more sinks are clogged or drain slowly. Drain(s) should be cleared as necessary, and by a qualified plumber if necessary.

    Photo 46  
     

    74) Caulk is missing or deteriorated along the base of one or more bathtubs, where flooring meets the tub. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the floor structure.
    75) Caulk is missing and/or deteriorated at one or more bathtubs. For example, where the tub base meets the floor below, where the tub surround meets the tub, and/or around the base of the tub spout. Caulk should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to wall and floor structures.
    76) Master bathroom door has wood veneer peeling away from door
    77) Recommend cleaning and sealing grout in tile or stone flooring now and in the future as necessary to prevent staining and to improve waterproofing.
    78) Master bathroom shower and tub plumbing not working......also missing showerhead.... Ask owner or have evaluated by licensed plumbing contractor

    Photo 60  

    Photo 61  
     
    Interior rooms Return to table of contents

    79) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
    http://www.google.com/search?q=old+smoke+alarms

    80) An insufficient number of smoke alarms are installed. Additional smoke alarms should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
    81) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit:
    http://www.cpsc.gov/cpscpub/pubs/5077.html

    82) Carpeting in one or more rooms is damaged and/or significantly deteriorated. Recommend replacing carpeting where necessary.
     
    Dear Client, Thank you for asking me to inspect your prospective new home. The inspection was performed according to the Standards Of Practice of the National Association of Certified Home Inspectors (NACHI) of which I am a certified member. NACHI inspectors are professionals who adhere to uniform standards for disclosing building deficiencies and a "code of ethics" that requires members to discharge their duties with fairness and impartiality to all.