Property Inspection Report-Mersman
Client(s): Ronald Mersman
Property address: 2886 S. 562 Road
Monkey Island, Oklahoma 74331
Inspection date: 5-9-2008
This report published on 5/10/2008 7:22:41 PM CDT

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Crawl space
Bathrooms
Interior rooms
 
General information Return to table of contents
Report number: 074
Structures inspected: Home and Dock
Age of building: 1970,s
Property owner's name: Ronald Mersman
Time started: 9:30am
Time finished: 12:30pm
Inspection Fee: $250
Payment method: Check
Present during inspection: Client(s), Realtor(s)
Occupied: No
Weather conditions: Clear
Temperature: Warm
Ground condition: Damp
Front of structure faces: North
Main entrance faces: North
Foundation type: Crawlspace
 
Exterior Return to table of contents
Footing material: Poured in place concrete
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Masonite
Driveway material: Poured in place concrete
Exterior door material: Solid core steel
Footing material: Poured in place concrete
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Masonite
Driveway material: Poured in place concrete
Exterior door material: Solid core steel


1) Non-metallic sheathed wiring is routed in one or more areas so it is subject to damage, such as on wall or ceiling surfaces. The insulation can be damaged by objects coming in contact with it and/or it being repeatedly moved. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary. For example, rewire using conduit, or re-routing through wall cavities.

Photo 7  
 

2) Fences and/or gates are damaged and/or deteriorated in some areas. A qualified contractor should evaluate and make repairs or replace sections as necessary.

Photo 6  
 

3) DOCK
The electrical outlet shows to have the hot and nuetral reveresed. This can cause damage to certain electrical devices when connected to this outlet.

Photo 2  
 

4) DOCK
The walway to the dock has become dislodged from its original foundation. It appears that floods have floated a 4x4 post which caused the walkway to rise.

Photo 1  
 

5) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.

Photo 8  
 

6) DOCK
Plants are starting to grow in the foam. These need to be removed to prevent foam deterioration.

Photo 3  
 
 
Roof Return to table of contents
Roof inspection method: Traversed
Roof type: Cross gable
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: 1 1/2 years
Gutter & downspout material: Aluminum
Roof ventilation: Adequate
7) Debris has accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

Photo 5  
 
 
Garage Return to table of contents

8) Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

Photo 9  

Photo 10  

9) The side door to the garage does not open correctly due to incorrect tolerance between the door and jam.

Photo 11  
 
 
Attic Return to table of contents
Inspection method: Viewed from hatch
Roof structure type: Rafters
Ceiling structure: Ceiling beams
Insulation material: Fiberglass roll or batt
Insulation depth: 8"
Insulation estimated R value: 29
 
Electric service Return to table of contents
Primary service type: Overhead
Primary service overload protection type: Circuit breakers
Service amperage (amps): 200
Service voltage (volts): 120/240
Location of main service switch: In service panel
Location of main disconnect: Breaker at top of main service panel
Service entrance conductor material: Aluminum
System ground: Cold water supply pipes
Main disconnect rating (amps): 200
Branch circuit wiring type: Copper
Solid strand aluminum branch circuit wiring present: No
Smoke detectors present: No
 
Water heater Return to table of contents
Estimated age: 1 year
Type: Tank
Energy source: Electricity
Capacity (in gallons): 50
Manufacturer: Whirlpool
Model: E1F5ORD045V
Water temperature (degrees Fahrenheit): Not Available due to water shut off
 
Heating and cooling Return to table of contents
Estimated age: 1-2 years
Primary heating system energy source: Electric
Primary heat system type: Forced air
Primary A/C energy source: Electric
Primary Air conditioning type: Split system
Distribution system: Flexible ducts
Manufacturer: Lennox
Model: 13HPD-024-230-01
Filter location: At the base of the furnace
Last service date: 2007
 
Plumbing and laundry Return to table of contents
Water pressure (psi): 80LB
Location of main water shut-off valve: METER
Location of main water meter: Driveway
Water service: Public
Service pipe material: Copper
Supply pipe material: Copper
Vent pipe material: Plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
10) Water supply valve for washing machine leaks.

Photo 12  
 
 
Crawl space Return to table of contents
Inspection method: Traversed
Insulation material underneath floor above: Fiberglass roll or batt
Pier or support post material: Concreteshimmed and leveled with concrete blocks
Beam material: Solid wood
Floor structure above: Solid wood joists
Vapor barrier present: No
11) The rawl space has been used to store unserviceable items. recommend removal to allow access and prevent soil to wood contact. This may cause a situation where rot can occur that may invite pest infestation.

Photo 16  
 

12) Concrete blocks with wood shims have been used during addition of room. Recommend evaluation be performed by a professional contractor familiar with this building process.
Referral:
Matt Janes
918-271-1033

Photo 15  
 
 
Bathrooms Return to table of contents

13) One or more electric receptacles have reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

Photo 13  
 
 
Interior rooms Return to table of contents

14) One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.

Photo 14  
 

 