HOME ANALYSIS REPORT
Client(s): Rob Campbell
Property address: 24 Geneva St
Brockville
On
Inspection date: 4/27/2010
This report published on Monday, May 03, 2010 10:14:58 PM EDT

View summary page

This report is the exclusive property of Charles W. Boyd Home Inspection Services and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior / Foundation
Roof / Attic
Garage / Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating
Cooling / Heat Pump
Fireplaces / Stoves / Chimneys
Kitchen
Bathrooms / Laundry / Sinks
Interior Rooms / Areas
Structural Pest Findings
 
General Information Return to table of contents
Report number: 24geneva
Time started: 3 pm
Time finished: 6 pm
Inspector: Charles Boyd
Present during inspection: Client
Client present for discussion at end of inspection: Yes
Weather conditions: Snow
Temperature: Cold
Ground condition: Snow covered
Inches of accumulated snow: 2
Inspection fee: $350
Payment method: Cash$80 cash on site, balance to be mailed
Type of building: Single family
Buildings inspected: 1
Number of residential units inspected: 1
Age of building(s): 1959 approx
Source for building age: Client
Front of building faces: North
Main entrance faces: North
Occupied: No, Furniture or stored items were present
Property owner's name:
1) In random order, I present to you seven different ways in which a home inspection report can be used by parties to a real estate transaction for mutual advantage and benefit.

Buyers can consider the reported conditions of the home's systems to determine their ability to afford and maintain the property.

A home with a 12-year-old water heater, an 18-year-old furnace, and a 25-year-old composite-shingle roof is going to need some costly investments in the near future.


Buyers can sometimes use information regarding undisclosed defects to negotiate the seller's action to repair the defect(s) or adjust the asking price for the home.


Sellers can obtain a home inspection and use the report to disclose known defects to potential buyers.


Sellers can obtain a home inspection and use the report to identify and correct significant defects that could interfere with a buyer's desire to submit a contract to buy the property.


Buyers can use the inspection report as a punch list (or to-do list) for maintaining the property after purchase.


Buyers/Sellers can use the report to communicate to contractors the nature of the defect(s) to obtain estimates for repair or to arrange for repairs or replacements.


Buyers can sometimes use the inspection report as a means to withdraw from the contracted agreement to purchase the home when certain types of undisclosed defects are reported.


Buyers and sellers should consider obtaining inspection reports only from professional, full-time home inspectors. Builders and contractors who generate inspection reports often use them as marketing tools and as a means to generate business for maintenance and repairs. Doing so is a conflict of interest, so their reports do not always represent the actual conditions of the property. Always use home inspectors who abide by a Code of Ethics and Standards of Practice, and who continually upgrade their knowledge and skills with regular Continuing Education courses.

2) Dear Client,
Thank you for choosing Charles Boyd Home Inspection Services to perform your home inspection. The goal of
this inspection and report is to put you in a better position to make an informed real estate decision. This
report is a general guide and provides you with some objective information to help you make your own
evaluation of the overall condition of the home and is not intended to reflect the value of the property, or
to make any representation as to the advisability of purchase. Not all improvements will be identified
during this inspection. Unexpected repairs should still be anticipated. This inspection is not a guarantee or
warranty of any kind.
When you contract me (Charles Boyd)to perform a general inspection in
accordance with the standards of practice established by the National Association of Certified Inspectors
(NACHI), a copy of which is either included with this report or can be downloaded from the Internet at http://www.nachi.org/sop.htm.
General inspections are visual, and distinct from those of specialists, as they do not always include the use of specialized instruments, the dismantling of equipment, or the sampling of air (unless contracted) Consequently, a general inspection and the subsequent report will not be as comprehensive, nor as technically exhaustive, as that generated by specialists, and it is not intended to be. The purpose of a general inspection is to identify significant defects or adverse conditions that would warrant a specialist evaluation. Therefore, you should be aware of the limitations of this type of inspection, which are clearly indicated in the sop (Standards of Practice). However, the inspection is not intended to document cosmetic deficiencies that would be apparent to the average person, and certainly not intended to identify insignificant deficiencies. Similarly, I can only inspect for evidence of vermin infestation, and advise the hiring of a licensed exterminator.
With regards to plumbing and electrical systems that is not visible due to being placed in interior walls, I cannot be responsible for any leaks that may occur before, during or after the course of the inspection.
As I am not destructive during my inspections we cannot and may not be able to give an accurate condition of the piping within the walls.
I highly encourage all clients to complete a FINAL walk through of the property prior to closing.
My inspection may occur many weeks before your closing date, sometimes 3 months or more. Please remember, the home will likely have been lived in during that time and consequently a “moving day” will have occurred. A “lived in” home gets wear and tear and it may not be in exactly the same condition as the day of the inspection. Remember that the seller may be experiencing some stress of selling, finding another home and then moving day. I take many, many pictures throughout the inspection for this reason. Some may not be included in the report but are on file with me if needed.
Please refer to the completed inspection report to ensure all defects noted within the report have been repaired if required.
Visit http://nachi.org/sop.htm to learn more about the scope of a home inspection.

3)   The residence is furnished, and in accordance with industry standards we only inspect those surfaces that are exposed and readily accessible. We do not move furniture, lift carpets or rugs, nor do we remove or rearrange items within closets or cabinets. On your final walk through, or at some point after furniture and personal belongings have been removed, it is important that you inspect the interior portions of the residence that were concealed or otherwise inaccessible and contact us immediately if any adverse conditions are observed that were not reported on in your inspection report.

Photo 82  

Photo 94  

Photo 95  
 

4)   Charles W. Boyd
Home Inspection Services
8251 Klitbo Rd North Augusta On.
613-926-0892
Home Inspection Agreement
The address of the property is: ________________________________________________________________________.
Fee for the home inspection is $___________. Inspector acknowledges receiving a deposit of $________ from CLIENT.
THIS AGREEMENT made this _________ day of _________________, 200__, by and between Charles W. Boyd Inspection Services(Hereinafter called “”THE INSPECTOR”) and the undersigned (hereinafter called “THE CLIENT”), collectively referred to herein as “the parties”. The Parties Understand and
Voluntarily Agree as follows:
1. This agreement constitutes the entire contract and agreement between the parties and there are no verbal understandings or other agreements of any
nature with respect to the subject matter of this contract except as contained in writing herein. CLIENT understands and agrees that the written report
provided by INSPECTOR pursuant to this Contract constitutes the only representations made by the INSPECTOR with respect to the subject matter
of this contract.
2. INSPECTOR agrees to perform a visual inspection of the home/buildings and provide CLIENT with a written inspection report identifying the
defects that INSPECTOR both observed and deemed material. This is a generalist inspection completed in a limited amount of time. It is not a code compliance
inspection and does not include any research, such as the necessary to establish boundaries, easements, or the issuance of permits and
certificates of occupancy. The inspection report is not a substitute for the Transfer Disclosure Statement, which is required by civil code.
INSPECTOR may offer comments as a courtesy, but these comments will not comprise the bargained-for report.
3. Unless otherwise inconsistent with this Agreement or not possible, INSPECTOR agrees to perform the inspection in accordance to the current
Standards of Practice of the National Association of Certified Home Inspectors a copy of which is posted at http://www.nachi.org/sop.htm. CLIENT
understands that these standards contain certain limitations, exceptions and exclusions.
4. The inspection and report are performed and prepared for the use of CLIENT, who gives INSPECTOR permission to discuss observations with
real estate agents, owners, repairpersons and other interested parties. INSPECTOR accepts no responsibility for use or misinterpretation by third
parties. INSPECTOR'S inspection of the property and the accompanying report are in no way intended to be a guarantee or warranty, express or
implied, regarding the future use, operability, habitability or suitability of the home/building or its components. Any and all warranties, express or
implied, including warranties or merchantability and fitness for a particular purpose, are expressly excluded by this Agreement.
5. INSPECTOR does not perform engineering, architectural, plumbing, or any other job function requiring an occupational license in the jurisdiction
where the inspection is taking place, unless the inspector holds a valid occupational license, in which case he/she may inform the CLIENT that he/she
is so licensed, and is therefore qualified to go beyond this basic home inspection, and for additional fee, perform additional inspections beyond those
within the scope of the basic home inspection. Any agreement for such additional inspections shall be in a separate writing.
6. In the event of a claim against INSPECTOR, CLIENT agrees to: (1) undertake emergency measures only; (2) not alter, repair, replace, correct or
modify any disputed component or condition without first supplying INSPECTOR written notification of adverse conditions within 14 days of
discovery; (3) allow INSPECTOR, or their representative, access to the premises for re-inspection of the disputed item(s). Failure to comply with the
above conditions will release INSPECTOR and its agents from any and all obligations or liability of any kind.
7. The parties agree that any litigation arising out of this Agreement shall be filed only in the Court having jurisdiction in the County in which the
INSPECTOR has its principal place of business. In the event that CLIENT fails to prove any adverse claims against INSPECTOR in a court of law,
CLIENT agrees to pay all legal costs, expenses and fees of INSPECTOR in defending said claims.
8. If any court declares any provision of this Agreement invalid or unenforceable, the remaining provisions will remain in effect. This Agreement
represents the entire agreement between the parties. All prior communications are merged into this Agreement, and there are no terms or conditions
other than those set forth herein. No statement or promise of INSPECTOR or its agents shall be binding unless reduced to writing and signed by
INSPECTOR. No change or modification shall be enforceable against any party unless such change or modification is in writing and signed by the
parties. This Agreement shall be binding upon and enforceable by the parties and their heirs, executors, administrators, successors and assignees.
CLIENT shall have no cause of action against INSPECTOR after one (1) year from the date of the inspection. This time may be shorter than the law
otherwise provides.
9. Payment of the fee to INSPECTOR (less any deposit noted above) is due upon completion of the on-site inspection. The CLIENT agrees to pay
all legal and time expenses incurred in collecting due payments, including attorney's fees, if any. If CLIENT is a corporation, LLC, or similar entity,
the person signing this Agreement on behalf of such entity does personally guaranty payment of the fee by the entity.
Client/Agent
Initials
_______ 10. INSPECTOR assumes no liability for the cost of repair or replacement of unreported defects or
deficiencies either current or arising in the future. CLIENT acknowledges that the liability of INSPECTOR, its
agents, employees, for claims or damages, costs of defence or suit, attorneys fees and expenses and payments
arising out of or related to the INSPECTOR'S negligence or breach of any obligation under this Agreement,
including errors and omissions in the inspection or the report, shall be limited to liquidated damages in an
amount equal to the fee paid to the INSPECTOR, and this liability shall be exclusive. CLIENT waives any
claim for consequential, exemplary, special or incidental damages or the loss of the use of the home/building
even if the CLIENT has been advised of the possibility of such damages. The parties acknowledge that the
liquidated damages are not intended as a penalty but are intended (i) to reflect the fact that actual damages may
be difficult and impractical to ascertain; (ii) to allocate risk among the INSPECTOR and CLIENT; an (iii) to
enable the INSPECTOR to perform the inspection at the stated fee.
AUTHORIZATION
I, ____________________________,_____________________________, have carefully read and understood all the above terms and conditions.
terms, conditions and limitations of this contract and voluntarily agree to be bound thereby and agree to pay the fee listed above.
 
Grounds Return to table of contents
Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
The following items are excluded from this inspection: Outbuildings, Fences and gates, Shed, Invisible fencing
Site profile: Level
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Asphalt
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Condition of decks, porches and/or balconies: Appeared serviceable
Condition of guardrails: Appeared serviceable
Deck, porch and/or balcony material: Wood
Condition of exterior stairs: Appeared serviceable
Condition of handrails: Appeared serviceable
Exterior stair material: Wood
5) One or more trip hazards were found in sidewalk and/or patio sections due to cracks, settlement, heaving and/or deterioration. A qualified contractor should evaluate and repair or replace sections as necessary to eliminate trip hazards.

Photo 59  
 

6) Minor cracks, settlement, heaving and/or deterioration were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
 
Exterior / Foundation Return to table of contents
Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of wall covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Brick veneer
Condition of foundation and footings: Appeared serviceable
Foundation type: Finished basement
Foundation material: Concrete block
Footing material: Not determined
Condition of floor substructure: Appeared serviceable
Pier or support post material: Steel
Beam material: Solid wood
Floor structure: Solid wood joists
Condition of the basement: Appeared serviceable
7) Minor cracks or deterioration were found in one or more sections of brick veneer. A qualified contractor should evaluate and make repairs as necessary, such as repointing mortar to prevent water intrusion and further deterioration in the future.

Photo 22  

Photo 41  

Photo 42  

Photo 47  

Photo 48  

Photo 50  

Photo 51  

Photo 52  

8) Parging on one or more foundation walls was damaged or deteriorated. A qualified person should repair as necessary.

Photo 44  

Photo 46  

9)   In accordance with the InterNACHI Standards of Practice pertaining to Exteriors, this report describes the
exterior wall coverings and trim. Inspectors are required to inspect the exterior wall coverings, flashing,
trim, all exterior doors, the stoops, steps porches and their associated railings, any attached decks and
balconies and eaves, soffits and fascias accessible from ground level. Inspectors shall also inspect
adjacent or entryway walkways, patios, and driveways; vegetation, grading, surface drainage, and
retaining walls that are likely to adversely affect the building.

10)   In accordance with the InterNACHI Standards of Practice pertaining to Structural Components, this report
describes the foundation, floor, wall, ceiling and roof structures and the method used to inspect any
accessible under floor crawlspace areas. Inspectors are required to inspect and probe the structural
components of the home, including the foundation and framing, where deterioration is suspected or
where clear indications of possible deterioration exist. Probing is not done when doing so will damage
finished surfaces or when no deterioration is visible or presumed to exist. Inspectors are NOT required to
offer an opinion as to the structural adequacy of any structural systems or components or provide
architectural services or an engineering or structural analysis of any kind. Despite all efforts, it is
impossible for a home inspection to provide any guaranty that the foundation, and the overall structure
and structural elements of the building is sound. The inspector suggests that if the client is at all
uncomfortable with this condition or our assessment, a structural engineer be consulted to independently
evaluate any specific concern or condition, prior to making a final purchase decision.

11)   Much of the basement has a drywall type of wallboard installed over vapou barrier directly on the block walls. This is a condition condusive to mould issues and some apparent mould type fungi was noted on parts of the west bsaement wall. Recommend removal of all outside wallboard, strapping and any vapour barrier and properly dispose of. Treat concrete walls with a mould removal type of cleaner and leave to dry out. Ventilation will be the key to a good clean up. Recommend a visual inspection and possible air quality sampling before installing any new walls.
New wall should be constructed as per sandard building practices and as per local building codes.
Some water staining also noted on basement ceiling tiles, client may wish to remove tiles

Photo 15  

Photo 16  

Photo 17  

Photo 18  

Photo 19  

Photo 20  

Photo 21  
 
 
Roof / Attic Return to table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
Condition of roof structure: Appeared serviceable
Roof type: Gable
Age of roof surface(s): unknown
Roof inspection method: Traversed
Roof surface material: Asphalt or fiberglass composition shingles
Apparent number of layers of roof surface material: One
Condition of gutters, downspouts and extensions: Appeared serviceable
Gutter and downspout material: Metal
Gutter and downspout installation: Full
Condition of attic: Appeared serviceable
Attic inspection method: Viewed from hatch(es)
Roof structure type: Rafters
Ceiling insulation depth: 12 inches approx
Vapor retarder: Not determined
Roof ventilation: Appears serviceable
12) Some downspouts were loose. Water may accumulate around the building foundation as a result. A qualified person should evaluate and repair as necessary.

Photo 41  
 

13) Most roof surfaces were obscured by snow and couldn't be fully evaluated. Aeas that could be seen have cracked, broken shingles and some partly missing tabs. My opinion is that roof covering needs replacing now, recommend qualified roofing contractor evaluate and repair or replace.
Caport roof was completely snow covered and may also need repair.

Photo 65  

Photo 66  

Photo 67  

Photo 68  

Photo 69  

Photo 70  

Photo 71  
 

14)   In accordance with the InterNACHI Standards of Practice pertaining to Roofing, this report describes the
roof coverings and the method used to inspect the roof. Inspectors are required to inspect the roof
covering, roof drainage systems, flashings, skylights, chimneys and roof penetrations. The following web
sites are an excellent resource of information on roofs:
http://www.home-roofs.com and http://www.roofhelper.com

15)  

Photo 27  

Photo 28  

Photo 29  

Photo 30  

Photo 31  

Photo 32  

Photo 33  

Photo 34  

Photo 35  

Photo 36  
 
Garage / Carport Return to table of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages varies between municipalities.
Type: Carport
Condition of detached garage or carport structure: Appeared serviceable
16)   It is not uncommon for moisture to penetrate garages, because their slabs are on-grade. Evidence of this
is typically apparent in the form of efflorescence, or salt crystal formations, that result when moisture
penetrates the concrete slab or sidewalls. This is a common with garages that are below grade, and some
sidewalls are even cored to relieve the pressure that can build up behind them, and which actually
promotes drainage through the garage. Also, if there is living space above the garage, that space will be
seismically vulnerable. Ideally, the columns and beams around the garage door will be made of structural
steel, but in many residences these components are made of wood but could include some structural
accessories, such as post-straps and hold-downs, and plywood shear paneling. However, we are not an
authority in such matters, and you may wish to discuss this further with a structural engineer. In
addition, and inasmuch as garage door openings are not standard, you may wish to measure the opening
to ensure that there is sufficient clearance to accommodate your vehicles.
 
Electric Return to table of contents
Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Required repair, replacement and/or evaluation (see comments below)
Primary service type: Overhead
Number of service conductors: 2
Service voltage (volts): 120
Service amperage (amps): 100
Primary service overload protection type: Circuit breakers
Main disconnect rating (amps): 100
System ground: Cold water supply pipes
Condition of main service panel: Appeared serviceable
Condition of sub: Appeared serviceable
Location of main service panel #A: Basement
Branch circuit wiring type: Non-metallic sheathed
Condition of branch circuit wiring: Required repair, replacement and/or evaluation (see comments below)
Solid strand aluminum branch circuit wiring present: Not determined
17) The service mast was bent, slightly. A qualified electrician should evaluate and replace the mast or make repairs as necessary.

Photo 72  

Photo 74  

18) Many electric receptacles had reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary. Mostly in the bedrooms were no ground and revese polarity, recommend upgrade by qualified electricain

Photo 101  
 

19) Relatively few electric receptacles were installed in areas. This can result in "octopus" wiring with extension cords, which is a fire hazard. A qualified electrician should evaluate and install additional receptacles as necessary and as per standard building practices.
20) One or more electric receptacles at the kitchen, exterior had no visible ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf

Photo 76  
 

21) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.google.com/search?q=old+smoke+alarms

22) This property has a fuel burning appliance, and no carbon monoxide detectors were visible. This is a safety hazard. Recommend installing one or more carbon monoxide detectors as necessary and as per the manufacturer's instructions. For more information, visit:
http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

23) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Centigrade. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950 may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Centigrade. Connecting older, 60 degree-rated wiring to such newer fixtures is a potential safety hazard due to the risk of fire. Repairs for such conditions often involve replacing the last few feet of wiring to newer fixtures with new 90 degree-rated wire. This often requires installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware that this safety hazard may be present in this building. Recommend consulting with the property owner to determine if and when newer fixtures were installed, and/or to have a qualified electrician evaluate and repair as per standard building practices.

24) The electric service to this property appeared to be rated at substantially less than 200 amps, and may be inadequate for the client's needs. Recommend consulting with a qualified electrician about upgrading to a 200 amp service.

Photo 7  

Photo 8  

Photo 25  

Photo 26  

25) Some electric receptacles were not evaluated because of furniture, stored items.
26)   In accordance with the InterNACHI Standards of Practice pertaining to Electrical Systems, this report
describes the amperage and voltage rating of the service, the location of the main disconnect and any
sub panel(s), the presence of solid conductor aluminum branch circuit wiring, the presence or absence of
smoke detectors and wiring methods. Inspectors are required to inspect the viewable portions of the
service drop from the utility to the house, the service entrance conductors, cables and raceways, the
service equipment and main disconnects, the service grounding, the interior components of the service
panels and sub panels, the conductors, the over-current protection devices (fuses or breakers), ground
fault circuit interrupters and a representative number of installed lighting fixtures, switches and
receptacles. All issues or concerns listed in this Electrical section should be construed as current and a
potential personal safety or fire hazard. Repairs should be a priority, and should be made by a
qualified, licensed electrician.
 
Plumbing / Fuel Systems Return to table of contents
Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Location of main water meter: basement
Location of main water shut: meter
Water service: Public
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of waste lines: Appeared serviceable
Waste pipe material: Copper
27) Copper water supply pipes in buildings built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:

  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than six hours.
  • Install appropriate filters at points of use.
  • Use only cold water for cooking and drinking. Hot water dissolves lead more quickly than cold water.
  • Use bottled or distilled water.
  • Treat well water to make it less corrosive.
  • Have a qualified plumbing contractor replace supply pipes and/or plumbing components as necessary.

    For more information visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
    http://www.epa.gov/safewater/lead/index.html
    28) Most water supply pipes in the basement were uninsulated. Recommend insulating pipes as per standard building practices for better energy efficiency and to prevent water pipes from freezing.
    29)   In accordance with the InterNACHI Standards of Practice pertaining to Plumbing systems, this report
    describes the water supply, drain, waste and vent piping materials and the water heating equipment,
    energy source and location of the main water and main fuel shut-off valves, when readily viewable or
    known. Inspectors are required to inspect the interior water supply and distribution systems, all fixtures
    and faucets, the drain waste and vent systems (including all fixtures for conveying waste), the water
    heating equipment (vent systems, flues and chimneys of water heaters or boiler equipment), fuel storage
    and distributions systems for water heaters and/or boiler equipment and drainage sumps, sump pumps
    and associated piping. Some simple plumbing repairs, such as a typical trap replacement, can be
    performed by a competent handyman. However, any more complex issues such as incorrect venting or
    improperly sloped drains should be repaired by a licensed plumber. All gas related issues should only
    be repaired by a licensed contractor —since personal safety is involved.

    30)   Unused oil tank in basement, recommend pump and remove soon, old oil tanks will rust and can result in an expensive oil spill

    Photo 11  

    Photo 12  
     
    Water Heater Return to table of contents
    Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
    Condition of water heater: Appeared serviceable
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 40
    Condition of burners: Appeared serviceable
    Condition of venting system: Appeared serviceable
    Condition of combustion air supply: Appeared serviceable
     
    Heating Return to table of contents
    Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating system components, does not determine if heating systems are appropriately sized, or perform any evaluations that require a pilot light to be lit. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks.
    Condition of heating system: Appeared serviceable
    Location of heating system: Basement
    Heating type: Forced air
    Fuel type: Natural gas
    Last service date:
    Condition of burners: Appeared serviceable
    Condition of venting system: Appeared serviceable
    Condition of combustion air supply: Appeared serviceable
    Condition of distribution system: Appeared serviceable
    Distribution system: Ducts and registers
    Condition of controls: Appeared serviceable
    Condition of air filters: Appeared serviceable
    Location of air filters: At base of air handler
    31)   In accordance with the InterNACHI Standards of Practice pertaining to Heating and Air Conditioning
    (HVAC) systems, this report describes the energy source and the distinguishing characteristics of the
    heating and cooling system(s). Inspectors are required to open readily openable access panels and
    visually inspect the installed heating equipment and associated vent systems, flues and chimneys; and
    central air conditioning equipment and distribution systems. The HVAC system inspection is general and
    not technically exhaustive. The inspector will test the heating and air conditioner using the thermostat
    and/or other normal controls. The inspector highly recommends that a standard, seasonal or
    yearly, Service and Maintenance Contract with an HVAC contractor be obtained. This provides a
    more thorough investigation of the entire home's heating, air conditioning and filtering system as well as
    maintaining it at peak efficiency —thereby increasing service life.
     
    Cooling / Heat Pump Return to table of contents
    Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
    32) The outdoor air temperature was below 60 degrees Fahrenheit during the inspection. Because of this, the inspector was unable to operate and fully evaluate the cooling system.

    Photo 45  
     
     
    Fireplaces / Stoves / Chimneys Return to table of contents
    Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, nor determine if prefabricated or zero clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit.
    Fuel type: Natural gas
    33)   Recommend sevice an full evaluation by qualified contactor before next heating season

    Photo 91  

    Photo 92  

    Photo 93  
     
     
    Kitchen Return to table of contents
    Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
    Condition of counters: Appeared serviceable
    Condition of cabinets: Appeared serviceable
    Condition of sinks and related plumbing: Appeared serviceable
    Condition of range, cooktop: Appeared serviceable
    Range, cooktop type: Electric
    34)   Inspector observed and operated the basic functions of the following appliances: Permanently installed
    dishwasher(s), through its normal cycle; Range, cook top, and permanently installed oven; Trash
    compactor; Garbage disposal; Ventilation equipment or range hood; Permanently installed microwave
    oven; and Conveying laundry appliances. Interior refrigerator/freezer temperatures are not tested.
    Inspection of stand-alone freezers and secondary refrigerators are outside the scope of this inspection. No
    opinion is offered as to the adequacy of dishwasher operation. Oven self or continuous cleaning
    operations, cooking functions, clocks, timing devices, lights and thermostat accuracy are not tested
    during this inspection. Appliances are not moved and the condition of any walls or flooring hidden by
    them cannot be judged.

    35)   Kitchen faucett seemed loose, recommend evaluate and repair.

    Photo 78  
     
     
    Bathrooms / Laundry / Sinks Return to table of contents
    Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
    Condition of counters: Appeared serviceable
    Condition of cabinets: Appeared serviceable
    Condition of sinks and related plumbing: Appeared serviceable
    Condition of toilets: Appeared serviceable
    Condition of bathtubs and related plumbing: Appeared serviceable
    Condition of shower(s) and related plumbing: Appeared serviceable
    Condition of laundry facilities: Appeared serviceable
    Gas supply for laundry equipment present: Not determined
    36) The bathroom with a shower at location #A didn't have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
    37)   Main bathroom is oler and may need some upgrading, winows in shower was quite common in the time period this house was built. This has led to some water damage in alot of homes. There is some minor water damage on the bottom corner of the window trim. It is not wet at this time, there may be some hidden damage behind ceramic tile walls

    Photo 2  

    Photo 3  

    Photo 4  

    Photo 5  

    Photo 6  
     
     
    Interior Rooms / Areas Return to table of contents
    Master Bedroom:
    Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
    Exterior door material: Wood
    Condition of exterior entry doors: Appeared serviceableMay wish to upgrade to newer insulated doors with proper weather strip
    Condition of interior doors: Appeared serviceable
    Type of windows: Single pane, Multi
    Condition of windows: Required repair, replacement and/or evaluation (see comments below)
    Wall type or covering: Drywall
    Condition of walls: Appeared serviceable
    Ceiling type or covering: Drywall
    Condition of ceilings: Appeared serviceable
    Flooring type or covering: Carpet, Vinyl
    Condition of flooring: Appeared serviceable
    38) Minor cracks and/or holes were found in walls in some closet areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.

    Photo 102  

    Photo 104  

    Photo 105  
     

    39)   In accordance with the InterNACHI Standards of Practice pertaining to Interiors, inspectors are required
    to inspect walls, ceilings and floors, steps, stairways and railings, installed countertops and a
    representative number of installed cabinets, and representative number of doors and windows. Garage
    door(s) and automatic garage door operators are inspected for proper function and the operation of
    installed safety features. If the home is occupied, the possessions of the owner necessarily conceal some
    areas/items. These are exempt from inspection. All reasonable attempt is made to more closely inspect
    behind the owner's possessions if any hint of a problem is found or suspected.
     
    Structural Pest Findings Return to table of contents
    Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than five feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood destroying organisms may infest, reinfest or become active at anytime. No warranty is provided as part of this inspection.
    Visible evidence of active wood destroying insects: No
    Visible evidence of active wood decay fungi: Possibly
    Visible evidence of past wood destroying insects: No
    Visible evidence of past wood decay fungi: Yes
    Visible evidence of damage by wood destroying insects: No
    Visible evidence of damage by wood decay fungi: YesBasement wallboard
    Visible evidence of conditions conducive to wood destroying organisms: No
     

    Photo 1  
    Flower gardens such as this trap moistue against walls, recommend removal or liner of some type

    Photo 9  
    Sump pump appeared serviceable.
    Note: effloresense on walls, it is a salt that comes out of concrete when humidity is present, this corner on the outside has a defective downspout.

    Photo 10  
    Copper wastepipe in most of the basement, appears to be working properly, it is 50 + years old and may begin to leak. Recommend monitoring

    Photo 13  
    Older water stains below main bath, no serious damge and repairs must have been made

    Photo 14  
    Minor repair at front corner of house recommened

    Photo 23  
    Effloresense in basement fom humidity

    Photo 24  

    Photo 39  

    Photo 40  

    Photo 43  
    Parging repair needed at step, back door

    Photo 49  

    Photo 53  
    Below deck, no issues here

    Photo 54  

    Photo 55  

    Photo 56  

    Photo 57  

    Photo 58  
    Stair stringers poperly located on patio stones helps prevent rot

    Photo 60  
    Some repointing needed at window sills

    Photo 61  

    Photo 62  

    Photo 63  

    Photo 64  

    Photo 73  

    Photo 75  

    Photo 77  

    Photo 79  

    Photo 80  

    Photo 81  

    Photo 83  

    Photo 84  

    Photo 85  

    Photo 86  

    Photo 87  

    Photo 88  

    Photo 89  

    Photo 90  

    Photo 96  

    Photo 97  

    Photo 98  

    Photo 99  

    Photo 100  

    Photo 103  

    Photo 106  

    Photo 107  

    Photo 108  

    Photo 109  

    Photo 110  

    Photo 111  

    Photo 112  

    Photo 113  

     