Summary Page

Home Inspection Report
Client(s): Joe Sample #2
Property address: 123 Sample Rd.
Sampletown, PA 12345
Inspection date: September 16, 2009

This summary page published on 10/7/2009 6:36:32 PM EDT

Return to report

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.


1) General information: Safety, Repair/Replace - This property has one or more fuel burning appliances, and no carbon monoxide alarms are visible. This is a safety hazard. Recommend installing one or more carbon monoxide alarms as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

2) General information: Safety, Comment - Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:

  • The Environmental Protection Association (http://www.epa.gov)
  • The Consumer Products Safety Commission (http://www.cpsc.gov)
  • The Center for Disease Control (http://www.cdc.gov)
    3) General information: Comment - Many wall, floor and/or ceiling surfaces were obscured by large amounts of furniture and/or stored items. Many areas couldn't be evaluated.

    4) Exterior: Safety, Repair/Replace, Evaluate - One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

    Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.

    5) Exterior: Safety, Repair/Replace, Evaluate - One or more outdoor electric receptacles appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all outdoor receptacles within six feet six inches of ground level have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    6) Exterior: Safety, Repair/Replace - One or more exterior electric receptacles aren't waterproof or rated for use in wet areas. This is a safety hazard due to the risk of shock and fire. Repairs should be made as necessary, and by a qualified electrician if necessary, so all exterior receptacles are waterproof as per standard building practices.

    7) Exterior: Repair/Replace - One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.

    8) Exterior: Repair/Replace - Gaps exist at one or more openings around the exterior, such as those where outside faucets, refrigerant lines, and/or gas supply pipes penetrate the exterior. Gaps should be sealed as necessary to prevent moisture intrusion and entry by vermin.

    9) Exterior: Comment - Minor cracks were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.

    10) Roof: Repair/Replace, Evaluate - One or more sections of flashing at the base of the chimney are deteriorated and/or substandard. Leaks may occur as a result. A qualified roofing contractor should evaluate and repair as necessary.

    11) Roof: Repair/Replace - One or more "rubber boot" flashings are damaged or deteriorated and may result in leaks or vermin intrusion. A qualified contractor should replace flashings where necessary.

    12) Garage: Comment - Much of the garage, including areas around the interior perimeter and in the center are excluded from this inspection due to lack of access from stored items.

    13) Electric service: Safety, Repair/Replace - The service drop wires are in contact with trees or vegetation. Recommend having a qualified tree service company or arborist prune or remove trees as necessary to prevent straining or abrading the service drop wires.

    14) Electric service: Major Defect, Repair/Replace, Evaluate - The electric service to this property appears to be rated at substantially less than 200 amps, and may be inadequate for the client(s) needs. Recommend consulting with a qualified electrician about upgrading to a 200 amp service.

    15) Water heater: Safety, Repair/Replace - Temperature-pressure relief valve drain line is too short. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should extend the drain line to 6 inches from the floor, or route it so as to drain outside.

    16) Plumbing and laundry: Safety, Repair/Replace - The clothes dryer is equipped with a vinyl or foil, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information, visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5022.html

    17) Plumbing and laundry: Safety, Comment - Copper water supply pipes in homes built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client(s) should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client(s) should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:

  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than six hours.
  • Install appropriate filters at points of use.
  • Use only cold water for cooking and drinking. Hot water dissolves lead more quickly than cold water.
  • Use bottled or distilled water.
  • Treat well water to make it less corrosive.
  • Have a qualified plumbing contractor replace supply pipes and/or plumbing components as necessary.

    For more information visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
    http://www.epa.gov/safewater/lead/index.html
    18) Plumbing and laundry: Repair/Replace - The clothes dryer exhaust duct is routed vertically. This can result in extended drying times, premature failure of the motor, drum rollers and heater. Recommend having a qualified contractor reconfigure the clothes dryer exhaust duct so it is routed horizontally, or as close to it as possible.

    19) Basement: Safety, Repair/Replace, Evaluate - One or more electric receptacles have reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

    20) Kitchen: Safety, Repair/Replace, Evaluate - One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    21) Bathrooms: Safety, Repair/Replace, Evaluate - One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    22) Interior rooms: Safety, Minor Defect - Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.