Inspector: Robert Johnson
|
Property Inspection Report |
| Client(s): |
Jack & Vicki Murrah |
| Property address: |
4805 Palm Stone Dr. Knoxville, TN 37918 |
| Inspection date: |
Saturday, June 21, 2008 |
This report published on 6/21/2008 8:54:37 PM EDT
View summary page
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and is shown in bold type. Items of concern follow descriptive information.
Concerns are shown and sorted according to these types: | Safety | Poses a risk of injury or death |
 | Major Defect | Correction likely involves a significant expense |
 | Repair/Replace | Recommend repairing or replacing |
 | Repair/Maintain | Recommend repair and/or maintenance |
 | Minor Defect | Correction likely involves only a minor expense |
 | Evaluate | Recommend evaluation by a specialist |
 | Comment | For your information |
Click here for a glossary of building construction terms.
Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp
Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Crawl space
Kitchen
Bathrooms
Interior rooms
Report number: 00621008
Structures inspected: 1
Type of building: Single family
Age of building: approx. 30 yrs.
Property owner's name: N/A
Time started: 9:00AM
Time finished: 11:30AM
Inspection Fee: 250.00
Payment method: Check
Present during inspection: Client(s), Property owner(s)
Occupied: Yes
Weather conditions: Clear
Temperature: Hot
Ground condition: Dry
Front of structure faces: North
Main entrance faces: North
Foundation type: Crawlspace
The following items are excluded from this inspection: Private sewage disposal system, Security system, Irrigation system, Swimming pool, Hot tub, Private well, Playground equipment, Sauna, Low voltage outdoor lighting, Central vacuum system, Water filtration system, Water softener system, Built-in sound system, Intercom system, Generator system, Sport court, Sea wall
Footing material: Not visible
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Brick veneer
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core wood
1)


One or more outdoor electric receptacles appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all outdoor receptacles within six feet six inches of ground level have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

Photo 9
No GFCI, cover, and use of extension cord
|
|
2)


Extension cords are being used as permanent wiring in one or more areas. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring poses a fire and shock hazard, and is an indication that wiring is inadequate and should be updated. Extension cords may be undersized. Connections may not be secure, resulting in power fluctuations, damage to equipment, and sparks that could start a fire. Extension cords should be removed as necessary, or a qualified electrician should evaluate and make repairs as necessary. For example, install additional circuits and/or electric receptacles.

Photo 9
No GFCI, cover, and use of extension cord
|
|
3)

Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

Photo 9
No GFCI, cover, and use of extension cord
|
|
4)

One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.
Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079
5)

Fences and/or gates are damaged and/or deteriorated in some areas. A qualified contractor should evaluate and make repairs or replace sections as necessary.
Mainly the gates and lower portion of the fence that is w/in 6" of the ground.
6)
Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
7)
Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
Roof inspection method: Traversed
Roof type: Gable, Cross gable
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: > 15 yrs.
Gutter & downspout material: Aluminum
Roof ventilation: Adequate
8)

Evidence of water activity were the chimney penetrates the roof.

Photo 10
Chimney/roof leak activity
|
|
9)

The roof surface material appears to be near the end of its service life and will likely need replacing in the near future, even with repairs. The client(s) should budget for a replacement roof surface, and may want to have a qualified roofing contractor evaluate and attempt to issue a "5 year roof certificate".
10)

One or more sections of flashing at the base of the chimney are deteriorated and/or substandard. Leaks may occur as a result. A qualified roofing contractor should evaluate and repair as necessary.

Photo 5
Chimney flashing
|
|
11)

One or more composition shingles are damaged, deteriorated and/or missing, and should be replaced. Leaks may occur as a result. A qualified roofing contractor should evaluate and make repairs as necessary.
12)
One or more "rubber boot" flashings are damaged or deteriorated and may result in leaks or vermin intrusion. A qualified contractor should replace flashings where necessary.

Photo 2
Roof flange
|

Photo 3
Roof flange
|

Photo 4
Roof flange
|
|
13)


One or more electric receptacles have burn or scorch marks on them. Receptacle(s) and/or wiring to them may be damaged. A qualified electrician should evaluate and make repairs as necessary, such as replacing damaged receptacles and/or wiring.

Photo 6
Garage receptacle scortched
|
|
14)


One or more garage electric receptacles appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all garage receptacles, except for one for use with a refrigerator or freezer, have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
15)
Much of the garage, including areas around the interior perimeter and in the center are excluded from this inspection due to lack of access from stored items.
16)
Loose receptacle noted in rear of garage next to window.
Inspection method: Traversed
Roof structure type: Trusses
Ceiling structure: Ceiling beams
Insulation material: Fiberglass loose fill
Insulation depth: 8 inches
Insulation estimated R value: 25- ideal is 30
17)


Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

Photo 11
Open splice-attic
|

Photo 12
Open lighting splice
|
18)
Bath exhaust vent terminating in the attic. It should terminate @ the ridge vent or to the out side. This will lead to assess humidity and moisture in the attic, which can lead to mold, rot, and decreased R value of the insulation.

Photo 13
Bath vent into attic
|
|
Primary service type: Overhead
Primary service overload protection type: Circuit breakers
Service amperage (amps): 200
Service voltage (volts): 120/240
Location of main service switch: Left outside of house
Location of main disconnect: Breaker at top of main service panel
Service entrance conductor material: Aluminum
System ground: Ground rod(s) in soil
Main disconnect rating (amps): 200
Branch circuit wiring type: Copper
Solid strand aluminum branch circuit wiring present: No
Smoke detectors present: Yes
19)

Bottom right breaker not properly connected. Recommend an electrician evaluate and repair.

Photo 7
Improper coded hot wire
|
|
20)

Several wires used as hot wires are not properly color coded. I highly recommend an electrician evaluate and repair before closing.

Photo 8
Improper breaker connection
|
|
21)
Smoke detectors noted in the house, but not functioning. May need batteries.
Estimated age: 1 month old
Type: Tank
Energy source: Electricity
Capacity (in gallons): 47
Manufacturer: General Electric
Model: GE47S06AA6, Serial# 0508D02135
Water temperature (degrees Fahrenheit): 115 degrees
22)

No drain line is installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.

Photo 16
TPR valve w/o drain pipe
|
|
Estimated age: 2002
Primary heating system energy source: Natural gas
Primary heat system type: Forced air, High efficiency
Primary A/C energy source: Natural Gas
Distribution system: Flexible ducts
Manufacturer: Armstrong
Model: PGE10B42D100A, Serial # 1602K14830
Filter location: Noted in hallway
23)


Significant amounts of rust or corrosion were found on one or more gas supply pipes. Based on this deterioration, the wrong materials may have been used. For example, black iron pipe may have been used where galvanized iron pipe should have been used instead. Leaks may occur as a result. This is a safety hazard. A qualified heating and cooling contractor should evaluate and make repairs as necessary.
24)
No drip leg is installed on the furnace or boiler gas supply line. Drip legs are intended to trap oil, scale, water condensation and/or debris from the gas supply lines before they reach and damage the furnace or boiler components. A qualified contractor should install a drip leg as per standard building practices.
Water pressure (psi): 100; normal - (40-80)
Location of main water shut-off valve: In crawspace to the far right corner.
Location of main water meter: Right front yard next to drive
Location of main fuel shut-off: Left side of house
Water service: Public
Service pipe material: Galvanized steel
Supply pipe material: Copper
Vent pipe material: Plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
25)
No GFCI receptacle for washer and is not linked to GFCI in breaker box.
26)
A sump pump is installed on the premises. This may indicate that water accumulates inside or below the structure. Recommend asking the property owners how often the sump pump operates and for how long at different times of the year. Also, the clients should be aware that the service life of most sump pumps is between five and seven years, and that the pump may need replacing soon depending on its age and how much it operates.
It appears to be operating properly @ this time!
Fireplace type: Masonry with metal liner
Chimney type: Masonry
27)
The gas supply for one or more gas fireplaces and/or stoves was turned off. As per the Standards of Practice for both the National Association of Certified Home Inspectors (NACHI) and the American Society of Home Inspectors (ASHI) the inspector does not operate gas shut off valves or light pilot lights during inspections. These appliances were not fully evaluated.
Inspection method: Traversed
Insulation material underneath floor above: Fiberglass roll or batt
Pier or support post material: Concrete
Beam material: Solid wood
Vapor barrier present: Yes
28)


Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

Photo 15
Open splice in crawspace
|

Photo 17
Open splice in crawspace
|
29)

Dryer vent disconnected in crawspace. This can lead to assess moisture, resulting rot, mold and insects.

Photo 14
Dryer vent open in crawspace
|
|
30)


One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
31)


One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
Noted in both bathrooms!
32)
Caulk is missing or deteriorated around one or more shower surrounds. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the wall structure.
33)


One or more electric receptacles and/or the boxes they are installed in are loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.
34)

Hall receptacle painted over. Paint is highly flammable and could lead to a fire!
35)

HOBBY SHOP
1) Hobby shop composition will require replacing in the near future. It is recommended that a roofing specialist evaluate and repair.
2) No GFCI receptacles noted in the hobby shop. It is recommended that a Lic. electrician evaluate and repair.
3) The exterior door in the hobby shop doesn't function properly. It is recommended that a Lic. contractor repair.
36)

One or more electric receptacles appear to have no power. Recommend asking the property owner(s) about this. Switches may need to be operated to make some receptacles energized. If necessary, a qualified electrician should evaluate and make repairs as necessary.
This was noted in the master bedroom to the right of the exterior door!