Property Inspection Report

Client(s):  Harold & Linda Wylie
Property address:  205 Springview Dr
Lynden WA 98264-9360
Inspection date:  Friday, March 09, 2018

This report published on Friday, March 09, 2018 8:15:53 PM PST

This report is the exclusive property of this A+ Handy Inspections and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard
Major DefectCorrection likely involves a significant expense
Repair/ReplaceRecommend repairing or replacing
Repair/MaintainRecommend repair and/or maintenance
Minor DefectCorrection likely involves only a minor expense
MaintainRecommend ongoing maintenance
EvaluateRecommend evaluation by a specialist
MonitorRecommend monitoring in the future
CommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows

View summary


General Information
Return to table of contents

Report number: DJH 0000053
Time started: 9:30 AM
Present during inspection: Client, Realtor, Layla Pollack, Keller Williams Western Realty
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cool
Inspection fee: 375.00
Payment method: Check
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 1998
Source for main building age: Municipal records or property listing
Front of building faces: North
Main entrance faces: North
Occupied: No

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable, Front Porch
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Required repairs, replacement and/or evaluation (see comments below)
Deck, porch and/or balcony material: Wood

1) Repair/Maintain - The front porch support post at the entry is close to contact with concrete porch. Water can week up into this post and cause water damage and or rot. Recommend to monitor the post and paint to preserve as required.
Photo
Photo 1-1
 

2) Maintain - Wooden back deck surfaces is starting to show wear and is going to need some normal maintenance. Recommend that a qualified person clean and preserve as necessary, such as apply another cover coat to wooden deck.
Photo
Photo 2-1
Photo
Photo 2-2

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Cement fiber
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete

3) Repair/Replace - a couple of sections of siding were deteriorated and/or cracked. The deteriorated piece is caused by water damage from not having kick-out flashing on the roof to gutter interface. Recommend that a qualified person repair/roofing company, replace or install siding or trim as necessary.
Photo
Photo 3-1
Photo
Photo 3-2

4) Repair/Replace - One dryer exhaust duct end cap is damaged and stuck open. Their purpose is to prevent unconditioned air from entering the building, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and can pose a fire hazard. Recommend that a qualified person repair or replace caps as necessary.
Photo
Photo 4-1
Photo
Photo 4-2

5) Repair/Maintain - Soil was less than 6 inches from siding. Regardless of what material is used for siding, it should not be in contact with the soil. If made of wood, siding or trim will eventually rot. For other materials, ground or surface water can infiltrate siding or trim and cause damage to the wall structure. Wood-destroying insects are likely to infest and damage the wall structure. This is a conducive condition for wood-destroying organisms. Recommend grading or removing soil as necessary to maintain a 6-inch clearance. Note that damage from fungal rot and/or insects may be found when soil is removed, and repairs may be necessary.
Photo
Photo 5-1
 

6) Maintain - Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 6-1
Photo
Photo 6-2

7) Maintain - The paint finish in some areas is starting to failing (e.g. peeling, faded, worn, thinning) on the trim boards around the windows on the south side of the house. Trim with a failing finish can be damaged by moisture. Recommend that a qualified contractor/person prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 7-1
Photo
Photo 7-2
Photo
Photo 7-3
Photo
Photo 7-4

8) Maintain - Caulk is starting to deteriorated in some areas on the south side of the house. For example, around windows and/or around doors. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
http://www.reporthost.com/?CAULK
Photo
Photo 8-1
Photo
Photo 8-2
Photo
Photo 8-3
Photo
Photo 8-4

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure above: Engineered wood joists
Condition of insulation underneath floor above: Appeared serviceable
Insulation material underneath floor above: Fiberglass roll or batt
Condition of vapor barrier: Appeared serviceable
Vapor barrier present: Yes
Condition of crawl space ventilation: Appeared serviceable
Ventilation type: Unconditioned space

9) Repair/Maintain - Some under-floor insulation was falling down in some areas. This may result in reduced energy efficiency. Recommend that a qualified person repair or replace insulation as necessary.
Photo
Photo 9-1
Photo
Photo 9-2

10) Repair/Maintain - A few crawl space vents were below grade, and either no wells were installed. Vent wells should be installed when vents are at or near grade to prevent debris from blocking vents and/or water from entering vents. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person install, replace or repair vent wells per standard building practices.
Photo
Photo 10-1
Photo
Photo 10-2
Photo
Photo 10-3
Photo
Photo 10-4

11) Monitor - Minor amounts of standing water were found at two locations in the crawl space. Some minor seasonal water accumulation can be normal. Rain runoff is the most common cause of wet crawl spaces but water can come from other sources such as groundwater or underground springs. It looks like some of the water is coming from the joint at the stem wall and footing interface. Recommend monitoring the crawl space in the future, especially after heavy and/or prolonged periods of rain. Correct any issues related to outside perimeter grading and/or roof drainage (see any other comments about this in this report). Also, review any disclosure statements available and ask the property owner about past accumulation of water in the crawl space.

If standing water persists or increases in amount, recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typically such repairs include:
  • Install vent wells to prevent water from entering crawl space
  • Repairing, installing or improving underground footing and/or curtain drains
  • Applying waterproof coatings to foundation walls
  • Digging trenches in the crawl space to collect or divert water
  • Installing sump pumps
Photo
Photo 11-1
Photo
Photo 11-2
Photo
Photo 11-3
 

12) Comment - Most of the crawl space vents were intentionally blocked (e.g. removable panels, rigid foam). This restricts ventilation in the crawl space and can result in increased levels of moisture inside. This is a conducive condition for wood-destroying organisms. Such vents should be left open at all times except during severe freezing weather. Recommend removing materials or items blocking vents as necessary.
Photo
Photo 12-1
Photo
Photo 12-2

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed, 8:12 pitch
Condition of roof surface material: Near, at or beyond service life
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable, Hipped
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable

13) Major Defect, Evaluate - The roof surface appeared to be near the end of its service life and will likely need replacing in the near future even if repairs are made now. Recommend discussing replacement options with a qualified contractor, and budgeting for a replacement roof surface in the near future. The client may also wish to consider having a qualified contractor attempt to issue a "5 year roof certificate."
Photo
Photo 13-1
Photo
Photo 13-2
Photo
Photo 13-3
Photo
Photo 13-4

14) Repair/Replace, Evaluate - One skylight appeared to have water running on the inside. Recommend that a qualified contractor/roofing company evaluate and repair as necessary.
Photo
Photo 14-1
 

15) Repair/Replace - The kick out flashing is missing at every gutter end and wall interface. Water may penetrate behind wall structure and cause water damage. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person install flashing as necessary or at least apply caulking to prevent water penetration behind wall structure..
Photo
Photo 15-1
Photo
Photo 15-2
Photo
Photo 15-3
Photo
Photo 15-4

16) Repair/Maintain, Maintain - Water and weather damage was found at the barge board tail ends that sit on the roof. Recommend that a qualified person or contractor repair as necessary. For example, by removing all water damage or replacing all rotten wood, priming and painting new wood.
Photo
Photo 16-1
Photo
Photo 16-2
Photo
Photo 16-3
 

17) Comment - The one downspout extension at the garage drains onto the walkway. This may result in ice or moss forming on walkways and may pose a fall hazard. Recommend monitoring or be careful during freezing conditions.
Photo
Photo 17-1
Photo
Photo 17-2

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): R-38
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Ridge vent(s), Enclosed soffit vents

Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Solid core
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 2
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): Yes
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable

18) Repair/Maintain - Self-closing device (hinge) on the door between the garage and the house didn't close and latch the door. These hinges are installed to completely close the door after being opened. This prevent possible fire and fumes from the garage spreading to the house. Recommend a qualified person adjust or repair hinges as necessary.
Photo
Photo 18-1
Photo
Photo 18-2
Photo
Photo 18-3
 

19) Repair/Maintain - The storm door doesn't close all of the way and water is seeping under the back door threshold. This is getting the rug on the garage room floor wet. The storm door needs to be re-installed, so it completely closes. If condition continues this is a conducive condition for rot and mold. A qualified contractor should repair as necessary.
Photo
Photo 19-1
Photo
Photo 19-2
Photo
Photo 19-3
 

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Garage
Location of sub-panel #C: Building exterior
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested

20) Safety, Repair/Replace, Evaluate - One wall switch was scorched in the garage west wall. The wiring for these switches may be damaged due to overheating. Recommend that a qualified electrician replace such switches, evaluate related wiring and repair if necessary.
Photo
Photo 20-1
 

21) Safety, Repair/Replace - A few electric receptacles and/or the boxes in which they were installed were loose and/or not securely anchored(Kitchen NE corner, Dining SW corner, Laundry NW corner and in garage West wall). Wire conductors can be damaged due to repeated movement and/or tension on wires, or insulation can be damaged. This is a shock and fire hazard. Recommend that a qualified electrician repair as necessary.
Photo
Photo 21-1
Photo
Photo 21-2
Photo
Photo 21-3
Photo
Photo 21-4

22) Safety, Repair/Replace - Smoke alarms were missing from one or more hallways leading to bedrooms. Smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM
Photo
Photo 22-1
 

23) Evaluate - One light fixture were inoperable (didn't turn on when 2 nearby switches were operated). Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
Photo
Photo 23-1
Photo
Photo 23-2
Photo
Photo 23-3
 

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Water pressure (psi): 60 PSI
Location of main water shut-off: Laundry room
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Location of main fuel shut-off valve: At gas meter

24) Repair/Maintain - One or more hose bibs leaked when tested. When hose bibs leak while turned off, it's often caused by a worn valve seat or a loose bonnet. When hose bibs leak while turned on, it may be due to worn "packing" around the stem or a defective backflow prevention device. Recommend that a qualified plumber repair as necessary.
Photo
Photo 24-1
Photo
Photo 24-2

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Not determined (inaccessible, obscured, or water, power or gas service off)
Type: Tank, Bradford White Corp, Model #MI75S6CN12, Serial #SJ29+04192-131, 09/1998
Energy source: Natural gas
Estimated age: 09/1998, approximatly 20 years old.
Capacity (in gallons): 75
Location of water heater: Garage
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 82.2 F
Condition of burners: Not determined (inaccessible, obscured, or gas service off)
Condition of venting system: Appeared serviceable

25) Safety, Repair/Replace - The water heater's earthquake reinforcement was substandard. For example, struts were used rather than straps, substandard fasteners were used, or they may allow significant movement. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines leaking if gas-fired, or electric wiring being damaged if powered by electricity. Water leaks may also occur. Recommend that a qualified person repair or replace existing earthquake reinforcement per standard building practices.
Photo
Photo 25-1
Photo
Photo 25-2

26) Evaluate, Comment - The water heater's local gas shut-off was off and/or pilot light was off. The water heater and hot water supply system (e.g. faucets, controls) were not fully evaluated because of this. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the water heater is operable. Note that per the standards of practice for various professional home inspection organizations, the inspector does not operate shut-off valves, pilot lights or over-current protection devices, or any controls other than "normal controls."
Photo
Photo 26-1
Photo
Photo 26-2

27) Evaluate, Comment - The estimated useful life for most water heaters is 8-12 years. This water heater (20 years old) appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 27-1
09/1998
 

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: 09/20/01
Source for last service date of primary heat source: Label
Condition of electric heaters (not forced air): Appeared serviceable
Electric heater type (not forced air): Wall mounted
Forced air heating system fuel type: Natural gas, Trane, Model #TDE080A945K2, Serial #N314RDB2G, 10/08/1998
Estimated age of forced air furnace: 10/1998, approximetly 20 Years old.
Location of forced air furnace: Garage
Forced air system capacity in BTUs or kilowatts: 80,000 BTU's
Condition of furnace filters: Required replacement
Location for forced air filter(s): Behind return air grill(s)
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct, Vent(s) to exterior
Condition of venting system: Appeared serviceable
Condition of controls: Appeared serviceable

28) Safety, Repair/Maintain, Evaluate - The last service date of the gas fired forced air furnace appeared to be more than 1 year ago from the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP
Photo
Photo 28-1
09/20/01
 

29) Major Defect, Comment - The estimated useful life for most forced air furnaces is 15-20 years. This furnace (20 years old) appeared to be at this age and may need some repairs at any time. Recommend budgeting for a replacement in the near future.

30) Repair/Replace, Evaluate - A small amount of a white, powdery residue was found in the furnace. Typically this is a result of condensation in the furnace and may indicate that the furnace has a substandard draw. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 30-1
Photo
Photo 30-2
Photo
Photo 30-3
 

31) Maintain, Comment - Dirt or lint can accumulated on the fins, fan blades and/or motor of the wall heater in the garage room fan-assisted electric wall heaters equipped with fans. This is a potential fire hazard. Recommend that a qualified person clean heaters now and as necessary in the future. Note that the power to heaters must be turned off at the electric panel before cleaning them.
Photo
Photo 31-1
 

32) Maintain - Recommend that home buyers replace or clean HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or cleaning them as necessary. How frequently they need replacing or cleaning depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo
Photo 32-1
 

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of gas-fired fireplaces or stoves: Appeared serviceable
Gas fireplace or stove type: Metal pre-fab fireplace
Condition of chimneys and flues: Appeared serviceable
Gas-fired flue type: Direct vent

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable, Maytag
Condition of ranges, cooktops and/or ovens: Appeared serviceable, Amana
Range, cooktop, oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Not determined, Maytag
Condition of built-in microwave oven: N/A (none installed)

33) Repair/Maintain - The sink drinking faucet plumbing has been disconnected to the water purifier system and leaking onto the kitchen cabinet. Recommend that a qualified person repair/install new system as necessary.
Photo
Photo 33-1
Photo
Photo 33-2

34) Comment - The exhaust fan over the range recirculated the exhaust air back into the kitchen. This may be due to no duct being installed, baffles not being installed, or problems with duct work. This can be a nuisance for odor and grease accumulation. Where a gas-fired range or cook top is installed, carbon monoxide and excessive levels of moisture can accumulate in living spaces. Recommend that a qualified contractor evaluate and repair as necessary so exhaust air is ducted outdoors.
Photo
Photo 34-1
 

35) Comment - The refrigerator was turned off.

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Half bath, first floor
Location #B: Full bath, Master bath, first floor
Location #C: Full bath, second floor
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Bathroom and laundry ventilation type: Spot exhaust fans
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Yes

36) Repair/Replace - The exhaust fan at the down stairs half bathroom was noisy or vibrated excessively. Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person clean, repair or replace fans as necessary.
Photo
Photo 36-1
 

37) Repair/Maintain - Water was leaking at the sink faucet base or handles at the upstairs bathroom. Recommend that a qualified plumber repair as necessary.
Photo
Photo 37-1
Photo
Photo 37-2

38) Repair/Maintain - Caulk around the base of the toilet at all bathrooms was missing. Modern standards require caulk to be installed around the entire toilet base where it meets the floor for sanitary reasons. Without it, soiled water can soak into flooring and sub-floor materials if the toilet overflows. Condensation from the toilet can also soak into the flooring. Recommend that a qualified person caulk around toilet bases per standard building practices.
Photo
Photo 38-1
Photo
Photo 38-2
Photo
Photo 38-3
 

39) Repair/Maintain - Gaps, no caulk, or substandard caulking were found several locations (sink, base of jetted tube, wall to backsplash, floor to tub and shower to floor) in the master bathroom and upstairs bathroom. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.
Photo
Photo 39-1
Photo
Photo 39-2
Photo
Photo 39-3
Photo
Photo 39-4
Photo
Photo 39-5
Photo
Photo 39-6

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Condition of interior doors: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Vinyl, Multi-pane
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Tile

40) Repair/Maintain - The glass sliding glass door caulking at the floor is starting to deteriorate and needs to be replaced. Recommend that a qualified person replace caulk as necessary.
Photo
Photo 40-1
Photo
Photo 40-2
Photo
Photo 40-3
 

41) Repair/Maintain - Three interior doors wouldn't latch, laundry room, upstairs bonus room and door to the room in the garage. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets.

Photo
Photo 41-1
Photo
Photo 41-2
Photo
Photo 41-3
Photo
Photo 41-4
Photo
Photo 41-5
Photo
Photo 41-6

42) Repair/Maintain - Some of the doors were missing door stops (den French doors, living room French doors and the upstairs closet). Door stops help prevent damage to walls. Recommend that a qualified person install door stops as necessary.
Photo
Photo 42-1
Photo
Photo 42-2
Photo
Photo 42-3
Photo
Photo 42-4
Photo
Photo 42-5
 

43) Minor Defect - Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product:
http://www.reporthost.com/?ECC

44) Evaluate, Monitor - Stains were found in laundry room ceiling areas. However, no elevated levels of moisture were found. The stain(s) may be due to past roof and/or plumbing leaks. Consult with the property owner and monitor the stained area(s) in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, then recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 44-1
Photo
Photo 44-2
Photo
Photo 44-3
 

45) Comment - Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the sub-floor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering and the access to the underside of the sub-floor. Recommend that a qualified contractor evaluate and repair as necessary. For more information, visit:
http://www.reporthost.com/?SQUEAK

Thank you for choosing A+ Handy Inspections, LLC. Please contact me at any time with questions regarding your inspection report.