Home Inspection Report
Client(s): Joe and Jane Doe
Property address: 123 Main St.
Brainerd, MN 56401
Inspection date: 2/10/2011
This report published on Monday, February 14, 2011 10:45:52 AM CST

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Basement
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Report number: 20100228-1
Inspector's name: Kurt Hanson
Type of building: Single family
Age of building: 24 years
Inspection Fee: $295
Occupied: Yes
Weather conditions: Clear
Temperature: Cold
Ground condition: Frozen
Front of structure faces: West
Main entrance faces: West
Foundation type: Finished basementConcrete Block
The following items are excluded from this inspection: Private sewage disposal system, Private well, Built-in sound system, Outbuildings
1) Some wall, floor and/or ceiling surfaces were obscured by furniture and/or stored items. Some areas couldn't be evaluated.
 
Exterior Return to table of contents
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Wood
Driveway material: Not visible due to snow
Sidewalk material: Not visible due to snow
Exterior door material: Solid core wood, Solid core steel
2) One or more electric receptacles and/or the boxes they are installed in are loose and/or not securely anchored on the front porch. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.
3) One or more ground fault circuit interrupter (GFCI) electric receptacles on the deck did not trip when tested. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.
4) One downspout extension on the garage is ineffective. It should be changed to divert the water away from the building.
5) The substructure of the deck is excluded from the inspection due to limited access because of the low height.
6) One or more outside faucets were not evaluated due to their being winterized, and are excluded from this inspection.
 
Roof Return to table of contents
Roof inspection method: Not inspected. Roof was snow covered
Roof type: Gable
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: 4 years
Gutter & downspout material: Aluminum
Roof ventilation: Unable to determine (no access to attic spaces)
7) The roof was completely obscured by snow and couldn't be fully evaluated.
 
Garage Return to table of contents

8) One or more wall and/or ceiling surfaces between the attached garage and interior living spaces have gaps, holes, or missing or inadequate surface materials. These surfaces are intended to prevent vehicle fumes from entering living spaces, and to slow the spread of fire from the garage to living spaces. A qualified contractor should evaluate and make repairs as necessary so the attached garage wall and ceiling surfaces that adjoin living spaces are tightly sealed and fire rated as per standard building practices. Typically these surfaces require a one-hour fire rating.

Photo 4  
Sheetrock wall should be taped.

Photo 5  
This wood wall should be taped sheetrock.

9) One or more electric receptacles are broken or damaged. This is a safety hazard due to the risk of fire and shock. A qualified electrician should replace them as necessary.

Photo 2  
 

10) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

Photo 3  
 
 
Attic Return to table of contents
Inspection method: Not inspected
11) The attic access hatch was inaccessible due to stored items, debris, or the hatch being permanently closed. The inspector was unable to evaluate the attic, and it's excluded from this inspection. Recommend moving items or modifying hatch(es) as necessary to allow periodic evaluation of attic spaces.
 
Electric service Return to table of contents
Primary service type: Underground
Primary service overload protection type: Circuit breakers
Service amperage (amps): 200
Service voltage (volts): 120/240
Location of main service switch: Basement Utility Room
Location of main disconnect: Breaker at top of main service panel
Service entrance conductor material: Aluminum
System ground: Cold water supply pipes
Branch circuit wiring type: Non-metallic sheathed
Smoke detectors present: Yes
12) One or more overcurrent protection devices (circuit breakers or fuses) are "double tapped", where 2 or more wires are clamped in a terminal designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. A qualified electrician should evaluate and repair as necessary.
 
Water heater Return to table of contents
Estimated age: 4 years
Type: Tank
Energy source: Electricity
Capacity (in gallons): 85
 
Heating and cooling Return to table of contents
Estimated age: 24 years
Primary heating system energy source: Propane gas
Primary heat system type: Forced air
Primary A/C energy source: Electric
Distribution system: Sheet metal ducts
Manufacturer: Lennox
Model: Pulse
Filter location: At the base of the furnace
Last service date: Uncertain, tag inside furnace shows heat exchanger service in 1998.
13) Because of the age and/or condition of this furnace, recommend that a qualified heating and cooling technician inspect the heat exchanger and perform a Carbon Monoxide test when it's serviced.
14) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. For more information visit:
http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

15) The estimated useful life for most forced air furnaces is 15 to 20 years. This furnace appears to be at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.
16) The outdoor air temperature was below 60 degrees Fahrenheit during the inspection. Because of this, the inspector was unable to operate and fully evaluate the cooling system.
 
Plumbing and laundry Return to table of contents
Location of main water shut-off valve: Furnace Room
Location of main fuel shut-off: By Furnace
Visible fuel storage systems: Propane tank behind house
Water service: Private
Supply pipe material: Copper, Polyethelene
Vent pipe material: Plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
17) Recommend having the septic tank inspected. Recommend having the tank pumped if it was last pumped more than 3 years ago.
18) The clothes washer had clothing in it and was not operated during this inspection. The inspector was unable to fully evaluate the washer and its drain line.
19) A sump pump is installed on the premises. This may indicate that water accumulates inside or below the structure. Recommend asking the property owners how often the sump pump operates and for how long at different times of the year. Also, the clients should be aware that the service life of most sump pumps is between five and seven years, and that the pump may need replacing soon depending on its age and how much it operates.
 
Fireplaces, woodstoves and chimneys Return to table of contents

20) A significant amount of creosote (1/8 inch or more) is visible in the fireplace flue. A qualified chimney service contractor should inspect, clean, and repair if necessary now and annually in the future.
 
Basement Return to table of contents
Insulation material underneath floor above: None visible
Pier or support post material: Not visible
Beam material: Solid wood
Floor structure above: Solid wood joists
21) One or more sections of wiring that weren't terminated were found. This is a potential safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary. For example, cutting the wire to length and terminating the wire with wire nuts in a securely anchored, covered, properly sized junction box.

Photo 13  
 

22) Trip hazard(s) exist at stairs due to non-uniform riser heights. Standard building practices call for riser heights not to vary more than 3/8 inch on a flight of stairs. At a minimum, the client(s) should be aware of this hazard, especially when guests who are not familiar with the stairs are present. Ideally a qualified contractor should evaluate and repair or replace stairs so all riser heights are within 3/8 inch of each other.

Photo 12  
The top step going into the basement is noticeably higher than the others.
 
 
Kitchen Return to table of contents

23) The dishwasher drain line is not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The clients should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.

Also, no "air gap" is installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client(s) should consult with a qualified contractor to determine if an air gap should be installed.

Photo 6  
 

24) Tile, stone and/or grout countertops are damaged and/or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary. For example, replacing broken tiles and deteriorated grout, and resealing grout.

Photo 7  
 
 
Bathrooms Return to table of contents

25) Caulk is missing or deteriorated along the base of one or more bathtubs, where flooring meets the tub. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the floor structure. There is evidence of leaking into the bathroom ceiling below this tub on the second floor.

Photo 11  
 
 
Interior rooms Return to table of contents

26) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html

27) Seals between double-pane glass in the family room window appears to have failed based on condensation or stains between the panes of glass. A qualified contractor should evaluate and replace glass where necessary.

The client(s) should be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Windows or glass doors other than those that the inspector identified may also have failed seals and need glass replaced too.

Photo 8  
 

28) Screen(s) in the master bedroom windows are missing. The client(s) should ask the property owner(s) about this. Screens are often removed for window cleaning and they may be stored somewhere. If not, then recommend installing screens where missing.
29) Lock mechanisms on one or more casement windows are missing and/or damaged so that they are inoperable. Repairs should be made by a qualified contractor or service technician so that windows lock and unlock easily.

Photo 10  
In addition to missing hardware, note the frost accumulation on the inside of the window. The window may leak or may not be closed tightly. This is the middle bedroom on the second floor.
 

30) The weatherstrip around one or more exterior entry doors is missing and/or deteriorated. Weatherstrip should be installed where missing and/or replaced where deteriorated, and by a qualified contractor if necessary.
31) One or more rooms that are considered living spaces in the basement appear to have no visible source of heat. The client(s) should consult with the property owner(s) regarding this, and if necessary, a qualified contractor should evaluate and install heat source(s) as necessary.
32) Minor cracks were found in walls on the second floor. They appear to have been caused when the wall beneath this one was removed for remodeling. The client(s) may wish to repair these for aesthetic reasons.

Photo 9