| Home Inspection Report | |
| Client(s): | XXXXXXXX |
| Property address: | XXXXXX XXXXX |
| Inspection date: | XXXX XXXXX XXXX |
This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
![]() | Safety | Poses a risk of injury or death |
![]() | Repair/Replace | Recommend repairing or replacing |
![]() | Repair/Maintain | Recommend repair and/or maintenance |
![]() | Minor defect | Correction likely involves only a minor expense |
![]() | Maintain | Recommend ongoing maintenance |
![]() | Evaluate | Recommend evaluation by a specialist |
![]() | Monitor | Recommend monitoring in the future |
![]() | Serviceable | Item or component is in servicable condition |
![]() | Comment | For your information |
Table of Contents
General information
Roof
Exterior
Crawl space
Heating and Cooling
Plumbing and laundry
Water heater
Well
Electrical
Fireplaces and solid fuel burning appliances
Doors, Windows, & Interior
Detached garage or buildings
| General information | Return to table of contents |
| Roof | Return to table of contents |
![]() ![]() ![]() |
1) The chimney flue doesn't have a screened cover installed. Screened covers prevent the following: Recommend having a qualified chimney service contractor install screened cover(s) where missing. Screens should have holes 1/4" or larger. |
||
![]() ![]() |
2) The rubber or vinyl vent pipe boot is lifting, causing a gap where rainwater can enter the vent pipe hole in the roof. This is a conducive condition for wood destroying insects and organisms since water may leak into the roof structure or attic. Recommend fastening vent pipe boots down as necessary to prevent leaks. This boot is located on the Northwest corner of the house.
|
||
![]() |
3) The shingles are nearing the end of their useful life. This can be observed by the edges beginning to curl in the accompanying photo. Given the heavy shade on the roof the existing roof could last another 5 years if desired.
|
| Exterior | Return to table of contents |
![]() ![]() ![]() |
4) Gaps larger than 4" were found in one or more guardrails. This was built to the codes that existed in 1990, and a deck of this height does not require a railing. This is just an observation for your information. No specific course of direction is recommended | ||
![]() ![]() |
5) One or more wooden deck support posts are in close proximity to soil. This is a conducive condition for wood destroying insects and organisms. However no damage from wood destroying insects or organisms was found. It's recommended that there be at least 6" of space between any wood and the soil below, since the wood is not treated. I recommend installing borate based Impel rods to prevent rot. | ||
![]() ![]() |
6) The end cap on the clothes dryer exhaust duct is damaged. Their purpose is to prevent air from entering the house through the clothes dryer, save energy, and keep out birds, rodents and bugs. Birds' nests can block the opening and are flammable. Recommend installing a new vent cap. | ||
![]() ![]() ![]() |
7) Soil is in contact with or less than 6" from siding and/or trim. This is a conducive condition for wood destroying insects and organisms. This condition has existed since building of the home. I found no evidence of pests or rot. The low moisture levels and good drainage help to alleviate these problems. The condition of the stain or sealer on the wood should be well maintained and monitored | ||
![]() ![]() |
8) One or more crawl space vent screens are clogged with debris. This can restrict ventilation in the crawl space, resulting in increased levels of moisture, and is a conducive condition for wood destroying insects and organisms. Recommend cleaning screens where necessary to allow maximum ventilation in the crawl space. The insulation over the vents should be removed in warmer months and only installed in cold weather to maintain crawl space temperatures above freezing. | ||
![]() |
9) The finish on the deck and railing is worn and/or deteriorated. Recommend cleaning and repainting deck and railing.
|
||
![]() |
10) A few areas were noticed where caulk is missing or deteriorated. Recommend caulking where necessary. |
| Crawl space | Return to table of contents |
![]() ![]() |
11) Insulation under the floor in the crawlspace is damaged, deteriorated, or has fallen down in two small spots. Also a small strip of insulation is missing running north to south along the west cross bracing. | ||
![]() |
12) The water supply pipes in the crawl space are uninsulated. Recommend insulating these pipes for better energy efficiency and to prevent water pipes from freezing. Given the age of the home and depth of the crawl space if no action is taken pipes should not freeze as there are no signs of any repairs to this point. Insulation of hot water pipes would result in some energy savings and increased comfort levels
|
| Heating and Cooling | Return to table of contents |
| Plumbing and laundry | Return to table of contents |
![]() ![]() |
13) The clothes dryer is equipped with a plastic (vinyl) or foil, accordion-type, flexible duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. The flexible plastic or foil type duct can more easily trap lint and is more susceptible to kinks or crushing, which can greatly reduce the airflow. Recommend replacing the duct with a corrugated semi-rigid metal duct. Most manufacturers specify the use of a rigid or corrugated semi-rigid metal duct, which provides maximum airflow. For more information on dryer safety issues, see http://www.cpsc.gov/CPSCPUB/PUBS/5022.html | ||
![]() |
14) Recommend having septic tank inspected. Recommend pumping tank if last pumped more than 3 years ago. | ||
![]() |
15) Turning off this valve at the pressure tank will shut off water flow in the house in case of emergency
|
| Water heater | Return to table of contents |
![]() ![]() |
16) Hot water heater is installed in an unheated space and isn't resting on an insulated pad. Recommend installing an insulated pad under the hot water heater. |
![]() ![]() |
17) No insulating blanket is installed on the water heater. Installing one will help save money and energy |
| Well | Return to table of contents |
![]() ![]() |
18) Recommend having the well water tested for bacteria by a qualified lab. (If no test has been performed in the past year or two) Test bottles and information are available from the county sanitarian or we can provide this service for an extra fee |
||
![]() |
19) The estimated life for a submersible pump is 20 years. This well pump may be nearing the end of its estimated useful life. The clients should be aware that this pump may need replacing in the next 5 years | ||
20) This valve is the pressure tank supply shut off
|
|||
21) This shows the pressure guage and incoming line from the well
|
| Electrical | Return to table of contents |
![]() ![]() |
22) An insufficient number of smoke detectors are installed to meet current codes. Recommend installing additional smoke detectors as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information on smoke detectors visit http://www.cpsc.gov/cpscpub/pubs/5077.html | ||
![]() |
23) This is the main panel to the left of the Main entrance. It should be noted that several breakers for the interior of the house are located here. (including the baseboard heater in the kitchen
|
||
![]() |
24) This is the sub panel located in the house
|
||
![]() |
25) This is the fuse panel in the crawl space for the well/pressure tank system.
|
| Fireplaces and solid fuel burning appliances | Return to table of contents |
![]() |
26) All solid fuel burning appliances (woodstoves and fireplaces) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary. |
![]() |
27) Significant amounts of ashes, wood and/or debris are in the fireplace. The inspector was unable to fully evaluate it however the damper is in working order. |
| Doors, Windows, & Interior | Return to table of contents |
![]() ![]() |
28) The gaps larger than 4" found in one or more guardrails were up to code when this house was built, however not to current codes This is a safety hazard, especially for small children. If this is a concern to you I recommend that a qualified contractor make modifications as necessary, such as installing additional balusters, so gaps in guardrails don't exceed 4".
|
||
![]() ![]() |
29) The weatherstrip at the bottom of the South exterior entry door is damaged. Recommend installing weatherstripping at entry door(s) where damaged. | ||
![]() ![]() |
30) Fixtures such as door stops, towel bars and/or toilet paper holders are missing in one or more areas. Recommend having a qualified contractor install fixtures where missing. Some work is in progress and some parts are on site. | ||
![]() |
31) No exhaust fan is installed in the laundry room. Due to the fact that the laundry area is in the hall way moisture may not be as big an issue as if it were enclosed by a door. This can lead to excessive accumulation of moisture. Recommend having a qualified contractor install an exhaust fan with a timer, duct and vent cap as per standard building practices in the laundry room if this is a concern to you. | ||
32) Additional photo of stair rails with larger than four inch gaps
|
|||
33) Kitchen cabinets were removed for floor installation at the time of inspection so no appliances were checked
|
| Detached garage or buildings | Return to table of contents |
![]() ![]() ![]() |
34) The garage vehicle door "auto-reverses", but requires too much force. The door should reverse relatively easily when closing and when it strikes something. This is a safety hazard, especially for small children. Recommend having a qualified garage door contractor evaluate and repair or replace opener as necessary. | ||
![]() |
35) Photo from Northeast of garage.
|
||
![]() |
36) The weatherstrip around the exterior entry dooris damaged. Recommend installing weatherstripping at entry door(s) where damaged. | ||
![]() |
37) Minor cracks (1/8" or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration. Numerous products exist to seal such cracks including: |
||
![]() ![]() ![]() |
38) There are no soffit vents to allow air flow up to the peak vents. Depending on the type of finish and cubic feet of attic space there may be insufficent ridge venting also | ||
39) Photo of storage shed to west of garage. shed is in good condition and much newer construction.
|
![]() Photo 3 |
![]() Photo 4 |
![]() Photo 5 |
![]() Photo 6 |
![]() Photo 9 |
![]() Photo 18 |