Property Inspection Report

Client(s):  Satisfied Customer
Property address:  100 Vintage Blvd
Outoftown, KY
Inspection date:  Thursday, April 4, 2052

This report published on Monday, September 18, 2023 3:50:03 PM EDT

This report is the exclusive property of Fulcrum Home Inspection and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
International Association of Certified Home Inspectors Better Business Bureau InterNACHI Certified Professional Inspector (CPI) State of Kentucky

How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at https://www.reporthost.com/glossary.asp

Table of Contents

General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Carport
Attic and Roof Structure
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Wood Destroying Organism Findings

View summary
Attachments
DixieMoore400WBroadwayEminenceKYhomeinprovements.pdf
FulcrumPreinspectionAgreement051318.pdf
InterNachiHomeInspectionStandardsofPractice.pdf

General Information
Table of contents
Report number: Sample4ksh18
Time started: 12 pm
Time finished: 3:30 pm
Present during inspection: Property owner
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), overcast
Temperature during inspection: Warm, 75 F
Payment method: Check, #130
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 85 yrs, built in 1933 per the Owner
Front of building faces: Southwest
Main entrance faces: Southwest
Occupied: Yes, by owner Dixie Moore
Overview of property: Two story home, 3165 sq ft, with covered front porch, rear carport and deck, 5 bedrooms, 1 1/2 baths, five (inoperative) fireplaces, kitchen, living rooms, crawlspace, several window A/C units, two furnaces, a heat pump, and one A/C unit on the roof. Barn and detached building on the property (not inspected).
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC
2) Some areas and items at this property were obscured by furniture and/or debris. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.
3) This Home Inspection Report does not address environmental hazards.
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing. Any comments made regarding these items are as a courtesy only.
Site profile: Level, with minor slope from back to front
Condition of driveway: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Driveway material: Asphalt, Gravel
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open rear deck. Covered rear patio/carport, and covered front porch.
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch material: Wood
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Wood
4) Flashing from the deck ledger board could not be verified. Missing flashing at this location can cause moisture to accumulate between the ledger board and the building. Fungal rot may occur in this area and cause the ledger board fasteners to fail. The deck may separate from the building in this event. This is a potential safety hazard. Recommend that a qualified contractor install flashing above ledger board if not present per standard building practices. For more information, visit:
http://www.reporthost.com/?LB
http://www.reporthost.com/?SD
5) Handrails at one or more flights of stairs were not graspable and posed a fall hazard. Handrails should be 1 1/4 - 2 inches in diameter if round, or 2 5/8 inches or less in width if flat. Recommend that a qualified person install graspable handrails or modify existing handrails per standard building practices.
Photo
Photo 5-1 
6) A deck joist hanger was missing at the header board. Recommend installing the missing hanger.
Photo
Photo 6-1 
7) Settlement cracks, gaps, heaving and/or deterioration resulting in trip hazards were found in the front sidewalk leading to the front porch, and under the rear deck. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
Photo
Photo 7-1 
Photo
Photo 7-2 
Photo
Photo 7-3 
8) One or more deck post supports had missing bolts in their attachment brackets to the concrete underneath. Recommend that all bolts be in place in the attachment brackets for safety
Photo
Photo 8-1 
9) Fungal or moisture rot was found at the base of support posts of the deck. The wood covering at the topo of one post was missing. Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Photo
Photo 9-1 
Photo
Photo 9-2 
Photo
Photo 9-3 
10) The gravel driveway was in poor condition. Recommend that a qualified person repair as necessary. For example, by filling holes, grading and spreading new gravel and asphalt.
11) Wooden deck or porch surfaces and/or railings were overdue for normal maintenance. Recommend that a qualified person clean and preserve as necessary. Where decks have been coated with a finish such as opaque stains or paint, it may be too difficult to strip the finish and apply anything but paint or opaque stain. Where transparent stain or penetrating oil has been applied in the past, recommend that a penetrating oil be used. For more information, visit:
http://www.reporthost.com/?PENOIL
http://www.reporthost.com/?DKMAIN
Exterior and Foundation
Table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Aluminum siding
Condition of foundation and footings: Not determined
Apparent foundation type: Crawl space
Foundation/stem wall material: Not determined (inaccessible or obscured)
Footing material (under foundation stem wall): Not determined (inaccessible or obscured)
12) Major cracks or areas with damage were found in the masonry (brick) veneer below the exterior siding. This may indicate that settlement has occurred and/or that the foundation has failed. At a minimum, a qualified contractor should repair the damaged masonry veneer to prevent water from entering wall cavities and causing mold, fungal rot or structural damage. Beyond that Consult with a qualified engineer to determine if foundation repairs are needed, and/or if settlement is ongoing. Any such repairs should be made by a qualified contractor. Such contractors and engineers may include:
  • Foundation repair contractors who may prescribe repairs, and will give cost estimates for prescribed repairs
  • Masonry contractors who repair and/or replace brick veneer
  • Geotechnical engineers who attempt to determine if settlement is ongoing, and the cause of the settlement
  • Structural engineers who determine if repairs are necessary, and prescribe those repairs
Photo
Photo 12-1 
Photo
Photo 12-2 
13) Soil was in contact with or less than 6 inches from siding or trim. Regardless of what material is used for siding, it should not be in contact with the soil. If made of wood, siding or trim will eventually rot. For other materials, ground or surface water can infiltrate siding or trim and cause damage to the wall structure. Wood-destroying insects are likely to infest and damage the wall structure. This is a conducive condition for wood-destroying organisms. Recommend grading or removing soil as necessary to maintain a 6-inch clearance. Note that damage from fungal rot and/or insects may be found when soil is removed, and repairs may be necessary.
Photo
Photo 13-1 
Photo
Photo 13-2 
Photo
Photo 13-3 
14) A gap was found in the siding trim around one of the windows. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.
Photo
Photo 14-1 
Crawl Space
Table of contents
Limitations: The condition of the crawl space is disclaimed in this inspection. There was insufficient space (<30") for the inspector to make an adequate assessment of the conditions thereunder, as it would have required traversing it in a prone position laying down to make observations. Doing so would be unsafe if vermin, insects, glass and/or sharp objects were present that that could not be seen.
The crawl space hatch consisted of three 2x6 boards over the entrance which was in a narrow pantry/closet room in the back of the house. Getting access below the three boards proved to be difficult, and cumbersome as they boards had to be pried out of their resting place. The only accessible and safely observable area was just below the crawl space hatch which allowed for no visibility beyond the loose ducts and debris on the ground.No exterior vents were seen around the foundation but ventilation may be occurring through the brick veneer seen in a few places at the base of the siding. The inspector attempts to locate all crawl space access points and areas. But access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. When possible, crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Viewed from hatch
Condition of floor substructure above: Not determined (inaccessible or obscured)
Pier or support post material: Not determined (inaccessible or obscured) but appeared to be concrete block around the hatch area.
Beam material: Not determined (inaccessible or obscured).
Floor structure above: Not determined (inaccessible or obscured) but appeared to be solid wood around the hatch area.
Condition of insulation underneath floor above: Not determined (inaccessible or obscured)
Insulation material underneath floor above: None visible, Not determined (inaccessible or obscured)
Condition of vapor barrier: Not determined (inaccessible or obscured)
Vapor barrier present: None visible, Not determined (inaccessible or obscured)
Condition of crawl space ventilation: Required repairs, replacement and/or evaluation (see comments below)
Ventilation type: Not determined (inaccessible or obscured)
15) Ventilation for the crawl space was substandard. There were no vents visible. Poor or no ventilation can lead to moisture in the crawl space and is a conducive condition for wood-destroying organisms. One square foot of vent area should be installed for 150 square feet of crawl space. Vents should be evenly distributed and within a few feet of corners to promote air circulation. Recommend that a qualified contractor install or improve venting per standard building practices.
16) View of crawl space hatch area. The crawl space was inaccessible.
Photo
Photo 16-1 
Photo
Photo 16-2 
Photo
Photo 16-3 
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.

Home owner indicated new roof and gutters were installed in 2015.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable, Two-wings
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Appeared serviceable
17) Extensions such as splash blocks or drain pipes for one or more downspouts were missing. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure. One downspout was not attached to the drain on the ground, and should be connected so as not to leak runoff onto the carport.
Photo
Photo 17-1 
Photo
Photo 17-2 
18) Chimney without a rain cap.
Photo
Photo 18-1 
19) Chimneys need tuck pointing and/or repointing.
Photo
Photo 19-1 
Photo
Photo 19-2 
20) Tree limbs were overhanging the roof on a back corner. These should be trimmed back so they don't damage the roofing as they grow and drop leaves onto the roof causing mold or mildew.
Photo
Photo 20-1 
21) Small amounts of debris such as leaves, needles, seeds, etc. have accumulated on the roof surface. Water may not flow easily off the roof, and can enter gaps in the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend cleaning debris from the roof surface now and as necessary in the future.
Photo
Photo 21-1 
Photo
Photo 21-2 
Limitations: The inspector does not determine the adequacy of firewall ratings.
Type: Attached, Carport
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Solid core, Wood, Glass
22) Minor cracks were found in the concrete slab floor. These are common and appeared to be only a cosmetic issue.
23)  Views of carport
Photo
Photo 23-1 
Photo
Photo 23-2 
Attic and Roof Structure
Table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Required repair, replacement and/or evaluation (see comments below)
Ceiling insulation material: Loose fiberfill insulation, old.
Approximate attic insulation R value (may vary in areas): Not determined (inaccessible or obscured)
Vermiculite insulation present: Not determined
Vapor retarder: None visible
Condition of roof ventilation: Required repair, replacement and/or evaluation (see comments below)
Roof ventilation type: Box vents (roof jacks), only on rear gable roof.
24) The attic was access through a fold down stairway and hatch, which was not insulated. Recommend installing insulation as necessary and per current standards at hatches or doors for better energy efficiency. For more information, visit:
http://www.reporthost.com/?ATTACC

The folding stairway was close to a ceiling fan and had to be carefully unfolded so as not to come into contact with it. Recommend the ceiling fan be moved for safety reasons to eliminate the potential to come into contact with the folding stairway.
Photo
Photo 24-1 
25) One or more sections of the roof structure appeared to have substandard ventilation, soffit and/or ridge vents were missing. This can result in high attic and roof surface temperatures, reduce the life of the roof covering materials, and/or increase cooling costs. High levels of moisture are also likely to accumulate in the roof structure or attic, and can be a conducive condition for wood-destroying organisms. Standard building practices require one free square foot of ventilation for every 150 square feet of attic space, and that vents be evenly distributed between the lowest points of the roof structure and the highest points to promote air circulation. Often this means that both soffit vents and ridge or gable end vents are installed. Recommend that a qualified contractor evaluate and repair per standard building practices.

Double hung windows served as the gable vents in the attic. They were closed and had no screens so no ventilation was present as long as the windows were closed. Two dormers with windows were also present facing the front of the house but those too were closed. A fan was present next to one of the dormers but was not tested. Depending on the season, these windows would need to be open or closed to provide ventilation in the attic. Recommend having a qualified roofing professional review and recommend adding ridge and/or soffit vents to provide more convenient and effective ventilation.

No hatch was found for access to the back wing roof and that area is disclaimed from this inspection.
Photo
Photo 25-1 
Photo
Photo 25-2 
Photo
Photo 25-3 
26) The ceiling insulation installed in the attic was substandard (compacted and uneven) and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.
Photo
Photo 26-1 
Photo
Photo 26-2 
Photo
Photo 26-3 
27) No vapor retarder was visible in the attic. Such vapor retarders reduce the flow of moisture from living spaces below, up into the attic, and prevent damage from moisture. For example, fungal rot, mold, and ice dams on the roof. Vapor retarders are not a standard recommendation except for very cold regions and in cases where there is high humidity in the house during the winter. Based on conditions found during this inspection, recommend that a qualified contractor install a vapor barrier.
28) One or more ducts in the attic and/or crawl space (what was observable) were not insulated. This can result in moisture forming inside the duct or "sweating" on the outside of the duct depending on the surrounding air temperature and the exhaust air temperature. Recommend that a qualified person install insulation on exhaust ducts per standard building practices (typically R-4 rating), or replace uninsulated ducts with insulated ducts.
Photo
Photo 28-1 
Photo
Photo 28-2 
29) The attic access hatch had no insulation or weatherstripping. Weatherstripping should be installed around hatches or doors as necessary to prevent heated interior air from entering the attic. The hatch door should be insulated for the same reason. For more information, visit:
http://www.reporthost.com/?ATTACC
Photo
Photo 29-1 
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only.

Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection.

Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Ground rod in soil, on the gas meter side of the house
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Building exterior, in carport area
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed, Copper
Ground fault circuit interrupter (GFCI) protection present: No
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested, One on the 1st floor, and another on the 2nd floor.
Carbon monoxide alarms installed: No, recommend install
30) One or more electric receptacles (outlets) at the kitchen and/or bathroom(s) had no visible ground fault circuit interrupter (GFCI) protection present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI
31) Non-metallic sheathed wiring in the attic was routed on surfaces within 6 feet of one or more access hatches or doors, and was subject to damage. Wiring can be damaged when hatches are lifted and set aside, when stored items are moved into or out of the attic, etc. This is a potential shock and/or fire hazard. Recommend that a qualified electrician repair per standard building practices.
32) Non-metallic sheathed wiring was loose, unsupported, or inadequately supported at one or more locations. Such wiring should be trimmed to length if necessary and attached to runners or to solid backing with fasteners at intervals of 4 1/2 feet or less. Fasteners should be installed within 12 inches of all enclosures. Recommend that a qualified electrician repair per standard building practices.
Photo
Photo 32-1 
Photo
Photo 32-2 
33) An extension cord appeared to being used as permanent wiring at one location. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring is a potential fire and shock hazard, and indicates that wiring is inadequate and needs updating. Extension cords may be undersized. Connections may not be secure resulting in power fluctuations, damage to equipment, overheating and sparks that could start a fire. Recommend that a qualified electrician repair per standard building practices and eliminate extension cords for permanently installed equipment.
Photo
Photo 33-1 
Photo
Photo 33-2 
34) In the kitchen, near the 1/2 bathroom door, one 3-slot electric receptacle (outlets) was found with an open ground. This is a shock hazard when appliances that require a ground are used with these receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. Recommend that a qualified electrician repair as necessary so all receptacles are grounded per standard building practices.
35) One or more attic outlets were missing or had a broken cover plate. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 35-1 
36) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.reporthost.com/?SMKALRMLS
Photo
Photo 36-1 
37) No carbon monoxide alarms were visible. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
http://www.reporthost.com/?COALRM
38) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. Consult with a qualified electrician for repairs as necessary.
39) One or more electrical components including switches, receptacles and/or light fixtures appeared to be older than their intended service life. Such old components may pose a fire or shock hazard. Several switches throughout the house were inoperative or not connected to anything visible that would turn on and off. Recommend consulting with a qualified electrician to determine which components should be replaced with newer, modern components.
40) 2-slot receptacles (outlets) rather than 3-slot, grounded receptacles were installed in one or more areas. These do not have an equipment ground and are considered unsafe by today's standards. Appliances that require a ground should not be used with 2-slot receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. The client should be aware of this limitation when planning use for various rooms, such as an office. Upgrading to grounded receptacles typically requires installing new wiring from the main service panel or sub-panel to the receptacle(s), in addition to replacing the receptacle(s). Consult with a qualified electrician about upgrading to 3-wire, grounded circuits where required.
Photo
Photo 40-1 
41) A plug-in style light fixture was mounted on the wall by the entry door from the carport. Recommend that it be replaced with a permanent and more secure fixture.

There was also a loose wire hanging from the carport ceiling in one corner that should be removed or properly terminate with its function identified.
Photo
Photo 41-1 
Photo
Photo 41-2 
42) Other concerns

The front door bell did not work.
Closets in the 2nd floor bedrooms did not have lights in them.
Three closets in the game room had lights that were all controlled by one switch near the door.
Recommend that a licensed electrician repair or replace the above to normal operations.
43) The legend for circuit breakers or fuses in panel(s) #A was incomplete. This is a potential shock or fire hazard in the event of an emergency when power needs to be turned off. Recommend correcting the legend so it's accurate, complete and legible. Evaluation by a qualified electrician may be necessary.
Photo
Photo 43-1 
44) One or more light fixtures were inoperable (didn't turn on when nearby switches were operated) or had missing bulbs. Recommend further evaluation by replacing bulbs and/or consulting with the property owner. If replacing bulbs doesn't work and/or no other switch(es) can be found, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.
45)  Views of the main electric panel and meter
Photo
Photo 45-1 
Photo
Photo 45-2 
Photo
Photo 45-3 
Photo
Photo 45-4 
Plumbing / Fuel Systems
Table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Water service: Public
Location of main water shut-off: The main water shutoff was in a closet-like room at the rear of the house that served as a pantry and also included the washer and crawl space hatch.
Condition of supply lines: Not determined, not accessible and obscured
Supply pipe material: Not determined (inaccessible or obscured). Information provided by the homeowner's son : supply lines are copper.
Condition of drain pipes: Appeared serviceable from the crawl space hatch, (otherwise inaccessible and obscured)
Drain pipe material: Plastic from the crawl space hatch (otherwise inaccessible and obscured), and from information provided by the homeowners son
Condition of waste lines: Appeared serviceable from the crawl space hatch. Otherwise not determined (inaccessible or obscured)
Waste pipe material (otherwise inaccessible and obscured): Cast iron from the crawl space hatch
Vent pipe condition: Not determined (inaccessible and obscured)
Vent pipe material: Plastic from the crawl space hatch (otherwise inaccessible and obscured), and Information from the homeowners son: vent pipes are plastic.
Sump pump installed: No
Sewage ejector pump installed: No
Visible fuel storage systems: None visible
Location of main fuel shut-off valve: At gas meter
46) Insulation for one or more water supply pipes in the crawl space In the hatch area was missing. Recommend replacing or installing insulation on pipes per standard building practices to prevent them from freezing during cold weather, and for better energy efficiency with hot water supply pipes.
Photo
Photo 46-1 
Photo
Photo 46-2 
Photo
Photo 46-3 
47) No hose bibs (outside faucets) were found. Recommend that a qualified plumber install one or more hose bibs for convenience, and per standard building practices (e.g. frost-free with anti-siphon device).
48) No sediment trap was installed in the gas supply line at the water heater. Sediment traps prevent damage to gas-fired appliances by trapping oil, scale, water condensation and/or debris. Recommend that a qualified contractor install a sediment trap per standard building practices.
Photo
Photo 48-1 
49)  Main water and gas shut offs
Photo
Photo 49-1 
Photo
Photo 49-2 
Water Heater
Table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.

The water heater, a Reliance 606 model, is located in the half bathroom on the 1st floor by the kitchen. The data label for the water heater was on a side that was not accessible as a result of being in close proximity to a wall. The data on the label could not be read and its Date of Manufacture and capacity were not available. Information provided by the homeowner indicated it had been in service for a while.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Capacity (in gallons): Not determined (label obscure or inaccessible)
Temperature-pressure relief valve installed: Yes, but no drain line
Location of water heater: Utility room, Mechanical room
Condition of venting system: Appeared serviceable
50) The water heater did not have earthquake straps or struts installed. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines breaking if it's gas-fired, or electric wiring being damaged if powered by electricity. Leaks can also occur in water-supply pipes. Recommend that a qualified person install earthquake straps or struts as necessary and per standard building practices.
Photo
Photo 50-1 
51) The outer flame shield for the water heater combustion chamber was missing. This is a potential fire hazard. Recommend that a qualified person replace any missing flame shields.
Photo
Photo 51-1 
52) No drain line was installed for the temperature-pressure relief valve. Drain lines are normally installed to prevent water from accumulating if/when the valve eventually leaks, and to prevent scalding if someone is standing next to the water heater when the valve opens. Recommend that a qualified plumber install a drain line so it drains outside and per standard building practices.
Photo
Photo 52-1 
53) The estimated useful life for most water heaters is 8-12 years. The inspector was unable to determine the age of the water heater due to the manufacturer's label being obscured and inaccessible, not clearly indicating the age. The client should be aware that this water heater may be near, at or beyond its useful life and may need replacing at any time. Recommend attempting to determine the water heater's age.

If found to be near, at or beyond its useful lifespan, recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater does fail. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 53-1 
Heating, Ventilation and Air Condition (HVAC)
Table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only.

Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).

two split HVAC systems - forced air
1) 1st floor split system - year built 2014, Carrier gas furnace model 58PH*090-1-16, capacity 90,000 BTU/hr
and Carrier heat pump model CNPVP4821ALAAAAA, serial no. 2614X26165, capacity 4 ton, 410A refrigerant

2) Attic split system - year built 2013, Carrier gas furnace model 58STA070-12, serial no. 0413A15578, capacity 70,000 BTU/hr, and air conditioner on the roof, data label not available.
General heating system type(s): Forced air, Furnaces
General heating distribution type(s): Ducts and registers
Source for last service date of primary heat source: Per information provided by the home owner, the last service dates were when the units were in stalled: 2013 for the attic unit, and 2014 for the 1st floor unit
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 1st floor furnace 2014, 4 yrs, Attic furnace 2013, 5 yrs
Location of forced air furnaces: 1st floor furnace stacked on top of heat pump, attic furnace and air conditioner on roof
Forced air system capacity in BTUs or kilowatts: 1st floor unit: 90,000 BTU/hr, attic unit 70,000 BTU/hr
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At base of air handlers
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct, Vent(s) to exterior, Vented door
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: 1st floor appeared serviceable, roof top A/C needs evaluation by a qualified HVAC professional
Cooling system and/or heat pump fuel type: Electric
Location: 1st floor heat pump located under the gas furnace in the 1/2 bath/water heater room, and a roof top air conditioner
Type: Split systems
Condition of controls: Appeared serviceable
54) The last service date of the gas furnaces appeared to be more than 1 year ago, according to information provided by the home owner. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service these systems, and make repairs if necessary.

For safety reasons, and because this system is fueled by gas, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP
Photo
Photo 54-1 
Photo
Photo 54-2 
Photo
Photo 54-3 
Photo
Photo 54-4 
Photo
Photo 54-5 
Photo
Photo 54-6 
Photo
Photo 54-7 
55) One or more cooling air supply registers on the 2nd floor had a weak air flow, or no apparent flow. This may result in an inadequate air supply. Recommend asking the property owner about this. Adjustable damper(s) in ducts may exist and be reducing the flow. If dampers exist, then they should be opened to attempt to improve the air flow. If the property owner is unaware of such dampers, or if adjusting dampers does not improve the air flow, then recommend that a qualified HVAC contractor evaluate and repair or make modifications as necessary.
Photo
Photo 55-1 
56) The roof top air conditioner unit did not appear to respond to normal controls (thermostat) and may be inoperable. The inspector was only able to perform a limited evaluation. If possible, consult with the property owner and/or review documentation on this system. Recommend that a qualified HVAC contractor evaluate and perform maintenance or make repairs as necessary.
Photo
Photo 56-1 
Photo
Photo 56-2 
Photo
Photo 56-3 
57) One or more heating or cooling ducts in an unconditioned space (e.g. crawl space, attict) were not insulated, or the insulation was damaged or deteriorated. This can result in reduced energy efficiency, moisture inside heating ducts, and/or "sweating" on cooling ducts. Recommend that a qualified person repair per standard building practices. For example, by wrapping ducts in insulation with an R-value of R-8.
Photo
Photo 57-1 
Photo
Photo 57-2 
Photo
Photo 57-3 
58) Window air conditioners
Window units were installed in 1st and 2nd floor windows.
This may indicate there is a problem with getting adequate cooling in the house.
Recommend that a qualified HVAC professional evaluate the cooling systems and repair as needed to obviate the need for the window units if required.
Photo
Photo 58-1 
Photo
Photo 58-2 
Photo
Photo 58-3 
59) Recommend replacing or washing HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or washing them as necessary. How frequently they need replacing or washing depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).
Photo
Photo 59-1 
Photo
Photo 59-2 
60) The estimated useful life for most heat pumps and air conditioning units is 10-15 years. The inspector was unable to determine the age of the roof top air conditioner unit. It may be near, at, or beyond its useful life and may need replacing or significant repairs at any time. Recommend attempting to determine the age (ask property owner or service technician), and budgeting for a replacement if necessary.
Fireplaces, Stoves, Chimneys and Flues
Table of contents
Limitations: The following items are not included in this inspection: gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only.

Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.

There are 5 inoperative fireplaces in the house. Each fireplace was inaccessible as they were covered and not open to inspection.
Condition of wood-burning fireplaces, stoves: Not determined (inaccessible or obscured)
Wood-burning fireplace type: Masonry, Masonry with metal liner
Condition of chimneys and flues: Required repair, replacement and/or evaluation (see comments below), Not determined, Chimneys need repair
Wood-burning chimney type: Masonry, Metal
61) When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
Photo
Photo 61-1 
Photo
Photo 61-2 
62) One chimney was missing a rain cap and one should be installed to prevent water, and insects from entering.
63) Mortar at the brick chimneys was deteriorated (e.g. loose, missing, cracked). As a result, water is likely to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary. For example, by repointing the mortar.
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, dishwashers, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only.

Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: N/A (none installed)
Condition of dishwasher: N/A (none installed)
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Electric
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
64) The cooktop exhaust fan was inoperable. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 64-1 
65) There is a freezer in the kicthen that is inoperable.
66) The light in the exhaust hood was inoperable. Recommend replacing light bulb(s) or that repairs be made by a qualified person if necessary.
Bathrooms, Laundry and Sinks
Table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only.

Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Half bath, first floor
Location #B: Full bath, second floor
Condition of counters: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Central exhaust fan
240 volt receptacle for laundry equipment present: Yes
67) The inspector was unable to verify that the glass used in one or more doors by the shower at location(s) #B was approved safety glass. Glazing that is not approved safety glass located in areas subject to human impact is a potential safety hazard. Standard building practices require that approved safety glass be used in enclosures for bathtubs, showers, spas, saunas and steam rooms, and in windows where the bottom edge of the window is less than 60 inches above the drain inlet or standing surface. Wire-reinforced glass is not acceptable. Recommend that a qualified contractor evaluate further to determine if glazing is approved safety glass, and replace glass if necessary, and per standard building practices.
Photo
Photo 67-1 
68) One or more cabinets, drawers and/or cabinet doors at location(s) #B were damaged or deteriorated. Recommend that a qualified person repair or replace as necessary.
Photo
Photo 68-1 
69) Washer and dryer locations

The electric washer was located in the closet/pantry/crawl space hatch room at the rear of the building. Information provided by the home owner indicated that the washer and dryer were moved from their former location in the upstairs bath.
The electric dryer is in the kitchen.

Neither location is ideal for these appliances. Recommend that consideration be given to relocating them as need and convenience permit.
Photo
Photo 69-1 
Photo
Photo 69-2 
70) The corner by the bathtub at location(s) #B was water-damaged. Recommend that a qualified person repair as necessary.

No active leaking was observed and this may be a cosmetic issue.
Photo
Photo 70-1 
71) The clothes dryer exhaust duct was not visible in one or more places. Clothes dryers produce large amounts of moisture which should not enter structure interiors. Moisture can accumulate and result in mold, bacteria or fungal growth.
The dryer was located in the kitchen and there was lint on the back side of the unit and along the walls there. There may be an air leak or gap in the dryer hose. Recommend that a qualified person make permanent repairs as necessary. For more information, visit:
http://www.reporthost.com/?DRYER
Interior, Doors and Windows
Table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only.

Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic or environmental hazard substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood, Metal, Glass panel
Condition of interior doors: Appeared serviceable
Condition of windows: Appeared serviceable, Front windows require repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Vinyl, Wood, Metal, Multi-pane, Double-hung
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall or plaster, Paneling
Ceiling type or covering: Drywall or plaster
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Vinyl, linoleum or marmoleum, Tile
72) The inspector was unable to verify that the glass used in one or more exterior doors, sliding glass doors and/or storm doors was approved safety glass. Glazing that is not approved safety glass, located in areas subject to human impact, is a safety hazard. Standard building practices generally require that approved safety glass be used in swinging and sliding doors except where "art glass," jalousie windows or glazing smaller than a 3-inch opening is used. Recommend that a qualified contractor evaluate further to determine if glazing is approved safety glass, and replace glass if necessary, and per standard building practices.
Photo
Photo 72-1 
Photo
Photo 72-2 
Photo
Photo 72-3 
73) Floors in one or more areas were springy. This can be caused by over-spanned, undersized or too few joists or beams, or too few support posts. Recommend that a qualified contractor and/or engineer evaluate further. Repairs should be performed by a qualified contractor.
74) One or more windows that were designed to open and close were stuck shut. Recommend that a qualified person repair windows as necessary so they open and close easily.

Front windows were sealed shut with duct tape.
Photo
Photo 74-1 
Photo
Photo 74-2 
75) A window blind in a bedroom was loose and came down when operated. Recommend repair or replacement of this blind and any other with a similar looseness.
Photo
Photo 75-1 
76) Screens were missing from some, many and/or attic windows. These windows may not provide ventilation during months when insects are active.
Wood Destroying Organism Findings
Table of contents
Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.
Visible evidence of active wood-destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood-destroying insects: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood-destroying organisms: No


International Association of Certified Home Inspectors Better Business Bureau