ERS Property Inspection Report

Client(s):  Lisa Rubel
Property address:  417 S. Rodeo Drive Beverly Hills 90212
Inspection date:  Saturday, July 16, 2016

This report published on Wednesday, July 20, 2016 6:44:15 PM PDT

Dear Customer:

Thank you for choosing Empire Realty Service to perform the following inspection on the property you wish to purchase. This report is the exclusive property of Empire Realty Service and the individual(s) paying for the inspection fee and report. Use of this report by any unauthorized persons is prohibited.

All findings should be made to Empire Realty Service.

This report represents our professional opinion of the condition of the inspected elements of the subject property, determine during a limited time inspection. This inspection was performed, where applicable, in a manner consistent with the standards of the home inspection industry, terms and conditions of the inspection agreement and limitations noted in the inspection agreement. Information contained herein was prepared exclusively for the named client and their authorized representatives.

We have inspected the subject property and must report to you exactly what we found. Because of the age, design and location of the home, we might find some hairline cracks on driveways or walls, see paint peeling off walls, cracks on tiles, chipped bathtubs or some cracks over windows and doors. These are normal and cosmetic conditions.

While due care was exercised in the performance of this inspection, the company makes no representations or guarantees with respect to latent deficiencies or future conditions as part of the inspection or this report. This report is valid only for a period of thirty (30) days from the date of the inspection. This report, including any attachments, should be reviewed in its entirety. Any questions about the inspection or report should be resolved prior to title transfer.

This inspection report was prepared in a format specifically for the individual/s paying for the inspections fee and report and such transfer does not cover all potential areas of concern a third party may have. This report is transferable only with the consent of the individual/s paying for inspections fee and report and such transfer does not imply any warranty or guarantee regarding the report by inspection firm.

No warranty, guarantee, or insurance by Empire Realty Service is expressed or implied. This report does not include inspection for wood destroying insects, mold, lead or asbestos. A representative sampling of the building components is viewed in areas that are accessible at the time of the inspection. No destructive testing or dismantling of components is performed. Not all defects will be identified during this inspection. Unexpected repairs should be anticipated.

The person conducting your inspection is not a licensed structural engineer or other professional whose license authorizes the rendering of an opinion as to the structural integrity of a building or its other component parts.

You are advised to seek two professional opinions and acquire estimates of repair as to any defects, comments, improvements or recommendations mentioned in this report. We recommend that the professional making any repairs inspect the property further, in order to discover and repair related problems that were not identified in the report. We recommend that all repairs, corrections, and cost estimates be completed and documented prior to closing or purchasing the property. Feel free to hire other professionals to inspect the property prior to closing, including HVAC professionals, electricians, plumbers, engineers, or roofers.

If you have any questions regarding this report, please feel free to call us.


How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeServiceableItem or component is in serviceable condition
Concern typeCommentFor your information
Concern typeInfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.)
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Swimming Pool
Exterior and Foundation
Crawl Space
Roof
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows


General Information
Return to table of contents

Time started: 1pm
Time finished: 3pm
Client present for discussion at end of inspection: Yes
Inspector: Dan Moreno
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Warm
Ground condition: Dry
Overnight temperature: Cool
Type of building: Single family
Age of main building: 1934
Occupied: Yes

1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC

2) Based on construction observed, to this property may have been made without the owner having attained permits or inspections from the municipality. Work may have been performed by someone other than a qualified contractor or person. Consult with the property owner about this, and if necessary research permits.

At worst case, if substantial work was performed without permits, this knowledge must be disclosed when the building is sold in the future. This can adversely affect future sales. Also, the local municipality could require costly alterations to bring the building into legal compliance or even require that the additions or modifications be removed.

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Condition of fences and gates: Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Wood, Masonry
Condition of retaining walls: Required repair, replacement and/or evaluation (see comments below)
Retaining wall material: Masonry block
Site profile: Level
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete, Stone
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Stones
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Concrete
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Metal

3) Guardrails at one or more locations with drop-offs higher than 30 inches had gaps that were too large. This poses a safety hazard for children (e.g. falling, getting stuck in railing). Guardrails should not have gaps or voids that allow passage of a sphere equal to or greater than 4 inches in diameter, or 6 inches in diameter at triangular spaces between stair edges and guardrails. Recommend that a qualified contractor repair or replace guardrails per standard building practices.
Photo
Photo 3-1
 

4) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.
Photo
Photo 4-1
Photo
Photo 4-2

5) Significant cracks, deterioration, leaning and/or bowing were found in one or more retaining walls. Recommend that a qualified contractor evaluate and repair or replace sections as necessary. Note that some retaining walls, based on their height or size, may require evaluation by a structural engineer.
Photo
Photo 5-1
Photo
Photo 5-2
Photo
Photo 5-3
Photo
Photo 5-4
Photo
Photo 5-5
Photo
Photo 5-6

6) One or more gates were damaged or deteriorated and need repair.
Photo
Photo 6-1
 

7) Found grounds to be in serviceable condition except where deficiencies were noted.
Photo
Photo 7-1
Photo
Photo 7-2

8) Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.
Photo
Photo 8-1
Photo
Photo 8-2

Swimming Pool
Return to table of contents

Limitations: The following items are not included in this inspection: swimming pool bodies; equipment on timers, remote controls or sensors; underground or concealed piping; motorized covers; waterfalls and related equipment; Ozone generators; ultraviolate light systems; filter backflushing mechanisms. Any comments made regarding these items are as a courtesy only. Note that the inspector does not disassemble filters, remove pool covers, nor determine if swimming pool bodies, filters or skimmers leak, nor determine if swimming pool bodies are level.
Condition of fences and gates: Required repairs, replacement and/or evaluation (see comments below)
Fence and gate material: Wrought iron
Condition of body: Required repairs, replacement and/or evaluation (see comments below)
Condition of deck: Required repairs, replacement and/or evaluation (see comments below)
Deck material: Concrete
Condition of pumps, lines and valves: Required repair, replacement and/or evaluation (see comments below)
Types of pumps installed: Circulation
Line material: CPVC
Condition of heater and related equipment: Appeared serviceable
Heater energy source: Natural gas
Condition of filter and related equipment: Required repair, replacement and/or evaluation (see comments below)
Filter type: Cartridge
Filter air relief valve installed: Yes
Filter pressure gauge installed: Yes
Condition of skimmers: Appeared serviceable
Condition of electrical equipment: Appeared serviceable

9) The alarm for one or more doors between the house was missing. While regulations vary between municipalities, all doors which give access to a swimming pool should be equipped with an audible alarm that should:
  • Sound for 30 seconds or more when the door and/or screen are opened
  • Sound within seven seconds after the door is opened
  • Be loud; at least 85 dBA (decibels) at 10 feet away
  • Be distinct from other sounds in the house
  • Have a manual switch to disable it temporarily where the switch is located at least 54 inches above the door's threshold
  • Have an automatic reset feature
A qualified person should evaluate and repair as necessary. For more information, visit:
http://www.reporthost.com/?POOLBARR
http://www.reporthost.com/?POOLSAFETY
Cost estimate: $100

10) Self-closing devices on one or more gates used with pool or spa fencing were missing. This is a safety hazard because these devices are intended to control access to the pool or spa, especially for children. A qualified person should repair, replace or install as necessary. For more information, visit:
http://www.reporthost.com/?POOLBARR

11) Self-latching devices on one or more gates used with pool or spa fencing were inoperable. This is a safety hazard because these devices are intended to control access to the pool or spa, especially for children. A qualified person should repair, replace or install as necessary. For more information, visit:
http://www.reporthost.com/?POOLBARR

12) Plaster on the pool body surface had extensive cracks, popups, chipping and/or significant wear. Recommend that a qualified contractor replaster the entire surface. Concrete pools or spas should be replastered every 10 to 15 years. For more information, visit:
http://www.reporthost.com/?POOLPLASTER
Cost estimate: $6,000 to $8,000
Photo
Photo 12-1
 

13) The grout and/or caulk in areas of the decking was cracked. A qualified person should repair as necessary.

14) The tile in sections of the coping was cracked. A qualified person should repair as necessary.

15) The reading at the cartridge filter's pressure gauge was relatively high. Cartridge filters should be cleaned when the pressure gauge reads 8 lbs or more above the clean, starting pressure (after cleaning or replacing cartridge). A qualified person should clean or replace cartridge(s) as necessary, and make repairs if necessary.
Photo
Photo 15-1
 

16) The motor for the circulation and/or jet pump appeared to be near, at or beyond its service life. Typically this is eight years but may be longer. The motor may need rebuilding or replacement in the near future.
Cost estimate: $2,000
Photo
Photo 16-1
 

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Stucco
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Crawl space, Post and pier
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
Anchor bolts or hold downs for seismic reinforcement: Installed

17) Conducive conditions Cracks, deterioration and/or damage were found in one or more areas of the exterior stucco finish. In damp climates, moisture may enter cracks or damaged areas and further deteriorate the stucco. Also the wall behind the stucco may become damaged from moisture. Note that areas behind the stucco are inaccessible and excluded from this inspection. Recommend that a qualified contractor repair or replace stucco as necessary.
Photo
Photo 17-1
Photo
Photo 17-2
Photo
Photo 17-3
Photo
Photo 17-4
Photo
Photo 17-5
Photo
Photo 17-6

18) Found dry rot damage at one or more wood trims.
Photo
Photo 18-1
 

19) Found exterior to be in serviceable condition except where deficiencies were noted.
Photo
Photo 19-1
Photo
Photo 19-2

20) Found raised foundation, post and piers to be in serviceable condition.
Photo
Photo 20-1
Photo
Photo 20-2
Photo
Photo 20-3
Photo
Photo 20-4

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Traversed
Location of crawl space access point #A: Hall closet
Location of crawl space access point #B: Building exterior
Crawl space access points that were opened and viewed, traversed or partially traversed: A, B
Condition of floor substructure above: Appeared serviceable
Condition of crawl space ventilation: Appeared serviceable

21) Infestation Found rodent droppings in one or more places in the crawl space, recommend to fumigate.
Photo
Photo 21-1
 

22) The screens for one or more crawl space vents were damaged. Vermin or pets can enter the crawl space and nest, die and/or leave feces and urine. Vermin often damage under-floor insulation too. Recommend that a qualified person install or replace screens where necessary using 1/8-inch to 1/4-inch wire mesh.
Photo
Photo 22-1
 

23) Found the crawl space to be in serviceable condition except where deficiencies were noted.
Photo
Photo 23-1
Photo
Photo 23-2
Photo
Photo 23-3
Photo
Photo 23-4
Photo
Photo 23-5
Photo
Photo 23-6

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Viewed from eaves on ladder
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Clay tile, Rolled composition
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
Gutter and downspout material: Metal
Gutter and downspout installation: Partial

24) Found the following deficiencies at the roof surface and or clay tiles:
Loose or sliding tiles due to lack of mortar.
One or more cracked tiles.
Trees in contact.
Damaged vent cover
Photo
Photo 24-1
Photo
Photo 24-2
Photo
Photo 24-3
Photo
Photo 24-4
Photo
Photo 24-5
Photo
Photo 24-6

25) Found roof to be in serviceable condition except where deficiencies were noted.
Photo
Photo 25-1
Photo
Photo 25-2
Photo
Photo 25-3
Photo
Photo 25-4
Photo
Photo 25-5
Photo
Photo 25-6

Garage or Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Swinging
Number of vehicle doors: 2
Condition of garage floor: Required repair, replacement and/or evaluation (see comments below)
Condition of garage interior: Required repair or evaluation (see comments below)
Condition of roof structure: Appeared serviceable
Roof inspection method: Viewed from eaves on ladder
Roof type: Flat or low slope
Roof surface material: Clay tile

26) Significant cracks, heaving and/or settlement were found in one or more sections of concrete slab floors. Uneven surfaces can pose a trip hazard. Recommend that a qualified contractor repair or replace concrete slab floors where necessary.
Photo
Photo 26-1
Photo
Photo 26-2

27) Found damage drywall at garage ceiling.
Photo
Photo 27-1
 

28) Found garage to be in serviceable condition except where deficiencies were noted.
Photo
Photo 28-1
Photo
Photo 28-2
Photo
Photo 28-3
Photo
Photo 28-4

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 200
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
Condition of main service panel: Required repair, replacement and/or evaluation (see comments below)
Condition of sub-panel(s): Appeared serviceable
Location of main service panel #A: Building exterior
Location of main service panel #B: Building exterior
Location of sub-panel #C: Laundry room
Location of main disconnect: At main disconnect panel outside
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Copper
Smoke alarm power source(s): Hard wired

29) Panel(s) #A were manufactured by the Zinsco company. These panels and their circuit breakers have a history of problems including bus bars made from aluminum that oxidize and corrode, breakers that don't trip under normal overload conditions, and breakers that appear to be tripped when they're not. This is a potential safety hazard for shock and/or fire. Recommend that a qualified electrician carefully evaluate all Zinsco brand panels and components and make repairs as necessary. Consider replacing Zinsco panels with modern panels that offer more flexibility for new, safer protective technologies like arc fault circuit interrupters (AFCls). For more information, visit:
http://www.reporthost.com/?ZINSCO1
http://www.reporthost.com/?ZINSCO2
Cost estimate: $7,000 to $10,000
Photo
Photo 29-1
 

30) Smoke alarms were missing from one or more bedrooms. Additional smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM
Photo
Photo 30-1
 

31) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.reporthost.com/?SMKALRMLS
Photo
Photo 31-1
 

32) No carbon monoxide alarms were visible. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
http://www.reporthost.com/?COALRM

33) Found electric system to be in serviceable condition except where deficiencies were noted.
Photo
Photo 33-1
Photo
Photo 33-2
Photo
Photo 33-3
Photo
Photo 33-4

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Water pressure (psi): 90
Location of main water meter: Alley
Location of main water shut-off: Building exterior
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Condition of waste lines: Appeared serviceable
Location(s) of plumbing clean-outs: Building exterior
Vent pipe condition: Appeared serviceable
Condition of fuel system:
Location of main fuel shut-off valve: At gas meter

34) Found plumbing to be in serviceable condition.
Photo
Photo 34-1
Photo
Photo 34-2
Photo
Photo 34-3
Photo
Photo 34-4
Photo
Photo 34-5
Photo
Photo 34-6
Photo
Photo 34-7
Photo
Photo 34-8
Photo
Photo 34-9
Photo
Photo 34-10

35) Found gas meter to be in serviceable condition.
Photo
Photo 35-1
 

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Natural gas
Estimated age: 2010
Capacity (in gallons): 40
Temperature-pressure relief valve installed: Yes
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable

36) Based on the capacity of the water heater, the number of bedrooms in this structure and the number of occupants expected to live in this structure, this water heater may be undersized. Consult with a qualified plumber or water heater distributor for more information, and may wish to upgrade the size of the water heater.
Photo
Photo 36-1
Photo
Photo 36-2

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Estimated age of forced air furnace: 3 years
Condition of furnace filters: Required replacement
Location for forced air filter(s): Behind return air grill(s)
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Location: Roof surface
Type: Packaged unit
Estimated age: 3 years
Condition of controls: Appeared serviceable
Condition of whole house fan: Appeared serviceable

37) Found HVAC system to be in serviceable condition.
Photo
Photo 37-1
Photo
Photo 37-2
Photo
Photo 37-3
Photo
Photo 37-4
Photo
Photo 37-5
Photo
Photo 37-6
Photo
Photo 37-7
Photo
Photo 37-8

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Wood-burning fireplace type: Masonry
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Masonry

38) Found fire place, chimneys and flues to have vegetation growing in them and in need of maintenance and or repairs.
Photo
Photo 38-1
Photo
Photo 38-2
Photo
Photo 38-3
Photo
Photo 38-4

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Required repair, replacement and/or evaluation (see comments below)
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Type of ventilation: Wall or ceiling mounted fan
Condition of refrigerator: Appeared serviceable

39) Countertops and/or backsplashes were damaged or deteriorated. Recommend repairing or replacing as necessary.
Photo
Photo 39-1
 

40) One or more cabinet drawers were damaged. Recommend that a qualified person repair as necessary.
Photo
Photo 40-1
 

41) Found kitchen and fixtures to be in serviceable condition except where deficiencies were noted.
Photo
Photo 41-1
 

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Location #B: Full bath
Location #C: Full bath
Location #D: Full bath
Location #E: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Gas supply for laundry equipment present: Yes
240 volt receptacle for laundry equipment present: Yes

42) Found the dryer exhaust cap to be damaged.
Photo
Photo 42-1
 

43) Found bathrooms and fixtures to be in serviceable condition except where deficiencies were noted.
Photo
Photo 43-1
Photo
Photo 43-2
Photo
Photo 43-3
Photo
Photo 43-4
Photo
Photo 43-5
Photo
Photo 43-6

44) Found laundry area and appliance connections to be in serviceable condition.

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Appeared serviceable
Type(s) of windows:
Condition of walls and ceilings: Required repairs, replacement and/or evaluation (see comments below)
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Wood or wood products, Tile
Condition of stairs, handrails and guardrails: Appeared serviceable

45) One or more walls and/or ceilings were damaged and/or were cracked. Recommend that a qualified person repair as necessary.
Photo
Photo 45-1
Photo
Photo 45-2
Photo
Photo 45-3
Photo
Photo 45-4

46) Found the wood floor to be damaged in one or more places.
Photo
Photo 46-1
 

47) Found interior and fixtures to be in serviceable condition.
Photo
Photo 47-1
Photo
Photo 47-2

1.1. A Home Inspection is a non-invasive, visual examination of a residential dwelling, performed for a fee, which is designed to identify observed material defects within specific components of said dwelling. Components may include any combination of mechanical, structural, electrical, plumbing, or other essential systems or portions of the home, as identified and agreed to by the Client and Inspector, prior to the inspection process.

I. A home inspection is intended to assist in evaluation of the overall condition of the dwelling. The inspection is based on observation of the visible and apparent condition of the structure and its components on the date of the inspection, and not the prediction of future conditions.

II. A home inspection will not reveal every concern that exists or ever could exist, but only those material defects observed on the day of the inspection.

III. A home inspection can include a survey and/or analysis of energy flows and usage in a residential property if the client requests it.
1.2. A Material Defect is a condition of a residential real property, or any portion of it, that would have a significant, adverse impact on the value of the real property, or that involves an unreasonable risk to people on the property. The fact that a structural element, system or subsystem is near, at or beyond the end of the normal useful life of such a structural element, system or subsystem is not by itself a material defect.

1.3. An Inspection Report shall describe and identify, in written format, the inspected systems, structures, and components of the dwelling, and shall identify material defects observed. Inspection reports may contain recommendations regarding conditions reported or recommendations for correction, monitoring or further evaluation by professionals, but this is not required.

This inspection was performed in accordance with the current Standards of Practice and Code of Ethics of the International Association of Certified Home Inspectors (InterNACHI). The Standards contain certain and very important limitations, exceptions, and exclusions to the inspection. A complete copy of the STANDARDS OF PRACTICE we adhere to can be found at the following link: http://www.nachi.org/sop.htm