2816 Charleston St NE 
Albuquerque NM 87110-2702
Inspector: Henry Schichtel

 

Property Inspection Report

Client(s):  Client
Property address:  1234 Street
Albuquerque NM
Inspection date:  Monday, April 25, 2016

This report published on Monday, May 09, 2016 9:06:04 PM MDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard
Repair/ReplaceRecommend repairing or replacing
Repair/MaintainRecommend repair and/or maintenance
MaintainRecommend ongoing maintenance
EvaluateRecommend evaluation by a specialist
MonitorRecommend monitoring in the future
CommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Attachments
Thermal_Imaging_Addendum.pdf


General Information
Return to table of contents

Time started: 11:05
Time finished: 3:00
Present during inspection: Realtor
Client present for discussion at end of inspection: No
Weather conditions during inspection: Sunny
Temperature during inspection: Cool, 66 degrees
Type of building: Single family
Buildings inspected: One house
Source for main building age: Realtor
Front of building faces: South
Main entrance faces: South
Occupied: Yes, Furniture or stored items were present

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Moderate slope, Slope in front, level in back
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground, with binoculars
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Stucco
Condition of foundation and footings: Not determined
Apparent foundation type: Concrete slab on grade

1) Repair/Maintain - Cracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture can enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco can become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.

2) Repair/Maintain - Water stains and deterioration to the exterior stucco was noted. Landscaping, gutters, and proper sprinkler adjustment can prevent stucco damage from water. Recommend avoiding excessive water to hit house to prevent stucco damage and repair stucco.
Photo
Photo 2-1
Photo
Photo 2-2
Photo
Photo 2-3
Photo
Photo 2-4
Photo
Photo 2-5
Photo
Photo 2-6
Photo
Photo 2-7
Photo
Photo 2-8
Photo
Photo 2-9
 

3) Maintain - Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.
Photo
Photo 3-1
Photo
Photo 3-2
Photo
Photo 3-3
Photo
Photo 3-4
Photo
Photo 3-5
Photo
Photo 3-6

4) Maintain - Caulk was missing in some areas. For example, around windows and/or at siding-trim junctions. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
http://www.reporthost.com/?CAULK
Photo
Photo 4-1
Photo
Photo 4-2
Photo
Photo 4-3
 

5) Monitor - One or more windows or doors were installed with no "drip cap" or "Z" flashings installed above them, or the flashing was not visible. Better building practices call for such flashings, which greatly reduce the chance of leaks above windows and doors. Without this flashing, caulk and paint must be maintained or water can enter the wall structure and cause rot and possible structural damage. Depending on the exposure (e.g. roof overhang, height of exterior wall, direction of prevailing rain) this may or may not be an issue. The client should monitor these areas in the future and maintain caulk and paint as necessary. Consult with a qualified contractor about installing flashings where needed, and per standard building practices. Note that when trim or siding is removed to install flashing, damaged wood may be found and additional repairs may be needed.
Photo
Photo 5-1
 

6) - Minor cracks noted in stucco finish. This could be from normal building settling. All cracks should be sealed (caulked, etc) especially any larger than 1/8" to prevent water and insect intrusion.
Photo
Photo 6-1
Photo
Photo 6-2
Photo
Photo 6-3
Photo
Photo 6-4
Photo
Photo 6-5
Photo
Photo 6-6
Photo
Photo 6-7
Photo
Photo 6-8
Photo
Photo 6-9
 

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Viewed from ground with binoculars
Condition of roof surface material: Appeared serviceable
Roof surface material: Clay tile
Roof type: Hipped
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)

7) Repair/Replace, Repair/Maintain - One or more gutters and/or downspouts were incomplete, missing and/or leaking. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.

One section of gutter in front of house has no ability to drain. Recommend connecting sections to be able to drain.
Photo
Photo 7-1
Gutter section to the left has no downspout therefore no way to drain collected water. Suggest connecting gutters with a 90 degree outside turn section to connect gutter systems.
Photo
Photo 7-2
Stains indicate possible leaking union.
Photo
Photo 7-3
Photo
Photo 7-4

8) Repair/Replace - Gutters were missing over one or more entrances. People entering and exiting the building are likely to get wet during periods of rain as a result. Most buildings benefit from having a complete drainage system installed, but at a minimum, recommend installing gutters over entrances.
Photo
Photo 8-1
Photo
Photo 8-2
At this back entrance, the failing water is actually starting to stain and deteriorate the stucco.

9) Repair/Replace - Extensions such as splash blocks or drain pipes for one or more downspouts were poorly sloped. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 9-1
 

10) Repair/Maintain - Located in the back east corner area. Tile looks to be installed improperly and could potentially come loose. The current placement of the tile is not shedding water therefore should be reinstalled correctly to function properly. Leaks may occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person replace tiles or make repairs as necessary.
Photo
Photo 10-1
 

11) Repair/Maintain - Small cracks were found around the masonry sealant areas of the skylight. This is often caused by the exterior drying prior to the masonry curing. This may eventually result in water penetrating the underlying roof membrane and causing leaks. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 11-1
 

12) Monitor - Stains were found on one or more gutters that indicate past leaks have occurred. However, the inspector was unable to verify that the gutters do or don't leak because of lack of recent rainfall. Monitor the gutters in the future while it's raining to determine if gutters leak. If they do, then recommend that a qualified person repair as necessary to prevent water from coming in contact with the building or accumulating around the building foundation.
Photo
Photo 12-1
Photo
Photo 12-2

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Trusses
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Appeared serviceable
Ceiling insulation material: Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas): R-19
Vermiculite insulation present: None visible
Vapor retarder: None
Condition of roof ventilation: Appeared serviceable
Roof ventilation type: Enclosed soffit vents, Seems appropriate for climate.

13) Comment - Attic structure and insulation seem to be in satisfactory condition. These thermal images illustrate the insulation at work, note the red roof but cool insulated ceiling.

Insulation is roughly 6 inches deep in the attic. Fiberglass provides roughly r-3 per inch deep.
Photo
Photo 13-1
Photo
Photo 13-2
Photo
Photo 13-3
Photo
Photo 13-4
Photo
Photo 13-5
Photo
Photo 13-6
Photo
Photo 13-7
Photo
Photo 13-8

Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Solid core, Wood
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of automatic opener(s): Appeared serviceable
Mechanical auto-reverse operable (reverses when meeting reasonable resistance during closing): No
Condition of garage floor: Appeared serviceable
Condition of garage interior: Required repair or evaluation (see comments below)
Garage ventilation: Exists, Adequate

14) Safety, Repair/Replace - One or more garage vehicle doors were damaged or deteriorated. Recommend that a qualified contractor repair or replace door(s) as necessary.

The dent in the middle upper section has actually caused some structural compromise. The door flexes at this point while the door is being operated. This is an indicator of a weakness in the door and therefore should repaired/replaced. Being that the garage door is one of the heaviest doors in the house, this is viewed as a safety concern.
Photo
Photo 14-1
 

15) Safety, Repair/Maintain, Evaluate - The auto-reverse mechanism on one or more automatic openers for garage vehicle doors was inoperable. This is a potential safety hazard. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
http://www.reporthost.com/?NRGD

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Service voltage (volts): 120-240
Estimated service amperage: 150
Primary service overload protection type: Circuit breakers
Main disconnect rating (amps): 150
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: No
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: No, recommend install
Smoke alarms installed: Yes, but not tested, No, recommend install, One installed, one missing
Carbon monoxide alarms installed: Yes, but not tested

16) Safety, Repair/Replace, Evaluate - One or more electric receptacles at the exterior had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
Photo
Photo 16-1
 

17) Safety, Repair/Replace - One or more light fixtures installed outside were substandard. This is a potential shock and/or fire hazard. Recommend that a qualified electrician repair as necessary.

Exterior light fixtures should be caulked to home to avoid water intrusion into electrical system.
Photo
Photo 17-1
Photo
Photo 17-2
Photo
Photo 17-3
 

18) Repair/Replace, Evaluate - One or more electric receptacles appeared to have no power after testing. One outlet found in each bathroom seem to be wired in the same run to a GFCI protection but inspector was unable to locate the circuit reset. Recommend asking the property owner about this. Switches may need to be operated or GFCI/AFCI protection may need to be reset to make some receptacles energized. If necessary, recommend that a qualified electrician evaluate and repair.
Photo
Photo 18-1
Photo
Photo 18-2

19) Repair/Replace, Evaluate - Vanity light in hallway bathroom has an electrical 'humming' sound when tuned on. This could indicate incorrect wiring. Recommend further evaluation and repair by qualified electrician.

Also one bulb was out during inspection. Recommend replacing.
Photo
Photo 19-1
 

20) Repair/Replace - Ceiling fan located in main living room was found to have no fan blades. Recommend reinstall fan blades prior to use.

21) Evaluate - One or more light fixtures were inoperable (didn't turn on when nearby switches were operated). Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.

Locations: Garage light and master bedroom fan.

22) Evaluate - Inspector was unable to determine the function of these switches in the master bedroom after a thorough search. Recommend asking owner about this and evaluate.
Photo
Photo 22-1
 

23) Comment - Being that the inspection was during the day, all outside motion lights were not inspected. Recommend evaluate during night.
Photo
Photo 23-1
Photo
Photo 23-2

24) Comment - Breaker box with removed dead panel. Thermal imaging shows no excessive heat coming from the breakers while under various electrical loads.
Photo
Photo 24-1
Photo
Photo 24-2

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water shut-off: Building exterior, Outside curb
Condition of supply lines: Not visible
Supply pipe material: Not determined (inaccessible or obscured)
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Sewage ejector pump installed: No
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: Below ground
Location of main fuel shut-off valve: At gas meter

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Garage
Hot water temperature tested: No
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Furnace
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: 10/26/2008
Source for last service date of primary heat source: Label
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 2008
Location of forced air furnace: Garage
Forced air system capacity in BTUs or kilowatts: 72000
Condition of furnace filters: Required replacement
Location for forced air filter(s): Behind return air grill(s), In return vent
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Vent(s) to exterior
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: west
Type: Split system
Condition of controls: Appeared serviceable

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of gas-fired fireplaces or stoves: Appeared serviceable
Gas fireplace or stove type: Metal pre-fab fireplace
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Metal
Gas-fired flue type: B-vent

25) Repair/Replace - One or more masonry chimney crowns were worn and/or deteriorated. Crowns are meant to keep water off of the chimney structure and prevent damage from freeze-thaw cycles. Chimney crowns are commonly constructed by mounding concrete or mortar on the top chimney surface, however this is substandard. A properly constructed chimney crown should:
  • Be constructed using either precast concrete slabs, cast-in-place steel reinforced concrete, solid stone, or metal
  • Be sloped down from the flue a minimum of 3 inches of fall per foot of run
  • Extend a minimum of 2 1/2 inches beyond the face of the chimney on all sides
  • Not directly contact the flue liner (if installed), with the gap filled with flexible caulk
  • Have flashing installed between the bottom of the crown and the top of the brick chimney
Recommend that a qualified contractor repair or replace crowns as necessary, and per standard building practices.

Looks like some repairs have already been made, but there are still signs of deterioration/cracks.
Photo
Photo 25-1
Photo
Photo 25-2

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable, Not determined
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable, Not determined
Condition of built-in microwave oven: Appeared serviceable, Not determined

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Master bath
Location #B: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Required repair, replacement and/or evaluation (see comments below)
Bathroom and laundry ventilation type: Windows, Spot exhaust fans, with individual ducts
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Yes

26) Safety, Repair/Replace - The exhaust fan at location(s) #B and/or Hallway was inoperable. Moisture may accumulate and result in mold, bacteria or fungal growth. Recommend that a qualified person clean, repair or replace fans as necessary.

Thermal imaging also showed excessive heat twenty minutes after operation. Even with good insulation, this seems to be unlikely to retain so much heat. Could possibly be electrical in nature and may be the reason for the fan not working. If so, this is a fire hazard.
Photo
Photo 26-1
Photo
Photo 26-2
Photo
Photo 26-3
 

27) Repair/Maintain - One or more sink drains were leaking at location(s) #A (left master bathroom). A qualified person should repair as necessary.

Small leak, drain pipes may just need tightening. Recommend evaluate and repair.
Photo
Photo 27-1
 

28) Comment - Dryer vent terminates outside with damper stuck open. This should be repaired to avoid pests from entering the appliance and home.
Photo
Photo 28-1
 

29) Comment - Toilets should not be caulked around base, toilets are sealed by their wax ring and if/when it fails, caulked toilets may not show leak. This is information only, no repairs needed at this time.
Photo
Photo 29-1
 

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows: Metal
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Wood or wood products, Tile

30) Repair/Replace, Evaluate - Condensation or staining was visible between multi-pane glass in one or more . This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's R-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.
Photo
Photo 30-1
 

31) Comment - Screens were missing from some windows. These windows may not provide ventilation during months when insects are active.

32) Comment - Many windows were found to have clear tape along the frame and glass seams. Recommend asking seller about this, further evaluation.
Photo
Photo 32-1
Photo
Photo 32-2

33) Comment - Thermal imaging can demonstrate where insulation is lacking and energy (heat and cold) is getting through into the living space, thus, costs more to keep the home comfortable. Please know that this is coming from a energy loss stand point and not a defect.
Photo
Photo 33-1
A) digital picture to reference location of picture C.
Photo
Photo 33-2
B) Picture D shows the heat entering where there is a gap in insulation.
Photo
Photo 33-3
C) crosshairs on triangular insulation gap.
Photo
Photo 33-4
D) Red/orange areas are insulation gaps in the wall seen in picture B.
Photo
Photo 33-5
E) Area in attic showing lack of insulation as noted in pictures A & C.
 

34) - Wall behind water heater is showing possible previous water damage. Selling realtor stated that previous water heater failed. Tested area for moisture with thermal imaging and moisture meter. Measurements indicate the presence (past and current) of moisture, but high enough levels to promote mold. It is possible that the walll is still drying from failed water heater incident.
Photo
Photo 34-1
Photo
Photo 34-2
Photo
Photo 34-3
Photo
Photo 34-4


Photo
Photo X-1
Photo
Photo X-2
masonry tool left on the roof from last roof repair/maintenance. Should be removed to avoid falling on someone.
Photo
Photo X-3
Downspout noted from one roof transition to another. This is correctly installed.
Photo
Photo X-4
Some minor water damage noted in the eaves in this one spot. All other area have seemed to be repaired.
Photo
Photo X-5
Minor crack noted in garage above exterior door.
Photo
Photo X-6
Photo
Photo X-7
Inspection limited by occupied house and stored items.
Photo
Photo X-8
Photo
Photo X-9
Photo
Photo X-10
Photo
Photo X-11
Photo
Photo X-12
Water Heater
Photo
Photo X-13
Furnace
Photo
Photo X-14
Photo
Photo X-15
Photo
Photo X-16
Photo
Photo X-17
Photo
Photo X-18
Photo
Photo X-19
Photo
Photo X-20
Photo
Photo X-21
Photo
Photo X-22
Photo
Photo X-23
CO and smoke detecters were not tested but are obviously not functional at time of inspection.
Photo
Photo X-24
Photo
Photo X-25
Photo
Photo X-26
Photo
Photo X-27
Photo
Photo X-28
Photo
Photo X-29
Photo
Photo X-30
Photo
Photo X-31
Photo
Photo X-32
Photo
Photo X-33
Photo
Photo X-34
Chimney flue is in great condition.
Photo
Photo X-35
Photo
Photo X-36
These three pictures illustrate no active water leaks readable by the water meter at the end of the inspection.
Photo
Photo X-37
These three pictures illustrate no active water leaks readable by the water meter at the end of the inspection.
Photo
Photo X-38
These three pictures illustrate no active water leaks readable by the water meter at the end of the inspection.
Photo
Photo X-39
A/C nomenclature
Photo
Photo X-40
Picture shows register in living room blowing cool air. Note the blue pattern and dark rectangle.

Prepared for: Client