Complete Home Inspection LLC

Website: http://www.yourcompletehomeinspection.com
Company email: ron@yourcompletehomeinspection.com
Inspector's email: completehomeinspec@yahoo.com
Company phone: (574) 904-4459
Inspector's phone: (574) 904-1304
P.o. Box 1061 
New Carlisle, IN 46552
Inspector: Ron Colpitts
HI00800074

 

Property Inspection Report
Client(s): Kirsten McKinney
Property address: 66350 US 31
Lakeville, Indiana
Inspection date: 04/07/2010
This report published on Wednesday, April 07, 2010 9:41:03 PM EDT

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Basement
Well
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Inspector: Ron Colpitts
Structures inspected: House/Garage
Type of building: Single family
Property owner's name: Timms
Time started: )9:00
Time finished: 10:30
Inspection Fee: 200.00
Payment method: Escrow
Occupied: Yes
Weather conditions: Rain
Temperature: Cool
Ground condition: Wet
Front of structure faces: West
Main entrance faces: West
Foundation type: Unfinished basement
The following items are excluded from this inspection: Private sewage disposal system, Irrigation system, Private well, Shed, Water filtration system, Water softener system, Outbuildings
1) Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:
  • The Environmental Protection Association (http://www.epa.gov)
  • The Consumer Products Safety Commission (http://www.cpsc.gov)
  • The Center for Disease Control (http://www.cdc.gov)
    2) Some wall, floor and/or ceiling surfaces were obscured by furniture and/or stored items. Some areas couldn't be evaluated.
     
    Exterior Return to table of contents
    Footing material: Poured in place concrete
    Foundation material: Poured in place concrete
    Apparent wall structure: Wood frame
    Wall covering: Vinyl
    Driveway material: Poured in place concrete
    Sidewalk material: Poured in place concrete
    Exterior door material: Solid core steel
    3) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

    Photo 4  
     

    4) Fascia boards are damaged or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary.This was found on the garage

    Photo 7  
     

    5) One or more outside faucets appeared to be inoperable. No water came out of the faucet(s) when turned on. This may be due to a (winterizing) shut-off valve being turned off. As per the NACHI and ASHI Standards of Practice, the inspector did not attempt to turn on or off any water supply shut-off valves. Recommend that the client(s) ask the seller about outside faucets with no water, and/or have a qualified plumber evaluate and repair faucet(s) as necessary.This was found on the faucet on the front of house.
    6) One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.This water is running alongside the sidewalk and can cause underminning and cause the sidewalk to crack.

    Photo 3  
     

    7) Recommend cleaning deck(s) and treating with a preservative claiming to waterproof, block ultraviolet light, and stop mildew. Consumer Reports recommends these products:

  • Cabot Decking Stain and PTW Stain
  • Olympic Water Repellent Deck Stain
  • Thompson's House and Deck Stain
  • Wolman PTW Deck Stain
  • Akzo Sikkens Cetol DEK
  • Benjamin Moore Moorwood Clear Wood Finish
  • DAP Woodlife Premium
  • Olympic Natural Look Protector Plus

    Photo 2  
     

    8) The exterior finish in some areas is failing. A qualified contractor should prep (pressure wash, scrape, sand, prime caulk, etc.) and repaint or restain areas as needed and as per standard building practices.

    Photo 8  
     

    9) Minor cracks were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.This was found by the garage.
    10) The substructure of the deck is excluded from the inspection due to limited access because of the low height.

    Photo 5  

    Photo 6  
     
    Roof Return to table of contents
    Roof inspection method: Viewed from eaves on ladder, Viewed from ground with binoculars
    Roof type: Gable
    Roof covering: Asphalt or fiberglass composition shingles
    Gutter & downspout material: Aluminum
    11) One or more composition shingles have raised, most likely due to nails that have loosened. Leaks may occur as a result. A qualified roofing contractor should evaluate and make repairs as necessary, such as reseating nails.This was found on the garage

    Photo 9  
     

    12) Debris has accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.
     
    Garage Return to table of contents

    13) Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

    Photo 35  
     

    14) Extension cords are being used as permanent wiring in one or more areas. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring poses a fire and shock hazard, and is an indication that wiring is inadequate and should be updated. Extension cords may be undersized. Connections may not be secure, resulting in power fluctuations, damage to equipment, and sparks that could start a fire. Extension cords should be removed as necessary, or a qualified electrician should evaluate and make repairs as necessary. For example, install additional circuits and/or electric receptacles.This was found to be powering lights.
    15) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

    Photo 33  
     

    16) The interior perimeter of the garage is excluded from this inspection due to lack of access from stored items.
    17)   Junction box uses edison style screw in fuses this poses a risk of shock when replacing fuses recommend updated box to circut breaker style fuses.

    Photo 34  
     
     
    Attic Return to table of contents
    Inspection method: Not inspected
    18) The attic access hatch was inaccessible due to stored items, debris, or the hatch being permanently closed. The inspector was unable to evaluate the attic, and it's excluded from this inspection. Recommend moving items or modifying hatch(es) as necessary to allow periodic evaluation of attic spaces.
     
    Electric service Return to table of contents
    Primary service type: Overhead
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120/240
    Location of main service switch: In the basement
    Location of sub panels: In the upstairs family room and garage
    Location of main disconnect: Breaker at top of main service panel
    Service entrance conductor material: Aluminum
    System ground: Ground rod(s) in soil, Concrete encased electrode
    Main disconnect rating (amps): 200
    Smoke detectors present: Yes
    19) One or more screws are missing from the main service panel cover and should be replaced. Because energized wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws do not come in contact with wiring inside the panel when they are installed. Stock screws from the panel manufacturer should be used, or their equivalent.

    Photo 15  
     

    20)   View of electrical panel

    Photo 16  
     
     
    Water heater Return to table of contents
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 40
    Model: G1H4040T3NV
    21)   View of water heater

    Photo 14  
     
     
    Heating and cooling Return to table of contents
    Primary heating system energy source: Natural gas
    Primary heat system type: Forced air
    Primary A/C energy source: Natural Gas
    Primary Air conditioning type: Split system
    Distribution system: Sheet metal ducts
    Manufacturer: Tempstar
    Model: NUG5075B 604
    Filter location: In return air duct below furnace
    22) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. For more information visit: http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
    23) What appears to be asbestos is visible on some ductwork. However, it appears to be intact and not significantly deteriorated. The client may wish to have this material tested at a qualified lab. For information on asbestos hazards in the home, visit http://www.cpsc.gov/CPSCPUB/PUBS/453.html

    Photo 21  
     

    24) The outdoor air temperature was below 60 degrees Fahrenheit during the inspection. Because of this, the inspector was unable to operate and fully evaluate the cooling system.
    25)   Silicone sealant is failing around the exhaust vent for the furnace recommend having sealant replaced by a qulified heating and air conditioning techniyion

    Photo 13  
     

    26)   View of furnace

    Photo 12  
     
     
    Plumbing and laundry Return to table of contents
    Water pressure (psi): 39 psi
    Location of main water shut-off valve: Basement
    Water service: Private
    Service pipe material: Copper, Galvanized steel
    Supply pipe material: Copper
    Vent pipe material: Plastic, Cast iron
    Drain pipe material: Plastic
    Waste pipe material: Plastic, Cast iron
    27) Copper water supply pipes in homes built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client(s) should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client(s) should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:

  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than six hours.
  • Install appropriate filters at points of use.
  • Use only cold water for cooking and drinking. Hot water dissolves lead more quickly than cold water.
  • Use bottled or distilled water.
  • Treat well water to make it less corrosive.
  • Have a qualified plumbing contractor replace supply pipes and/or plumbing components as necessary.

    For more information visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
    http://www.epa.gov/safewater/lead/index.html
    28) Water pressure is below 40 psi, but the flow appeared to be adequate. 40-80 psi is considered to be the normal range for water pressure in a home. The inspector performed a "functional flow test" during the inspection, where multiple fixtures are run simultaneously, and found there to be adequate flow. For example, the shower flow did not decrease significantly when the toilet was flushed.

    If the client finds the flow to be inadequate, recommend having a qualified plumber evaluate and repair as necessary. Installing a pressure boosting system is one possible solution. For information on these systems, visit: http://www.low-water-pressure.com/

    Photo 11  
     

    29) Recommend having the septic tank inspected. Recommend having the tank pumped if it was last pumped more than 3 years ago.
    30) Neither the clothes washer nor dryer were operated or evaluated. They are excluded from this inspection.
    31)   Well pump area has a edison style fuse box with screw in type fuses these pose a safety risk due to shock. Fuse box is also dirty and filled with cobb webs .Recommend having a qualified electrician evauluate and repair if needed.

    Photo 17  
     

    32)   Water flow from outside faucet

    Photo 10  
     
     
    Fireplaces, woodstoves and chimneys Return to table of contents
    Fireplace type: Metal prefabricated
    Woodstove type: Metal
    Chimney type: Metal
    33) All solid fuel burning appliances (woodstoves and fireplaces, etc.) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
    34)   Woodstove could not be fully evauluated due to it being in use
     
    Basement Return to table of contents
    Insulation material underneath floor above: None visible
    Beam material: Solid wood
    Floor structure above: Solid wood joists
    35) Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

    Photo 20  
     

    36) Handrail(s) at some stairs are ungraspable and are a safety hazard. Handrails should be sized and shaped so your hand can encircle them. A qualified contractor should make repairs or modifications as necessary. For example, replacing existing handrails or installing additional handrails.Also hand rail is missing on other side of stairs with jagged wood sticking up which poses a safety risk should someone fall. Recommend removing jagged wood and installing an appropriate handrail.

    Photo 23  
     

    37) Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains and/or efflorescence on the foundation or floor, water stains at bases of support posts, etc. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. The client(s) should review any disclosure statements available and ask the property owner(s) about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:
  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.The west end of the basement appeared to have newer paint.

    Photo 18  
     

    38) Some portions of the basement could not be fully evauluated due to stored items.

    Photo 22  
     

    39)   The sub floor under the tub on the main level appeared to have past water leaking problem. Although the area appeared to be dry at present this area should be monitored.

    Photo 19  
     
     
    Well Return to table of contents
    Location of well equipment: Basement
    40) Recommend having the well water tested for coliform bacteria, nitrates, and anything else of local concern, by a qualified lab. For more information, visit http://www.wellowner.org
    41) This property's water pressure was below 40 psi at times during the inspection. 40-80 psi is considered to be the normal range for water pressure in a home. Most well equipment operates in a 20 psi range during its use and recharge cycle. The client(s) may find that the lower pressures in this range may not be adequate. For example, when one person is showering and another is using other plumbing fixtures. Modifications can be made such as adjusting or replacing the pressure regulator switch. Recommend having a qualified well or plumbing contractor evaluate and make repairs as necessary. For more information, visit http://www.wellowner.org/awellmaintenance/waterpressure.shtml
    42) No pressure gauge installed. A qualified plumber or well contractor should install one as per standard building practices. The inspector was not able to fully evaluate the well equipment due to there being no pressure gauge.
     
    Kitchen Return to table of contents

    43) One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested with the inspector's test instrument. These devices should trip when tested with a test instrument in addition to tripping via the test buttons on the receptacles. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.

    Photo 32  
     

    44)   Dishwasher had dishes in it and could not be fully evaluated.

    Photo 31  
     
     
    Bathrooms Return to table of contents

    45) One or more wall-mounted electric switches are within reach of shower stalls. This is a safety hazard due to the risk of shock. At a minimum, the client(s) should be aware of the shock hazard this represents and never operate such switches while showering. Ideally, a qualified electrician should evaluate and move switches as necessary, or a qualified contractor should make modifications as necessary so wall switches are unreachable from shower stalls.
    46) One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

    Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.This was found in main bathroom by the sink.

    47) One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.This was found in main bathroom a swell as laundry room bath
     
    Interior rooms Return to table of contents

    48) One or more open ground, three-pronged electric receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. For example, replacing receptacles or correcting wiring circuits.

    Grounding type receptacles began being required in residential structures during the 1960s. Based on the age of this structure and the presence of 2-pronged receptacles in some areas of this structure, an acceptable repair may be to simply replace the ungrounded 3-pronged receptacles with 2-pronged receptacles. However the following appliances require grounding type receptacles: Found upstairs on all outlets

  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

    This list is not exhaustive. Grounded circuits and receptacles should be installed in locations where such appliances will be used.
    49) Evidence of "light to moderate" rodent infestation was found in one or more areas. The Center for Disease Control (CDC) defines this as less than 20 feces per square foot. Rodent infestation may be a safety hazard due to the risk of contracting Hantavirus Pulmonary Syndrome (HPS). HPS is a rare (only 20-50 cases per year in the United states) but deadly (40% mortality rate) disease transmitted by infected rodents through urine, droppings, or saliva. Humans can contract the disease when they breathe in aerosolized virus. For example, from sweeping up rodent droppings.
    Bait traps found in closet.
    Recommend following guidelines in the CDC's Clean Up, Trap Up, Seal Up article for eradicating rodents, cleaning up their waste and nesting materials, and preventing future infestations. While Hantavirus is believed to survive less than one week in droppings and urine, specific precautions should be taken during clean up. The client(s) may wish to consult with a qualified, licensed pest control operator for eliminating the infestation. A qualified licensed abatement contractor or industrial hygienist could be contacted for clean up. If the infestation was minimal, clean up of rodent waste and nesting materials in non-living spaces (crawl spaces and attics) may not be necessary, or may be performed for aesthetic reasons only (odor and appearance).

    50) This structure was built prior to 1979 and may contain lead paint. Laws were enacted in 1978 in the US preventing the use of lead paint in residential structures. Lead is a known safety hazard, especially to children but also to adults. The paint found in and around this structure appeared to be intact and may be encapsulated by more recent layers of paint that are not lead-based. Regardless, recommend following precautions as described in the following links to Consumer Products Safety Commission website articles regarding possible lead paint.

    What You Should Know About Lead Based Paint in Your Home: Safety Alert - CPSC Document #5054

    CPSC Warns About Hazards of "Do lt Yourself" Removal of Lead Based Paint: Safety Alert - CPSC Document #5055

    51) The doorbell appears to be inoperable. Recommend having a qualified electrician evaluate and repair as necessary.
    52)   Unfinished drywall was found at the top of stairs on the second level
     

    Photo 24  

    Photo 25  

    Photo 26  

    Photo 27  

    Photo 28  

    Photo 29  

    Photo 30  
     

     
    The inspection and report will be preformed according to the Standards of the American Society of Home Inspectors (ASHI) the terms in this agreement shall have the same meaning given to them in the ASHI standards. A copy of the ASHI standards will be provided at the client’s request. Visit www.ashi.org for further information.