This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
![]() | Safety | Potential safety hazard |
![]() | Major defect | Correction likely involves a significant expense |
![]() | Repair/Replace | Recommend repairing or replacing |
![]() | Repair/Maintain | Recommend repair and/or maintenance |
![]() | Minor defect | Correction likely involves only a minor expense |
![]() | Maintain | Recommend ongoing maintenance |
![]() | Evaluate | Recommend evaluation by a licensed technician |
![]() | Comment | For your information |
Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Kitchen
Bathrooms
Interior rooms
| General information | Return to table of contents |
![]() ![]() |
1) Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygenists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites: |
| Exterior | Return to table of contents |
![]() |
2) Trees and/or shrubs are in contact with or are close to the roof edge(s) in one or more areas. Damage to the roof may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.
|
| Roof | Return to table of contents |
![]() |
3) Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof. |
| Garage | Return to table of contents |
![]() ![]() ![]() |
4) Flexible lamp or appliance cord is being used for permanent wiring in one or more areas. This wiring is not intended to be used as permanent wiring, and poses a safety hazard of shock and fire. A qualified electrician should evaluate and make repairs as necessary. |
| Attic | Return to table of contents |
![]() ![]() |
5) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing. | ||
![]() |
6) Ceiling insulation is missing in some areas. Recommend installing insulation where missing for better energy efficiency.
|
||
![]() |
7) Some attic areas were inaccessible due to stored items, lack of permanently installed walkways, the possibility of damage to loose fill insulation, and/or low height. These areas are excluded from this inspection. |
| Electric service | Return to table of contents |
![]() ![]() ![]() |
8) One or more ground fault circuit interrupter (GFCI) breakers in the main service panel would not trip when tested. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs and/or replace circuit breakers as necessary. |
| Water heater | Return to table of contents |
![]() ![]() |
9) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future. | ||
![]() ![]() |
10) Water stains were found below the water heater. This may be a sign that the water heater is failing. A qualified plumbing contractor should evaluate and replace or repair the water heater if necessary. | ||
![]() ![]() |
11) No water supply shut-off valve is visible for the water heater. A shut-off valve allows the supply to the water heater to be turned off when the water heater needs repair or replacement, while allowing the remainder of the plumbing system to be operable (toilets, sinks, etc.). Recommend having a qualified, licensed plumbing contractor determine if a water supply shut-off valve exists, and install one if it is missing.
|
| Heating and cooling | Return to table of contents |
![]() ![]() |
12) The estimated useful life for forced air furnaces is 15 to 20 years. This furnace appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future. |
![]() ![]() |
13) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future. |
| Plumbing and laundry | Return to table of contents |
| Fireplaces, woodstoves and chimneys | Return to table of contents |
| Kitchen | Return to table of contents |
![]() ![]() |
14) The dishwasher is excessively noisy. A qualified appliance technician should evaluate and repair as necessary, or the dishwasher should be replaced. |
![]() ![]() |
15) The range hood fan is inoperable. A qualified contractor should evaluate and repair or replace the fan or the range hood as necessary. |
![]() ![]() |
16) One or more stove top burners are inoperable. A qualified appliance technician should evaluate and repair as necessary. |
| Bathrooms | Return to table of contents |
![]() ![]() ![]() |
17) One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested with the inspector's test instrument. These devices should trip when tested with a test instrument in addition to tripping via the test buttons on the receptacles. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary. | ||
![]() ![]() |
18) One or more exhaust fans is inoperable or provides inadequate air flow. Moisture may accumulate as a result. A qualified contractor should evaluate and replace the fan or make repairs as necessary.
|
||
![]() ![]() |
19) One or more faucets leak or drip when turned off. A qualified plumber should evaluate and repair as necessary.
|
| Interior rooms | Return to table of contents |
![]() ![]() ![]() |
20) Relatively few electric receptacles are installed in one or more interior rooms. This can result in "octopus" wiring with extension cords, which is a fire hazard. A qualified electrician should evaluate and install additional receptacles as necessary and as per standard building practices. | ||
![]() ![]() |
21) An insufficient number of smoke alarms are installed. Additional smoke alarms should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html | ||
![]() ![]() |
22) The doorbell appears to be inoperable. Recommend having a qualified electrician evaluate and repair as necessary. | ||
![]() ![]() |
23) Seals between double-pane glass in one or more windows appear to have failed based on condensation or stains between the panes of glass. A qualified contractor should evaluate and replace glass where necessary. The client(s) should be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Windows or glass doors other than those that the inspector identified may also have failed seals and need glass replaced too.
|