Property Inspection Report

Client(s):  SAMPLE REPORT
Property address:  3715 Colony Cove Trl
Jacksonville FL 32277-2239
Inspection date:  Friday, February 19, 2016

This report published on Wednesday, April 13, 2016 12:18:40 PM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited. All Inspection Reports are Warrentied for 90 days.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
GENERAL INFORMATION
EXTERIOR
ROOF
ATTIC
GARAGE / CARPORT
HEATING AND COOLING SYSTEM #1
PLUMBING AND LAUNDRY
WATER HEATER
ELECTRIC SERVICE
FIREPLACES AND CHIMNEYS
KITCHEN
BATHROOMS
INTERIOR ROOMS
Water Test
Swimming Pool
WDO - INSPECTION FINDINGS & PHOTOS
Attachments
DUVAL-TAX-ROLLS.pdf
WDO-TERMITE-INSPECTION-SAMPLE.pdf
WIND-MITIGATION-SAMPLE.pdf


GENERAL INFORMATION
Return to table of contents

Date: Friday, February 19, 2016
INSPECTOR: MASTER - R.B.McCORMICK
Structures inspected: RESIDENTIAL
County: Duval
STORIES: 1
Type of building: Single family
Home Built In: 1969
Estimated Age of Home: 46 YRS
Total Square Footage: 2881
Heated Square Footage: 2400
Property owner's name: PARKE,R CHARLES J
Time started: 12:30PM
Time finished: 3:00PM
Inspection Fee: $600
Payment method: Cash, / PAID
Present during inspection: Client(s), Realtor(s)
Occupied: Yes
Weather conditions: Partly cloudy
Temperature: Cool
Ground condition: Dry
Front of structure faces: North, West
Main entrance faces: North, West
Foundation type: Slab on grade
The following items are excluded from this inspection: Security system
Agent: DEB SCOGIN
Contact #: 904.460.8934
Email: DENSCOGIN@WATSONREALTYCORP.COM
Broker / Realtor: WATSON REALTY CORP
Referring: AGENT: SHALIA STEUER
Report Specialist: JESSICA FRANK:

EXTERIOR
Return to table of contents

GFCI Outlet Present: NO
Footing material: Masonry
Foundation material: Brick
Apparent wall structure: Brick
Wall covering: Brick
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core wood

1) EXTERIOR DEFECTS:
Photo
Photo 1-1
EXTERIOR: INSULATION OFF PIPE
Photo
Photo 1-2
EXTERIOR: WINDOW GAS SEAL IS BROKEN
Photo
Photo 1-3
EXTERIOR: WINDOW GAS SEAL IS BROKEN
Photo
Photo 1-4
EXTERIOR: FENCE SLATS ARE LOOSE
Photo
Photo 1-5
EXTERIOR: FENCE BOARD DETACHED
Photo
Photo 1-6
EXTERIOR: FENCE BOARD DETACHED
Photo
Photo 1-7
EXTERIOR: SETTLING CRACK IN BRICK
Photo
Photo 1-8
EXTERIOR: TREE TOUCHING HOUSE

2) Fences and/or gates are damaged and/or deteriorated in some areas. A qualified contractor should evaluate and make repairs or replace sections as necessary.

3) Minor cracks were found in one or more sections of CONCRETE BLOCK / BRICK VENEER. A qualified contractor should evaluate and make repairs as necessary, such as repointing mortar to prevent water intrusion and further deterioration in the future.

4) Seals between double-pane glass in one or more sliding glass doors appear to have failed based on condensation or stains between the panes of glass. A qualified contractor should evaluate and replace glass where necessary.

The client(s) should be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Glass doors or windows other than those that the inspector identified may also have failed seals and need glass replaced too.

5) Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.

6)   EXTERIOR VIEWS:
Photo
Photo 6-1
EXTERIOR: FRONT
Photo
Photo 6-2
EXTERIOR: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 6-3
EXTERIOR: FRONT ENTRY
Photo
Photo 6-4
EXTERIOR: FRONT LOCK MECHANISMS OPERATIONAL
Photo
Photo 6-5
EXTERIOR: SIDE
Photo
Photo 6-6
EXTERIOR: REAR
Photo
Photo 6-7
EXTERIOR: SIDE
Photo
Photo 6-8
EXTERIOR: SIDE

ROOF
Return to table of contents

Permitting: Roofing Permit - R-08-250712.000 - FINALIZED - Paid: 4/29/2008 / Re roof
Permitting: Roofing Permit - R-89-27610.000 - EXPIRED - Paid: 8/11/1989 / 38 SQSRB LDB
Roof inspection method: Traversed
Roof type: Cross gable
Roof covering: Asphalt or fiberglass composition shingles
Shingle Type: Architect
Number of layers: 1
Gutter & downspout material: Aluminum
Roof ventilation: Adequate
Ventilation Type(s): Eave Vents, Roof Box Vent
ORIGINAL: NO
Estimated age of roof: 8 YRS
Estimated Remaining Life: Per-Manufacture: 15+ YRS

7) One or more plumbing vent pipes screens are missing. Animals such as vermin or may enter the vent space and nest or die. Leaves or debris may clog the vent and not allow proper venting and waste gasses may backup into home . A qualified contractor should install screens where missing using screen material .

8) ROOF DEFECTS:
Photo
Photo 8-1
ROOF VIEW: DEBRIS PRESENT
Photo
Photo 8-2
ROOF VIEW: PLUMBING VENT MISSING SCREEN
Photo
Photo 8-3
ROOF VIEW: TREE OVERHANGING HOUSE
Photo
Photo 8-4
ROOF VIEW: PLUMBING VENT MISSING SCREEN
Photo
Photo 8-5
ROOF VIEW: DEBRIS PRESENT
Photo
Photo 8-6
ROOF VIEW: DEBRIS PRESENT
Photo
Photo 8-7
ROOF VIEW: DEBRIS IN GUTTER
Photo
Photo 8-8
ROOF VIEW: PLUMBING VENT MISSING SCREEN
Photo
Photo 8-9
ROOF VIEW: TREE TOUCHING ROOF
Photo
Photo 8-10
ROOF VIEW: TREE TOUCHING ROOF
Photo
Photo 8-11
ROOF VIEW: DEBRIS IN GUTTER
 

9) Debris has accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

10) Debris such as leaves, needles, seeds, etc. have accumulated on the roof. This is a conducive condition for wood destroying insects and organisms since water may not flow easily off the roof, and may enter gaps in the roof surface. Leaks may occur as a result. Debris should be cleaned from the roof now and as necessary in the future.

11) Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.

12)   ROOF VIEWS:
Photo
Photo 12-1
AERIAL VIEW
Photo
Photo 12-2
ROOF VIEW
Photo
Photo 12-3
ROOF VIEW
Photo
Photo 12-4
ROOF VIEW
Photo
Photo 12-5
ROOF VIEW
Photo
Photo 12-6
ROOF VIEW
Photo
Photo 12-7
ROOF VIEW
Photo
Photo 12-8
ROOF VIEW
Photo
Photo 12-9
ROOF PERIMETER
 

ATTIC
Return to table of contents

Inspection method: Traversed
Roof structure type: Trusses
Ceiling structure: Trusses
SHEATHING TYPE: O.S.B. (ORIENTED STRAND BOARD)
Insulation material: Fiberglass loose fill, CLOSED Cell Spray Foam
Insulation depth: 6" LOOSE FILL / 4" CLOSED CELL FOAM
Estimated (R)esistance value: R-16 / R-24
ATTIC FAN INSTALLED: NO

13) ATTIC DEFECTS:
Photo
Photo 13-1
ATTIC: ACCESS NEEDS REPAIR
 

14) Pull-down stairs are installed for the attic access. No insulation is installed above the stairs and no weatherstripping is installed around the hatch perimeter. To reduce air leakage, recommend installing weatherstripping . An example of one can be seen at http://www.batticdoor.com/

Interior air leaking into the attic results in heating and cooling losses, increased energy costs, and a possible increase in moisture levels in the attic due condensation forming on the underside of the roof sheathing during cold weather.

15)   ATTIC VIEWS:
Photo
Photo 15-1
ATTIC: ACCESS
Photo
Photo 15-2
ATTIC VIEW
Photo
Photo 15-3
ATTIC VIEW
Photo
Photo 15-4
ATTIC VIEW
Photo
Photo 15-5
ATTIC: TRUSSES ON 16" CENTER
Photo
Photo 15-6
ATTIC: NAILS 2.5"
Photo
Photo 15-7
ATTIC: NAILS ON 6" CENTER
Photo
Photo 15-8
ATTIC VIEW
Photo
Photo 15-9
ATTIC VIEW
Photo
Photo 15-10
ATTIC: HURRICANE CLIP
Photo
Photo 15-11
ATTIC: INSULATION
Photo
Photo 15-12
ATTIC: ACCESS
Photo
Photo 15-13
ATTIC VIEW
Photo
Photo 15-14
ATTIC VIEW
Photo
Photo 15-15
ATTIC VIEW
 

GARAGE / CARPORT
Return to table of contents

GFCI Outlet Present: NO
Door Safety Sensors Present: YES
Driveway material: Poured in place concrete

16) One or more trip hazards were found in sidewalk and/or patio sections due to cracks, settlement and/or heaving. A qualified contractor should evaluate and repair or replace sidewalk and/or patio sections as necessary to eliminate trip hazards.

17) GARAGE / DRIVEWAY DEFECTS:
Photo
Photo 17-1
DRIVEWAY: CRACKS IN CONCRETE
Photo
Photo 17-2
DRIVEWAY: CRACKS IN CONCRETE
Photo
Photo 17-3
DRIVEWAY: CRACK IN CONCRETE
Photo
Photo 17-4
DRIVEWAY: DAMAGE TO CONCRETE
Photo
Photo 17-5
GARAGE: ELECTRICAL OUTLET NO GFCI PROTECTION
Photo
Photo 17-6
GARAGE: CRACK IN CEILING
Photo
Photo 17-7
GARAGE: LIGHT BULBS MISSINGS
Photo
Photo 17-8
GARAGE: BULBS FLICKERING

18) One or more light fixtures appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.

19) Minor cracks were found in ceilings / walls in one or more areas. They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.

20)   GARAGE / DRIVEWAY VIEWS:
Photo
Photo 20-1
EXTERIOR: GARAGE
Photo
Photo 20-2
EXTERIOR: DRIVEWAY
Photo
Photo 20-3
INTERIOR: GARAGE
Photo
Photo 20-4
GARAGE: DOOR
Photo
Photo 20-5
INTERIOR: GARAGE
Photo
Photo 20-6
GARAGE: ELECTRICAL OUTLET OPERATIONAL

HEATING AND COOLING SYSTEM #1
Return to table of contents

Permitting: Mechanical Permit - M-93-41974.000 - FINALIZED - Paid: 10/4/1993 /1 C/U TWN060 TRANE 51 A/H TWV060 TRANE 62M1 H/S BAY96X1510 TRANE 10KW
HEATING SYSTEM: AIR HANDLER:
Manufacturer: PAYNE
Model #: PGINMC061
Serial #: 1806A83359
TON'S: 5
BTU'S: 60, 000
Heating Temperature (F): 116.5
Primary heating system energy source: Electric
Primary heat system type: Forced air, Heat pump
EMER. HEAT STRIPS INSTALLED: YES
SIZE KILOWATT: 10KW
Visable Fuel Storage: NONE
Filter location: At the base of the furnace
Manufacture Date:: 5/2006
Estimated Age of Heating Unit: 10 YRS
Estimated Life Remaining Heating Unit: PER MFG: 5+ YRS
__________________________________________________:
COOLING SYSTEM: OUTSIDE UNIT:
Manufacturer: Carrier
Model #: 38YKC060300
Serial #: 3399E0518
TONS: 5.0
Cooling Temperature (F): 44.5
Primary A/C energy source: Electric
Primary Air conditioning type: Split system, Heat pump
Distribution system: Metal pipe
Manufacture Date: 6/1999
Estimated Age of Cooling Unit: 17 YRS
Estimated Life Remaining of Cooling Unit: 5+ YRS
Last service date: 12/11/2015
Thermostat Installed: YES
Thermostat Programmable: YES
Thermostat functioning: YES

21) HEATING / COOLING DEFECTS:
Photo
Photo 21-1
A/C HEAT PUMP: INSULATION MISSING
 

22) Insulation for the outside condensing unit's refrigerant lines is damaged, deteriorated and/or missing in one or more areas. This may result in reduced efficiency and increased energy costs. A qualified heating and cooling contractor should replace insulation as necessary.

23)   HEATING / COOLING VIEWS:
Photo
Photo 23-1
A/C HEAT: THERMOSTAT SET TO 68 DEGREES AT BEGINNING OF INSPECTION
Photo
Photo 23-2
A/C HEAT PUMP
Photo
Photo 23-3
A/C HEAT PUMP: SERVICE TAG
Photo
Photo 23-4
A/C HEAT PUMP: DISCONNECT
Photo
Photo 23-5
AIR HANDLER
Photo
Photo 23-6
AIR HANDLER: MODEL AND SERIAL NUMBERS
Photo
Photo 23-7
AIR HANDLER: SERVICE TAG
Photo
Photo 23-8
AIR HANDLER: LAST MAINTENACE: 12/11/2015
Photo
Photo 23-9
AIR HANDLER: FILTER LOCATION
Photo
Photo 23-10
A/C HEAT: A/C TEMPERATURE 44.5 DEGREES
Photo
Photo 23-11
A/C HEAT: HEAT TEMPERATURE 116.5 DEGREES
Photo
Photo 23-12
A/C HEAT: THERMOSTAT SET TO 68 DEGREES AT END OF INSPECTION

PLUMBING AND LAUNDRY
Return to table of contents

Permitting: Plumbing Permit - P-97-31058.000 - FINALIZED - Paid: 6/26/1997
Permitting: Plumbing Permit - P-94-47577.000 - FINALIZED - Paid: 10/25/1994 /13 FIXTURE REPIPE
Permitting: Plumbing Permit - P-86-11970.000 - EXPIRED - Paid: 5/5/1986 /LAWN SPRINKLERS NEW WATER METER SERVICE
WASHER PRESENT: YES, WORKING
DRYER PRESENT: YES, WORKING
GFCI Outlet Present: NO, / NO SINK
Water pressure (psi): 62 PSI
Location of main water meter: FRONT YARD
Location of main water shut-off: FRONT OF HOUSE
Visable Fuel Storage: NONE
Water service: Public
Service pipe material: Copper
Supply pipe material: CPVC
Vent pipe material: Cast iron
Drain pipe material: Plastic
Waste pipe material: Not visible
SEPTIC PRESENT: NO

24) PLUMBING / LAUNDRY / IRRIGATION DEFECTS:
Photo
Photo 24-1
IRRIGATION: NEEDS REPAIR
Photo
Photo 24-2
LAUNDRY ROOM: OUTLET LOOSE

25)   IRRIGATION VIEWS:
Photo
Photo 25-1
IRRIGATION: CONTROL
Photo
Photo 25-2
IRRIGATION: OPERATIONAL
Photo
Photo 25-3
IRRIGATION: OPERATIONAL
Photo
Photo 25-4
IRRIGATION: OPERATIONAL
Photo
Photo 25-5
IRRIGATION: OPERATIONAL
Photo
Photo 25-6
IRRIGATION: OPERATIONAL

26)   PLUMBING / LAUNDRY VIEWS:
Photo
Photo 26-1
PLUMBING: WATER SHUT OFF
Photo
Photo 26-2
PLUMBING: WATER PRESSURE GAUGE 60 PSI
Photo
Photo 26-3
PLUMBING: WATER SOFTENER
Photo
Photo 26-4
INTERIOR: LAUNDRY ROOM
Photo
Photo 26-5
LAUNDRY ROOM: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 26-6
BATHROOM #1: SINK
Photo
Photo 26-7
BATHROOM #1: TOILET
Photo
Photo 26-8
BATHROOM #2: SINK
Photo
Photo 26-9
BATHROOM #2: TOILET
Photo
Photo 26-10
BATHROOM #3: SINK
Photo
Photo 26-11
BATHROOM #3: TOILET
Photo
Photo 26-12
KITCHEN: GARBAGE DISPOSAL AND SINK

WATER HEATER
Return to table of contents

Permitting:
Type: Tank
Energy source: Electricity
Capacity (in gallons): 50
Manufacturer: American Standard
Model: E52-50R 045 DV
Serial #: 9724129764
Water temperature (degrees Fahrenheit): 116.5
LOCATION: GARAGE
PRESSURE RELIEF VALVE PRESENT: YES
SHUT OFF VALVE PRESENT: YES
CATCH PAN PRESENT (INSIDE ONLY): YES
DATE OF MANUFACTURE: 1997
Estimated Age of Unit: 18 YRS
Estimated Life Remaining PER MFG: 1+ YRS

27) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.

NOTE: CHANGING THE HEATING ELEMENTS WHEN TEMPERATURE DROPS MAY ONLY BE NECCESARY INSTEAD OF REPLACING THE TANK IF IT IS IN GOOD CONDITION.

28) WATER HEATER DEFECTS:

29)   WATER HEATER VIEWS:
Photo
Photo 29-1
WATER HEATER
Photo
Photo 29-2
WATER HEATER: PRESSURE RELIEF VALVE
Photo
Photo 29-3
WATER HEATER: SHUT OFF VALVE
Photo
Photo 29-4
WATER HEATER: SERVICE TAG
Photo
Photo 29-5
KITCHEN: HOT WATER TEMPERATURE 116.5 DEGREES
 

ELECTRIC SERVICE
Return to table of contents

Permitting: Electrical Permit - E-05-61220.000 - EXPIRED - Paid: 10/13/2005 / $ 5.00 CHANGE OUT 2 SWITCHES
Permitting: Electrical Permit - E-94-49740.000 - FINALIZED - Paid: 11/8/1994 / 13995184/01METER REGROUND & REPLACE DEFECTIVERECEPT.PAT
Permitting: Electrical Permit - E-93-41750.000 - FINALIZED - Paid: 9/30/1993 /INSTALL CIRCUITS FOR AND CONNECT HEATAND AC METER 13995184-01
Primary service type: Underground
Primary service overload protection type: Circuit breakers
MAIN PANEL:
Main Panel Location: GARAGE
Manufacture: GENERAL ELECTRIC
MAIN Panel Service amperage (amps): 150
Service voltage (volts): 120/240
Location of main service switch: GARAGE
Main disconnect rating (amps): 150
Location of main disconnect: Breaker at top of main service panel
Sub Panels: 0
Service entrance conductor material: Aluminum
System ground: Copper
Branch circuit wiring type: Copper, Aluminum multi-strand
Solid strand aluminum branch circuit wiring present: No
Smoke detectors present: Yes
Permitting:

30) ELECTRICAL DEFECTS:
Photo
Photo 30-1
ELECTRIC PANEL: BREAKER WAS IN THE OFF POSITION WHEN INSPECION STARTED
 

31)   ELECTRICAL VIEWS:
Photo
Photo 31-1
ELECTRIC SERVICE METER
Photo
Photo 31-2
ELECTRIC: GROUND WIRE
Photo
Photo 31-3
ELECTRIC PANEL
Photo
Photo 31-4
ELECTRIC PANEL
Photo
Photo 31-5
ELECTRIC PANEL: WIRING
Photo
Photo 31-6
ELECTRIC PANEL: MAIN SUPPLY FEED
Photo
Photo 31-7
ELECTRIC PANEL: GROUND WIRE
Photo
Photo 31-8
ELECTRIC PANEL: BRANCH WIRING
Photo
Photo 31-9
ELECTRIC PANEL: BRANCH WIRING
 

FIREPLACES AND CHIMNEYS
Return to table of contents

Fireplace type: Masonry
Chimney type: Masonry
Fire Place Usage Type: WOOD

32) A wood burning fireplace has been converted to use gas logs, and no glass doors are installed on the fireplace. For gas conversions like this, the fireplace damper is modified so it is permanently open to prevent combustion gases from the pilot light and main burners accumulating in living spaces. Since the damper is always open, unconditioned air from outside can enter living spaces through the chimney, and conditioned air from inside can exit through the chimney. This can result in higher energy costs from heating and cooling. The client(s) should consider having a qualified chimney service contractor install glass doors on the fireplace to reduce or eliminate this air flow.

33) FIREPLACE / CHIMNEY DEFECTS:
Photo
Photo 33-1
FIREPLACE: MISSING COVER
 

34)   FIREPLACE VIEWS:
Photo
Photo 34-1
LIVING ROOM: FIREPLACE
Photo
Photo 34-2
FIREPLACE: INTERIOR
Photo
Photo 34-3
FIREPLACE: FLU VIEW
Photo
Photo 34-4
FIREPLACE: FLU VIEW
Photo
Photo 34-5
ROOF VIEW: CHIMNEY
 

KITCHEN
Return to table of contents

Refridgerator / Freezer Present: YES, WORKING
Dishwaher Present: YES, WORKING
Oven Present: YES, WORKING
Microwave Present: YES, WORKING
GFCI Outlet Present: YES

35) KITCHEN DEFECTS: NONE

36)   KITCHEN VIEWS:
Photo
Photo 36-1
INTERIOR: KITCHEN
Photo
Photo 36-2
KITCHEN: MICROWAVE OPERATIONAL
Photo
Photo 36-3
KITCHEN: OVEN TEMPERATURE 109.5 DEGREES
Photo
Photo 36-4
KITCHEN: BROILER TEMPERATURE 116.5 DEGREES
Photo
Photo 36-5
KITCHEN: DISHWASHER TEMPERATURE 85.0 DEGREES
Photo
Photo 36-6
KITCHEN: ADJUSTABLE BURNER

BATHROOMS
Return to table of contents

GFCI Outlet Present: NO

37) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

38) One or more faucets / shower heads leak by handle(s) or at their base when turned on. A qualified plumber should evaluate and repair as necessary.

39) One or more toilet tanks are cracked / broken or Loose. A qualified plumber should replace, repair or tighten the toilet(s) or tank(s) as necessary.

40) BATHROOM DEFECTS:
Photo
Photo 40-1
BATHROOM #1: ELECTRICAL OUTLET NO GFCI PROTECTION
Photo
Photo 40-2
BATHROOM #1: TOILET TANK LOOSE
Photo
Photo 40-3
BATHROOM #2: SHOWER HEAD NEEDS REPAIR
Photo
Photo 40-4
BATHROOM #3: ELECTRICAL OUTLET NO GFCI PROTECTION
Photo
Photo 40-5
BATHROOM #3: TOILET LID MISSING PAINT
Photo
Photo 40-6
BATHROOM #3: SHOWER HEAD LEAKS
Photo
Photo 40-7
BATHROOM #3: SHOWER HEAD NEEDS REPAIR
 

41)   BATHROOM VIEWS:
Photo
Photo 41-1
INTERIOR: BATHROOM #1
Photo
Photo 41-2
BATHROOM #1: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 41-3
INTERIOR: BATHROOM #2
Photo
Photo 41-4
BATHROOM #2: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 41-5
INTERIOR: BATHROOM #3
Photo
Photo 41-6
BATHROOM #3: ELECTRICAL OUTLET OPERATIONAL

INTERIOR ROOMS
Return to table of contents


42) One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.

43) Carpeting in one or more rooms is soiled and/or stained. Recommend having carpeting professionally cleaned as necessary.

44) INTERIOR DEFECTS:
Photo
Photo 44-1
DINING ROOM: WALLPAPER PEELING
Photo
Photo 44-2
DINING ROOM: WALLPAPER PEELING
Photo
Photo 44-3
DINING ROOM: WALLPAPER PEELING
Photo
Photo 44-4
LIVING ROOM: ELECTRICAL OUTLET OPEN GROUND
Photo
Photo 44-5
LIVING ROOM: STAIN ON CARPET
 

45)   INTERIOR ROOM VIEWS:
Photo
Photo 45-1
INTERIOR: FRONT ENTRY
Photo
Photo 45-2
FRONT ENTRY: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 45-3
INTERIOR: DINING ROOM
Photo
Photo 45-4
DINING ROOM: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 45-5
INTERIOR: LIVING ROOM
Photo
Photo 45-6
INTERIOR: DEN
Photo
Photo 45-7
DEN: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 45-8
INTERIOR: SMOKE DETECTORS THROUGHOUT HOME
Photo
Photo 45-9
INTERIOR: SITTING ROOM
Photo
Photo 45-10
SITTING ROOM: ELECTRICAL OUTLET OPERATIONAL

46)   BEDROOM VIEWS:
Photo
Photo 46-1
INTERIOR: BEDROOM #1
Photo
Photo 46-2
BEDROOM #1: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 46-3
INTERIOR: BEDROOM #2
Photo
Photo 46-4
BEDROOM #2: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 46-5
INTERIOR: BEDROOM #3
Photo
Photo 46-6
BEDROOM #3: ELECTRICAL OUTLET OPERATIONAL
Photo
Photo 46-7
INTERIOR: BEDROOM #4
Photo
Photo 46-8
BEDROOM #4: ELECTRICAL OUTLET OPERATIONAL

47)   HALLWAY VIEWS:
Photo
Photo 47-1
INTERIOR: HALLWAY
Photo
Photo 47-2
INTERIOR: HALLWAY

48)   BEDROOM DEFECTS
Photo
Photo 48-1
BEDROOM #3: DAMAGE TO CEILING AND WALL FROM CABLE INSTALLATION
Photo
Photo 48-2
BEDROOM #4: STAIN ON CARPET

Water Test
Return to table of contents

BACTERIA: NEGATIVE
PH: 8.5=SAFE
ALKALINITY: 180=IDEAL
CHLORINE: 0.0=SAFE
HARDNES: 50=IDEAL
IRON: 0.0=LOW
COPPER: 0=SAFE
NITRATE: 0=SAFE
NITRITE: 0.0=SAFE
LEAD=: NEGATIVE
PESTICIDES=: NEGATIVE

Swimming Pool
Return to table of contents

Limitations: The following items are not included in this inspection: swimming pool bodies; equipment on timers, remote controls or sensors; underground or concealed piping; motorized covers; waterfalls and related equipment; Ozone generators; ultraviolate light systems; filter backflushing mechanisms. Any comments made regarding these items are as a courtesy only. Note that the inspector does not disassemble filters, remove pool covers, nor determine if swimming pool bodies, filters or skimmers leak, nor determine if swimming pool bodies are level.
The following items are excluded from this inspection: NONE
Water level: Full
Has been empty for/since: N/A
LENGTH (FEET): 30
WIDTH (FEET): 14444A009973
AVGERAGE DEPTH (FEET): 5
TOTAL APPROX: CUBIC FEET: 2100
APROXIMATE SIZE IN GALLONS: 15,709
Condition of fences and gates: Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Wood
Condition of body: Appeared serviceable
Body type: Below ground ~
Body material: Plaster-Gunite ~
Condition of deck: Required repairs, replacement and/or evaluation (see comments below)
Deck material: Concrete
Condition of coping: Appeared serviceable
Coping material: Tile
Condition of pumps, lines and valves: Appeared serviceable
Water is refilled through: Hose
Types of pumps installed: Circulation
Line material: PVC
HEATER TYPE: NONE INSTALLED
Condition of filter and related equipment: Appeared serviceable
Filter type: Sand
Filter air relief valve installed: Yes
Filter pressure gauge installed: Yes
Filter pressure at time of inspection (psi): 12 PSI
Condition of skimmers: Required repair, replacement and/or evaluation (see comments below)
Condition of electrical equipment: Appeared serviceable
Location of electrical disconnect: In sub-panel at equipment
Type of wiring: (BX) Armor clad

49) Fencing around the pool in one or more areas was deteriorated. This is a safety hazard because they are intended to control access to areas with a drowning hazard. Standard building practices require that fencing:
  • Be a minimum of five feet in height
  • Not be climbable by children
  • Not have gaps or voids that allow climbing or access to gate latch mechanisms
A qualified person should evaluate and repair or replace as necessary, and as per standard building practices. For more information, visit:
http://www.reporthost.com/?POOLBARR

50) No removable cover was installed for the . Recommend that one be installed to maintain water quality and for safety purposes.

51) POOL DEFECTS:
Photo
Photo 51-1
POOL VIEW: DAMAGE TO SKIMMER LID
Photo
Photo 51-2
POOL VIEW: CRACK IN CONCRETE
Photo
Photo 51-3
POOL VIEW: CRACK IN CONCRETE
Photo
Photo 51-4
POOL VIEW: CRACK IN CONCRETE
Photo
Photo 51-5
POOL VIEW: CRACK IN CONCRETE
Photo
Photo 51-6
POOL VIEW: CRACK IN CONCRETE

52) Significant cracks or damage were found in one or more skimmer covers. A qualified pool specialist should evaluate and replace skimmers or components as necessary.

IS BRITTLE FROM UV RAYS: BROKE WHEN OPENED UP FOR INSPECTION

53) Minor cracks, settlement, heaving and/or deterioration were found in the decking. Recommend that a qualified person caulk or seal cracks as necessary to prevent water intrusion and further cracking or movement.

54)   POOL VIEWS:
Photo
Photo 54-1
ROOF VIEW: POOL
Photo
Photo 54-2
POOL VIEW
Photo
Photo 54-3
POOL VIEW: POOL WIDTH 14'
Photo
Photo 54-4
POOL VIEW: POOL LENGTH 30'
Photo
Photo 54-5
POOL VIEW: SKIMMER
Photo
Photo 54-6
POOL VIEW: FILTER
Photo
Photo 54-7
POOL VIEW: FILTER
Photo
Photo 54-8
POOL VIEW: LIGHT OPERATIONAL
Photo
Photo 54-9
POOL VIEW: JET
Photo
Photo 54-10
POOL VIEW: JET
Photo
Photo 54-11
POOL VIEW: STAIRS
Photo
Photo 54-12
POOL VIEW: MAIN DRAIN
Photo
Photo 54-13
POOL VIEW
Photo
Photo 54-14
POOL VIEW
Photo
Photo 54-15
POOL VIEW: STORAGE
Photo
Photo 54-16
EXTERIOR: GATE LOCK
Photo
Photo 54-17
EXTERIOR: GATE LOCK
Photo
Photo 54-18
EXTERIOR: FENCE
Photo
Photo 54-19
INTERIOR: DOOR ALARM
 

55)   ELECTRICAL / PUMP VIEWS:
Photo
Photo 55-1
POOL VIEW: PUMP
Photo
Photo 55-2
POOL VIEW: FILTER
Photo
Photo 55-3
POOL VIEW: WATER PRESSURE GAUGE 24 PSI
Photo
Photo 55-4
POOL VIEW: SKIMMER
Photo
Photo 55-5
POOL VIEW: PUMP
Photo
Photo 55-6
POOL VIEW: CONTROLS
Photo
Photo 55-7
POOL VIEW: POOL ELECTRICAL JUNCTION BOX
Photo
Photo 55-8
POOL VIEW: SWITCHES
Photo
Photo 55-9
POOL VIEW: WATER SHUT OFF
 

WDO - INSPECTION FINDINGS & PHOTOS
Return to table of contents

Scope of Inspection: THIS REPORT IS MADE ON THE BASIS OF WHAT WAS VISIBLE AND READILY ACCESSIBLE AT THE TIME OF INSPECTION AND DOES NOT CONSTITUTE A GUARANTEE OF THE ABSENCE OF WOOD-DESTROYING ORGANISMS (WDOs) OR DAMAGE OR OTHER EVIDENCE UNLESS THIS REPORT SPECIFICALLY STATES HEREIN THE EXTENT OF SUCH GUARANTEE.

This report does not cover areas such as, but not limited to, those that are enclosed or inaccessible, areas concealed by wall-coverings, floor coverings, furniture, equipment, stored articles, insulation or any portion of the structure in which inspection would necessitate removing or defacing any part of the structure.

This property was not inspected for any fungi other than wood-decaying fungi, and no opinion on health related effects or indoor air quality is provided or rendered by this report. Individuals licensed to perform pest control are not required, authorized or licensed to inspect or report for any fungi other than wood-destroying fungi, nor to report or comment on health or indoor air quality issues related to any fungi. Persons concerned about these issues should consult with a certified industrial hygienist or other person trained and qualified to render such opinions. A wood-destroying organism (WDO) means an arthropod or plant life which damages and can re-infest seasoned wood in a structure, namely, termites, ants, beetles and wood-decaying fungi.

NOTE: This is NOT a structural damage report, it should be understood that there may be damage, including possible hidden damage present. FURTHER INVESTIGATION BY QUALIFIED EXPERTS OF THE BUILDING TRADE SHOULD BE MAKE TO DETERMINE THE STRUCTURAL SOUNDNESS OF THE PROPERTY.

The inspection company can give no assurances with regard to work done by other companies. The company that performed prior treatment should be contacted for information on treatment history and any warranty or service agreement which may be in place.

Based on a visual inspection of the accessible areas, the findings below were observed:
Scope of Inspection: THIS REPORT IS MADE ON THE BASIS OF WHAT WAS VISIBLE AND READILY ACCESSIBLE AT THE TIME OF INSPECTION AND DOES NOT CONSTITUTE A GUARANTEE OF THE ABSENCE OF WOOD-DESTROYING ORGANISMS (WDOs) OR DAMAGE OR OTHER EVIDENCE UNLESS THIS REPORT SPECIFICALLY STATES HEREIN THE EXTENT OF SUCH GUARANTEE.

This report does not cover areas such as, but not limited to, those that are enclosed or inaccessible, areas concealed by wall-coverings, floor coverings, furniture, equipment, stored articles, insulation or any portion of the structure in which inspection would necessitate removing or defacing any part of the structure.

This property was not inspected for any fungi other than wood-decaying fungi, and no opinion on health related effects or indoor air quality is provided or rendered by this report. Individuals licensed to perform pest control are not required, authorized or licensed to inspect or report for any fungi other than wood-destroying fungi, nor to report or comment on health or indoor air quality issues related to any fungi. Persons concerned about these issues should consult with a certified industrial hygienist or other person trained and qualified to render such opinions. A wood-destroying organism (WDO) means an arthropod or plant life which damages and can re-infest seasoned wood in a structure, namely, termites, ants, beetles and wood-decaying fungi.

NOTE: This is NOT a structural damage report, it should be understood that there may be damage, including possible hidden damage present. FURTHER INVESTIGATION BY QUALIFIED EXPERTS OF THE BUILDING TRADE SHOULD BE MAKE TO DETERMINE THE STRUCTURAL SOUNDNESS OF THE PROPERTY.

The inspection company can give no assurances with regard to work done by other companies. The company that performed prior treatment should be contacted for information on treatment history and any warranty or service agreement which may be in place.

Based on a visual inspection of the accessible areas, the findings below were observed:
(1) Visible signs of WDO(s) (live, evidence or damage) observed: Yes
Evidence of WDO(s): WOOD ROT ON LEFT FRONT SOFFFIT EAVE
(2) Live wood-destroying organisms observed: No
Live WDO(s) observed: N/A
(3) Visible damage observed: No
Visible damage observed (common name, description and location): N/A
(4) Visible evidence of previous treatment observed: No
Name of Company: PEST EXPRESS
TYPE OF PREVIOUS TREATMENT / INSPECTION: INSPECTION ONLY
Evidence of previous treatment / inspection (description and locations)::
(5) This company has treated the structure(s) at the time of the inspection: No
(6) This company has treated the structure(s) previously: No
A Notice of Inspection has been affixed to the structure at: ELECTRICAL PANEL
A Notice of Treatment has been affixed to the structure at: NONE
Signature of Licensee or Agent: R.B.McCORMICK
Date Signed: Friday, February 19, 2016

56) WDO DEFECTS
Photo
Photo 56-1
WDO VIEW: SIGNS OF WOOD ROT FROM WATER INTRUSION
 

57)   WDO DOOR CASINGS
Photo
Photo 57-1
WDO VIEW: ENTRY CASING WDO FREE
Photo
Photo 57-2
WDO VIEW: ENTRY CASING WDO FREE
Photo
Photo 57-3
WDO VIEW: ENTRY CASING WDO FREE
Photo
Photo 57-4
WDO VIEW: ENTRY CASING WDO FREE
Photo
Photo 57-5
WDO VIEW: ENTRY CASING WDO FREE
Photo
Photo 57-6
WDO VIEW: ENTRY CASING WDO FREE

58)   ATTIC VIEWS
Photo
Photo 58-1
ATTIC VIEW
Photo
Photo 58-2
ATTIC VIEW

59)   SUBTERRANEAN CHECK:
Photo
Photo 59-1
WDO VIEW: NO SUBTERRANEAN TERMITES PRESENT
Photo
Photo 59-2
WDO VIEW: NO SUBTERRANEAN TERMITES PRESENT
Photo
Photo 59-3
WDO VIEW: NO SUBTERRANEAN TERMITES PRESENT
Photo
Photo 59-4
WDO VIEW: NO SUBTERRANEAN TERMITES PRESENT

60)   PREVIOUS TREATMENT / INSPECTIONS
Photo
Photo 60-1
WDO VIEW: PREVIOUS INSPECTION
 

All inspections carry a 90 day Re- Inspection Warranty Coverage and are non-transferable without the expressed consent of F.H.I.
F.H.I. and all Sub Contractors are not held liable for areas that are not visable or accesable during the inspection process. Nor are we held liable for any repairs to the home or any attached or free standing structures.

State of Florida
Licensed, Insured & Certified:
InterNACHI ID# NACHI12110107 http://www.nachi.org/verify.php?nachiid=NACHI12110107
FLORIDA LICENSE# HI7801 www.myfloridalicense.com/dbpr
WDO InterNACHI Certified
Wind Mitigation InterNACHI Certified

[sig]
Inspector: R.B.McCormick