Fine Point Inspection LLC

Website: http://www.reporthost.com/finepoint
Email: Bob@finepointinspection.com
Phone: (860) 434-7966
23 Four Mile River Rd. 
Old Lyme, CT 06371
Inspector: Bob Reemsnyder

Home Inspection Report
Client(s): Sample Report
Property address: 123 American Ave.
Historic, US
Inspection date: Wed. Jun. 1, 0000
This report published on 8/13/2005 11:10:47 AM EDT

View summary page

This report is the exclusive property of FINE POINT INSPECTION, LLC and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.


How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and shown in bold type. Items of concern follow descriptive information and are shown as follows:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor defectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
ServiceableItem or component is in serviceable condition 
CommentFor your information 
Concern items are sorted by the types listed above. Click here for a glossary of building construction terms.

Structural Pest Inspection Concerns
Items marked with the following icons relate to the structural pest inspection
InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.)
DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Conducive
conditions
Conducive conditions for wood destroying insects or organisms. (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Table of Contents
General information
Exterior
Termites and Wood Boring Insects
Roof
Electric service
Water heater
Heating and air conditioning
Attic
Plumbing and laundry
Basement
Interior stairs
Fireplaces and Wood Stoves
Crawl space
Interior rooms
Bathrooms


General information Return to table of contents  
Report number: XXXXX
Time started: 11:30 AM
Time finished: 1:30 PM
Present during inspection: Buyer, Listing Agent, Buyers Realtor
Occupied: Yes
Age of building: 150 + yrs. old
Type of building: Single family
Weather conditions: Partly cloudy
Temperature: Hot
Ground condition: Dry
Main entrance faces: South
Foundation type: Unfinished basement, Crawlspace - inaccessible
  1) It is the goal of the inspection to put a home-buyer in a better position to make a buying decision. Not all improvements will be identified during this inspection. Unexpected repairs should still be anticipated. The inspection is not to be considered a guarantee or warranty of any kind.
This inspection is visual only. A representative sampling of building components are viewed in areas that are accessible at the time of the inspection. Furniture and storage, when present, limit accessibility to inspect some areas. As per State of Connecticut Home Inspection Regulations, no destructive testing or dismantling of building components is performed. Furniture is not moved, and main valves are not turned on.
 
Exterior Return to table of contents  
Footing material: Not visible
Foundation material: Stone
Apparent wall structure: Wood frame
Wall covering: Wood clapboard
Driveway material: Gravel
Exterior door material: Wood panel
Basement/crawl access: Hatch
Basement/Crawl windows: Wood
2) The perimeter grading slopes towards the structure at the back and a swale or gulley was dug. We recommend installing perforated pipe and stone to fill area, as it is a trip hazard at present. The purpose of gulley is to help eliminate water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. An excavation contractor could further recommend improving this area.

Photo 7  
Red: siding to grade contact. Yellow: swale improvements recommended.
 
  3) Rot was noted at front skirt board, stair risers. Rot should be repaired or replaced as necessary. Hidden damage may be present. Unattended rot can quickly spread to healthy wood and should be addressed immediately. Consult with a carpenter.

Photo 1  
Some rot has been painted over at the stair risers.

Photo 3  
Rot noted at front southeast skirt board.
4) One or more downspouts are loose or detached. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Recommend making repairs as necessary so downspouts are securely anchored and functional.

Photo 2  
Downspouts should be connected to extensions.
 
5) One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Recommend making repairs as necessary such as repairing or installing splash blocks or tie-ins to underground drain lines so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.

Photo 2  
Downspouts should be connected to extensions.

Photo 27  
Extension shoud be opened up at downspout.
6) Soil is in contact with or less than 6" from siding and/or trim. This is a conducive condition for wood destroying insects and organisms. Recommend grading soil as necessary so there's at least 6" of space between the siding and trim and the soil below.

Photo 7  
Red: siding to grade contact. Yellow: swale improvements recommended.
 
  7) Stone or brick exposed foundation needs repointing of the joints. Consult with a mason for repairs.

Photo 6  
As typical, foundation stones need localized re-pointing.
 
  8) Wood basement window(s) need typical repairs, including reglazing, repairing cracked or broken glass, or painting of sash. Recommend repairs be made as necessary.

Photo 19  
Foundation windows in need of maintenance and repair in some areas.
 
9) Window wells at crawl or basement need improvement. Silt or organic growth should be removed and installing a cover will prevent this from occuring in the future.
10) Vegetation (trees, shrubs and/or vines) are in contact with the structure's exterior. This is a conducive condition for wood destroying insects and organisms. Vegetation can serve as a conduit for insects and may retain moisture against the exterior after it rains. Recommend pruning or removing vegetation as necessary so there's at least a one foot gap between all vegetation and the structure's exterior.
  11) Front porch ceiling had prior water damage at one time, warping noted.

Photo 37  
Front porch ceiling has warped boards evident/no leakage detected at inspection - appears to be past leakage.
 
    12) Trim is loose and should be secured at north upper porch area.

Photo 4  
Small section of trim loose at front porch/north side.
 
 
Termites and Wood Boring Insects Return to table of contents  
  13) There was no indication of the presence of wood boring insects at the time of the inspection. Indications would include mud tubes, damage, frass, ant bodies, and carpenter bee holes. We recommend annual or seasonal inspections by a professional exterminating company to prevent future infestation.
 
Roof Return to table of contents  
Roof inspection method: Traversedupper areas viewed from lower roof
Roof type: Gable
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: Newer- addition and front porch. Older upper main maybe-15-20 years
Gutter & downspout material: Aluminum
Roof ventilation: Adequateaddition ok,upper only windows in top floor.
  14) The back masonry chimney has deterioration and spalling evident and requires repairs such as sealing brick, replacing bricks, and/or replacing the crown. Recommend having a qualified chimney service contractor or mason evaluate chimney and repair as necessary. Because of this spalling, also recommend that the chimney service contractor perform a Level 2 inspection as per the National Fire Protection Association (NFPA) guidelines.

Photo 5  
Back chimney has evidence of spalling.
 
  15) One or more chimney flues don't have a screened cover installed. Screened covers prevent the following:

  • Fire hazard from wood fire sparks and embers exiting flues
  • Wildlife (birds, rodents, racoons, etc.) entering flues
  • Rainwater entering flues and mixing with combustion deposits, creating caustic chemicals which can corrode flues
  • Rainwater entering flues and causing damage to terracotta flue tiles from freeze-thaw cycles

    Recommend having a qualified chimney service contractor install screened cover(s) where missing. Screens should have holes 1/4" or larger.
  •   16) The smaller chimney (boiler) should have the voids in the flashing sealed better. This is a job for a roofer.
      17) The small older chimney is out of plumb, however appears to be tilted somewhat and should be monitored.
     
    Electric service Return to table of contents  
    Primary service type: Overhead
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 100
    Service voltage (volts): 120-240
    Location of main service panel: basement
    Location of sub panels: basement to side of.
    Location of main disconnect: Breaker at top of main service panel
    Service conductor material: Aluminum
    Main disconnect rating (amps): 100
    Branch circuit wiring type: Non-metallic sheathed, Armored cable, Knob and tube
    Solid strand aluminum branch circuit wiring present: No
    Smoke detectors present: Yes
      18) Knob and Tube wiring was used in the 1920's and 30's. Some is still active in the home, visible in side attic and probably serving some of the top floors behind walls. Usually this wiring is upgraded when major renovations are done. For example, when walls and/or floor are opened up. Some should be repaired here as noted in the picture and this is usually done by an electrician snaking a new wire in the structure. Consult with a licensed electrician.

    Photo 33  
    Some old knob and tube wires evident in side attic should be upgraded -bare spots.
     
      19) There are several smaller electrical repairs needed in basement. An electrician should be consulted.

    Photo 11  
    Electrical panel box opening should be plugged.

    Photo 14  
    Open junction box in basement

    Photo 15  
    Open junction box in basement.

    Photo 18  
    Wire should be terminated properly in basement.
      20) A clamp should be installed better above the meter socket (it holds the service wire).
      21) Electrical components concealed behind finished surfaces are not inspected.
    Only a representative sampling of outlets and light fixtures were tested.
    Furniture and/or storage may have restricted access to some electrical components, which would then have not been inspected
    The inspection does not include remote control devices, alarm systems and components, low voltage wiring, systems, and components, ancillary wiring, systems, and other components which are not part of the primary electrical power distribution system.
     
    Water heater Return to table of contents  
    Estimated age: 5-10 years
    Type: Tank
    Energy source: Electricity, Oiltankless feed
    Capacity (in gallons): 80
    Brand & model: Kenmore
    Heating and air conditioning Return to table of contents  
    Heating system energy source: Oil
    Heat system type: GravitySteam one pipe
    Distribution system: Metal pipe
    Brand & model: Utica
      22) Steam systems were used years ago and tend to be more temperamental and require a service company with some degree of knowledge and patience. This boiler has been maintained with a service record in place. The unit in service was operational at inspection, however several hours are needed to fully heat all radiators in order to determine effective heat transfer to all radiators (it was around 90 degrees F at inspection). As such, some limitation to this inspection is present.

    Photo 13  
    Water level good in steam boiler at inspection.

    Photo 17  
    Service record for boiler looks good.

    Photo 25  
    Boiler information label.
     
      23) The back addition is served by electric heat and this was operational at inspection.
     
    Attic Return to table of contents  
    Inspection method: side space limited view
    Roof structure type: Rafters
    Ceiling structure: Ceiling beams
    Insulation material: Fiberglass roll or batt, Cellulose loose fill
    Insulation depth: Minimal levels
      24) When re-roofing the upper portion, adding ridge vents is recommended, as ventilation is done by opening windows. The lower newer roof has ridge venting installed.
      25) One of the side access areas was covered or not accessible at inspection.

    Photo 30  
    Back side crawl obstructed at inspection.
     
     
    Plumbing and laundry Return to table of contents  
    Location of main water shut-off valve: basement back wall
    Location of main water meter: basement back wall
    Location of main fuel shut-off: at oil tank
    Visible fuel storage systems: 275 gallon fuel tank-basement
    Water service: Public
    Service pipe material: Copper
    Supply pipe material:
    Vent pipe material: Plastic, Copper
    Waste pipe material: Plastic, Cast iron, Copper
    26) No dryer duct is installed. Recommend installing a rigid or corrugated semi-rigid metal duct. For information on dryer safety issues, see http://www.cpsc.gov/CPSCPUB/PUBS/5022.html

    Photo 22  
    Dryer should be vented to exterior.
     
      27) A valve was dripping at inspection and should be repaired consult with a plumber.

    Photo 8  
    Dripping valve noted in basement.
     
      28) Some of the steam piping is older pipe and could fail at any time,it is usually replaced on an as needed basis.
     
    Basement Return to table of contents  
    Insulation material underneath floor above: None visible
    Pier or support post material: Wood, Steel
    Beam material: Solid wood, Built up wood
    Floor structure above: Solid wood joists
    Evidence of basement leakage found in the form of: Water stains, Rot caused from water penetrationSub panel support
      29) Extension cords are being used as permanent wiring at sump pump. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring poses a fire and shock hazard, and is an indication that wiring is not adequate and should be updated. Recommend either removing extension cords or having a qualified, licensed electrician evaluate and make modification as necessary. For example, install additional circuits and/or electric outlets.
      30) The metal pads below the front wood columns are deteriorating and should be replaced. Consult with a builder.

    Photo 21  
    Post supports are deteriorating at floor in basement.
     
      31) One joist at the north side is cracked and should be sistered (adding another member to the side). Consult with a builder.

    Photo 31  
    One cracked rafter at north side should be sistered.
     
      32) The support to the sub panel box should be repaired at the base. This will help secure the box.

    Photo 29  
    This board supports sub panel and is rotted at base.
     
     
    Interior stairs Return to table of contents  
      33) The spindles of the interior stairs are spaced too wide, creating a safety hazard, as a small child could fall through.

    Photo 32  
    Open areas should be closed in.
     
     
    Fireplaces and Wood Stoves Return to table of contents  
    Fireplace type: Masonry
    Chimney type: Masonry
      34) A significant amount of creosote visible in fireplace flue (in newer section, family room). The damper needs adjustment and or repair. Recommend cleaning, inspection and repairs if necessary by a qualified chimney service contractor.
      35) The damper needs adjustment in the family room fireplace. The living room fireplace slides, and may be difficult to operate. You may want to install glass doors to keep from losing heat up the flue.

    Photo 36  
    damper at front chimney needs adjustment.
     
      36) All solid fuel burning appliances (woodstoves and fireplaces) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
      37) Typical wear was noted in the livingroom firebox.

    Photo 34  
    Typical floor wear inside front firebox (a few chips, etc.)

    Photo 35  
    Older fire box, front chimney. Some wear noted at back.
     
    Crawl space Return to table of contents  
    Inspection method: Viewed from hatch
    Insulation material underneath floor above: Fiberglass roll or battat back crawl
    Pier or support post material: brick
    Floor structure above: Solid wood joists
    Vapor barrier present: only at back crawl space
    38) Vapor barrier is missing at south crawl area. Recommend installing 6 mil polyethylene with seams overlapped at least 24" so no soil is exposed in the crawlspace.

    Photo 23  
    Crawl area to the south needs moisture barrier.
     
    39) Cellulose-based debris such as wood scraps, form wood, cardboard and/or paper were found in crawl space. Recommend removing all cellulose-based debris to avoid attracting wood destroying insects.

    Photo 23  
    Crawl area to the south needs moisture barrier.
     
      40) The back crawl space has a fan mounted to help circulate air, probably to keep area dryer and also to move warm air from boiler to help prevent winter freezing of pipes. Consult with seller on how often it was used or needed.

    Photo 26  
    appears back crawl space has a fan to help dry or move air.
     
      41) Minimal work room space (or inspection space) is present in the crawl areas.
     
    Interior rooms Return to table of contents  
      42) One or more open ground, 3-pronged receptacles were found. This is a safety hazard and poses a risk of electric shock. Recommend that a qualified, licensed electrician evaluate and make repairs as necessary. For example, replacing receptacles or correcting wiring circuits.

    Consult with an electrician for a proper remedy. The following appliances require grounded receptacles:

  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

    This list is not exhaustive. Grounded circuits and receptacles should be installed in locations where such appliances will be used.
  •   43) One or more doors swing outward over stairs without a landing area in front of the door. This a safety hazard, specifically in the case of someone tripping or falling when standing on the stairs and opening the door while someone else walks through the door as they are opening it. A qualified contractor should evaluate and make repairs as necessary. One solution may be to install a door that opens in the other direction (away from the stairs).
      44) One or more receptacles are loose, broken or damaged. A qualified, licensed electrician should resecure or replace them as necessary.
      45) Handrail(s) are missing from one or more flights of stairs with more than two risers. This is a safety hazard. Recommend having a qualified contractor install graspable handrails that your hand can completely encircle at stairs with more than two risers where missing.
      46) Gaps larger than 4" were found in one or more deck or stair rails. This is a safety hazard, especially for small children. Recommend that a qualified contractor make modifications as necessary, such as installing additional balusters, so gaps in rails don't exceed 4".
      47) Some windows will not stay open without being propped. This can be a safety hazard, as fingers could be caught in the sill when the sash drops open. Recommend repairing sash cords, springs or weights, as needed to assure proper working of windows.
      48) Few outlets and 2-pronged receptacles rather than 3-pronged, grounded outlets are installed in one or more interior rooms. This can result in "octopus" wiring with extension cords (a fire hazard), and limits the ability to use appliances that require a ground (computers and some other electronic appliances) in these areas. Recommend having a qualified electrian evaluate and install additional receptacles and grounded receptacles where necessary and as per the current National Electric Code.
      49) The hardware on the window(s) is missing, damaged or broken and needs repair or replacement (third floor, older windows). Window hardware should be repaired so that windows easily open and close and are able to be locked.
      50) Window(s) stuck shut and can't open (third floor office). Recommend repairing window(s) so they open easily.
      51) One or more doors don't latch when closed. Recommend making repairs as necessary such as adjusting latch plates or lockset mechanisms.
      52) One or more doors bind in their jambs. Recommend making repairs as necessary so they close easily.
      53) The walls in one or more rooms displayed typical flaws such as:

    * minor cracks
    * minor stains from past leakage
    * popped nails
    * loose or dried out taping seams
    * small, cosmetic holes that may need filling
    * limited areas of peeling paint

    These are considered cosmetic issues and are not considered defects, although it may be desirable to patch holes, cracks and popped nails, and repaint for aesthetic purposes.
      54) There were floor slopes evident that are typical of an antique home. Antique homes have generally settled over the years and repairs may have been made to improve support to the structure. It is unlikely that these types of floor slopes can be repaired without major renovations or replacement of the floors, and it is unlikely that this would be the preference, as many people buying an antique home choose to keep the character of the home. If repairs or improvements to the floor are anticipated, consultation with a structural engineer would be recommended.
     
    Bathrooms Return to table of contents  
    55) Leak at drain under sink in first floor bathroom. Recommend repairing leak.
      56) Claw foot tub is missing one leg. Some sort of support should be put under this area to keep the tub from "rocking" when used.
      57) Rust was noted in the drain of the claw foot tub. Repair or replacement may be needed in near future. Consult with a plumber.
      58) The drain plug on the tub does not operate or does not hold water. Recommend repairing plug mechanism so it holds water. Consult with a plumber.
      59) Cracks were noted in the second floor vanity sink. They appear to be surface cracks as leakage below the sink was not observed. This should be monitored.
     

    Photo 9  
    Water heater manufacturer.

    Photo 10  
    Information label water heater.

    Photo 12  
    This is where main water shut off is.

    Photo 16  
    Some dampness noted on basement floor.

    Photo 20  
    Sump pump should have a dedicated outlet.

    Photo 24  
    View looking into back crawl space.

    Photo 28  
    level of oil in the tank at inspection.
     

    As part of this inspection, the client is given a copy of the State of Connecticut Regulations pertaining to Home Inspections, as well as an Inspection Agreement, that explains what is covered, and what is not covered in this Home Inspection.

    An inspection of the sewage system is outside the scope of this inspection, unless specifically contracted for prior to the inspection date.
    An inspection of the pool is outside the scope of this inspection.
    A representative sampling of components was inspected rather than every occurrence of components.
    The inspection does not include an assessment of geological, geotechnical, or hydrological conditions, or environmental hazards.
    Screening, shutters, awnings, or similar seasonal accessories, fences, recreational facilities, outbuildings, seawalls, break-walls, docks, erosion control and earth stabilization measures are not inspected.

    Fine Point Inspection does not test for Indoor Air Quality and does not test for mold.

    This report was published with ReportHost, the premier web-based inspection report writing service. For more information visit http://www.reporthost.com