"HOME INSPECTIONS REPORT"
Client(s): Jenifer Moreau & Mark Garrard
Property address: 15 Sanders Drive
Port Hope, Ontario
L1A 4E8
Port Hope
Inspection date: Tuesday, March 27, 2007
This report published on 3/29/2007 9:06:16 AM EDT

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
www.reporthost.com/certresinsp
www.inspectorpages.com/tlabrosse1

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major defectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor defectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Basement
Kitchen
Bathrooms
Interior rooms
 

General information 
Return to table of contents

Report number: 0125
Report number:
Structures inspected: two-story residential home
The following items are excluded from this inspection: Playground equipment
Type of building: Single family
Time started: 12:30
Time finished: 3:00
Inspection Fee: $300.00
Occupied: Yes
Weather conditions: Partly cloudy
Temperature: Warm
Ground condition: Damp
Front of structure faces: West
Main entrance faces: West
Foundation type: Finished basement
1) Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygenists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:
  • The Environmental Protection Association (http://www.epa.gov)
  • The Consumer Products Safety Commission (http://www.cpsc.gov)
  • The Center for Disease Control (http://www.cdc.gov)
    2) Some wall, floor and/or ceiling surfaces were obscured by furniture and/or stored items. Some areas couldn't be evaluated.
    3) GENERAL LIMITATIONS:
    We cannot visually inspect the interior of any covered walls, floors, or ceilings.We do not disassemble equipment , move boxes or furniture or lift up carpet or area rugs etc.
    unlessspecified within this report we do not inspect septic tanks,wells, appliances,heat exchangers,wood stoves, fireplaces,heating appliances,interior of chimney flues, central vacuum systems, air-conditioners,intercom systems, phone lines, cable lines, security systems, enviromental issues, underground storage sysytems, fuel storage systems, underground water,waste or draiage lines,U.F.F.I,asbestos containing materials,marine items and the like. We can only report on items that are able to be inspected visually and only at the will of the property owner.
     
    Return to table of contents

    Footing material: None
    Foundation material: Poured in place concrete
    Apparent wall structure: Brick
    Wall covering: Brick veneer, Vinyl
    Driveway material: Asphalt
    Sidewalk material: Brick
    Exterior door material: Solid core steel
    4) One or more trip hazards were found in sidewalk and/or patio sections due to cracks, settlement and/or heaving. A qualified contractor should evaluate and repair or replace sidewalk and/or patio sections as necessary to eliminate trip hazards.

    Photo 4  
     

    5) One or more electric receptacles and/or the boxes they are installed in are loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.

    Photo 5  
     

    6)
    7) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

    Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079

    Photo 10  
     

    8) One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.

    Photo 7  

    Photo 11  

    Photo 16  
     

    9) One or more exhaust duct end caps are damaged and/or deteriorated. Their purpose is to prevent unconditioned air from entering the house, and keep out birds, rodents and bugs. Blocked ducts can cause fan motors and/or clothes dryers to overheat and may pose a fire hazard. New vent cap(s) should be installed where necessary.

    Photo 8  
     

    10) One or more minor cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks including:
  • Hydraulic cement. Requires chiseling a channel in the crack to apply. See http://www.quickrete.com/catalog/HydraulicWater-StopCement.html for an example.
  • Resilient caulks (easy to apply). See http://www.quickrete.com/catalog/GrayConcreteRepair.html for an example.
  • Epoxy sealants (both a waterproof and structural repair). See http://www.mountaingrout.com/ for examples of these products.

    Photo 3  
     

    11) One or more sections of foundation and/or exterior walls are excluded from this inspection due to lack of access from vegetation, debris and/or stored items.

    Photo 9  
     

    12) Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.

    Photo 17  
     

    13)   LIMITATIONS:Substantially / partially finished basements / crawlspace observations.
    **We are unable to detect existance or type of mould in interior spaces.Further investigation is required.
     
    Return to table of contents

    Roof inspection method: Viewed from eaves on ladder
    Roof type: Gable
    Roof covering: Asphalt or fiberglass composition shingles
    Estimated age of roof: 17 years
    Gutter & downspout material: Aluminum
    Roof ventilation: Adequate
    14) The roof surface material appears to be near the end of its service life and will likely need replacing in the near future, even with repairs. The client(s) should budget for a replacement roof surface, and may want to have a qualified roofing contractor evaluate and attempt to issue a "5 year roof certificate".
    15) Debris has accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.
    16) **LIMITIATIONS: Due to the unpredictable and latent nature of roof leaks, no assurances or warranty can be provided that your roof wil not develop leaks at any time after the inspection date.
     
    Return to table of contents


    17) The interior perimeter of the garage is excluded from this inspection due to lack of access.
     
    Return to table of contents

    Inspection method: Viewed from hatch, Partially traversed
    Roof structure type: Trusses
    Ceiling structure: Trusses
    Insulation material: Fiberglass loose fill
    Insulation depth: 8-9 inchs
    Insulation estimated R value: R28- R30
    18) **LIMITATIONS: The inspection process cannot predict the ability of the roof structures to support heavy snow loads.
    19)

    Photo 22  

    Photo 23  

    Photo 24  

    Photo 25  

    Photo 26  
     
     
    Return to table of contents

    Primary service type: Underground
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 125
    Service voltage (volts): 120/240
    Location of main disconnect: Breaker at top of main service panel
    Service entrance conductor material: Copper
    System ground: Copper
    Main disconnect rating (amps):
    Branch circuit wiring type: Copper
    Smoke detectors present: Yes
    20) One or more overcurrent protection devices (circuit breakers or fuses) are "double tapped", where 2 or more wires are clamped in a terminal designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. A qualified electrician should evaluate and repair as necessary.

    Photo 27  

    Photo 28  

    Photo 29  
     

    21) Based on the size of the rating of the main service panel, the size of the service conductor wires, and/or the rating of the main disconnect device, it appears that the main service panel is undersized. This is a potential fire hazard. A qualified electrician should evaluate and repair if necessary.

    Photo 1  
     

    22) The electric service to this property appears to be rated at substantially less than 200 amps, and may be inadequate for the client(s) needs. Recommend consulting with a qualified electrician about upgrading to a 200 amp service.
     
    Return to table of contents

    Estimated age: 17 years
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 50
    Manufacturer: Rheem
    23) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age or older and may need replacing at any time. Recommend budgeting for a replacement in the near future.

    Photo 34  

    Photo 35  
     
    Return to table of contents

    Estimated age: 17 years
    Primary heating system energy source: Natural gas
    Primary heat system type: Forced air
    Primary A/C energy source:
    Distribution system: Sheet metal ducts
    Manufacturer: Lennox
    Filter location: At the top of the furnace
    24) Because of the age and/or condition of this furnace, recommend that a qualified heating and cooling technician inspect the heat exchanger and perform a Carbon Monoxide test when it's serviced.
    25) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. For more information visit: http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html
    26) The estimated useful life for forced air furnaces is 15 to 20 years. This furnace appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.

    Photo 36  
     

    27) The estimated useful life for heat pumps is 15 to 20 years. This heat pump appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
    28) The filter(s) for the heating/cooling system should be checked monthly and replaced or washed as necessary.
    29)   **LIMITATIONS:Determining winter comfort within specific areas is beyond the scope of a visual inspection.
    **LIMITATION: The heat exchanger is concealed within the furnance and cannot be fully inspected. Further evauluation is recommended.
     
    Return to table of contents

    Water pressure (psi): 60
    Location of main water shut-off valve: basement
    Location of main water meter:
    Water service: Public
    Service pipe material: Copper
    Supply pipe material: Copper
    Vent pipe material: Plastic
    Drain pipe material: Plastic
    Waste pipe material: Plastic
    30) The clothes dryer is equipped with a vinyl or foil, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, see http://www.cpsc.gov/CPSCPUB/PUBS/5022.html

    Photo 33  
     

    31) The laundry sink is not anchored to the wall or floor. A qualified contractor should securely anchor the sink to the wall and/or floor to prevent damage to and leaks in the water supply and/or drain pipes due to the sink being moved.
    32) The laundry sink is stained badly. Recommend replace the sink.

    Photo 32  
     

    33) The clothes dryer exhaust duct is routed vertically. This can result in extended drying times, premature failure of the motor, drum rollers and heater. Recommend having a qualified contractor reconfigure the clothes dryer exhaust duct so it is routed horizontally, or as close to it as possible.
    34) The inspector was not able to find the water meter. Recommend that the client(s) attempt to find the water meter by consulting with the property owner(s), searching for it themselves, or consulting with the local water municipality. It is especially important to find the meter if no main shut-off valve is found because the meter may be the only way to turn off the water supply in the event of an emergency, such as when a supply pipe bursts.
    35) Neither the clothes washer nor dryer were operated or evaluated. They are excluded from this inspection.
    36)   **LIMITATIONS: The visual acess to main drain lines and drain underneath basement floors is restricted. No assurances can be provided regarding proper drainage conditions or performances. Sewer backup is beyond our ability to detect or predict.
     
    Return to table of contents

    Insulation material underneath floor above: None visible
    Pier or support post material: Wood
    Beam material: Steel
    Floor structure above: Solid wood joists
    37) Some wiring is loose, unsupported, or inadequately supported. Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.

    Photo 30  
     

    38) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

    Photo 31  
     

    39) Cover plate(s) are broken at one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be replaced where necessary.
    40)   **LIMITATION: Due to the unpredictable and latent nature of basement leaks, no assurances or warranty can be provided that your basement will not leak in the future.
    We caution you that it is common for basement leaks to develop at any time in the future where no such leak existed in the past.
     
    Return to table of contents


    41) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
    42) Vinyl flooring is damaged and/or deteriorated in one or more areas. A qualified contractor should replace or repair the damaged flooring.

    Photo 38  
     

    43) None of the kitchen applainces were inspected at buyers request.
    (not included)

    Photo 40  
     
     
    Return to table of contents


    44) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
    45) Tile and/or grout in one or more showers is damaged and/or deteriorated. For example, deteriorated or missing grout, cracked, missing or loose tiles, etc. A qualified contractor should evaluate and repair tile and/or grout as necessary.
    46)   **LIMITATIONS: Due to the unpredictable and latent nature of plumbing,shower, and bathtub enclosure leaks, no assurances or warranty can be provided that leaks will not develop at any time after the inspection date.
     
    Return to table of contents


    47) Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

    Photo 31  
     

    48) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
    49) Screen(s) in one or more windows are damaged.

    Photo 6  
     

    50) One or more air supply registers are loose or installed in a substandard way. Repairs should be made as necessary so registers are securely attached, flush with the surface they are installed on, and otherwise correctly installed.

    Photo 19  
     

    51) The doorbell button is loose or damaged. It should be repaired or replaced as necessary, and by a qualified contractor if necessary.

    Photo 18  
     

    52) One or more windows are rotted and/or deteriorated in some way. Repairs should be made as necessary by a qualified contractor.

    Photo 12  

    Photo 13  

    Photo 14  
     

    53) Screen(s) in one or more windows are torn or have holes in them. Screens should be replaced where necessary.

    Photo 37  
     

    54)
    55)

    Photo 20  

    Photo 21  

    Photo 39  
     

     
    IF YOU HAVE ANY QUESTIONS OR CONCERNS ABOUT THE REPORT FILL FREE TO CONTACT ME AT (905)885-7941 OR YOU CAN E-MAIL ME AT tlabrosse@on.nachi.org.
    THANK YOU FOR CHOOSING CERTIFIED RESENTIAL INSPECTIONS.
    www.inspectorpages.com/tlabrosse1
    www.reporthost.com/certreinsp
    http://www.reporthost.com/certresinsp/contract.doc
    http://www.reporthost.com/certresinsp/moldwaiver.pdf
    http://www.reporthost.com/certresinsp/radon.doc.pdf