Bowman Home Inspections

Website: http://www.reporthost.com/bowmanhi
Email: bowmanhomeinspections@hotmail.com
Phone: (785) 218-6202
2523 Ousdahl Rd. 
Lawrence, KS 66046
Inspector: Ryan Bowman

 

Residential home inspection for the following residence:
Client(s): Home Buyer
Property address: 555 Somewhere Road,
Anywhere, KS
Inspection date: --/--/--
This report published on 11/21/2007 11:07:02 PM CST

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major defectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor defectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Basement
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Report number: 103
Structures inspected: Residential Structure
Type of building: Single family
Age of building: 40 yrs
Property owner's name: John Bowman
Time started: 9:00 am
Inspection Fee: ----
Payment method: ----
Present during inspection: Client(s), Property owner(s)
Occupied: Yes
Weather conditions: Cloudy
Temperature: Cold
Ground condition: Dry
Front of structure faces: West
Main entrance faces: West
Foundation type: Unfinished basement


1) Some wall, floor and/or ceiling surfaces were obscured by furniture and/or stored items. Some areas couldn't be evaluated.
 
Exterior Return to table of contents
Footing material: Not visible
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Metal
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core steel
2) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079

3) One or more soffit vent panels are missing and/or deteriorated. Birds and vermin may enter the attic because of this. Screens should be replaced or repaired where necessary, or installed where missing.

Photo 5  
Missing soffit section
 

4) One or more moderate cracks (1/8 inch to 3/4 inch) were found in the foundation. These may be a structural concern, or an indication that settlement is ongoing. The client(s) should consider hiring qualified contractors and/or engineers as necessary for further evaluation. Such contractors may include:

  • Foundation repair contractors who may prescribe repairs, and will give cost estimates for prescribed repairs
  • Masonry contractors who repair and/or replace brick veneer
  • Geotechnical engineers who attempt to determine if settlement is ongoing, and what the cause of the settlement is
  • Structural engineers who determine if repairs are necessary, and prescribe those repairs

    At a minimum, recommend sealing cracks to prevent water infiltration. Numerous products exist to seal such cracks including:
  • Hydraulic cement. Requires chiseling a channel in the crack to apply. See http://www.quickrete.com/catalog/HydraulicWater-StopCement.html for an example.
  • Resilient caulks (easy to apply). See http://www.quickrete.com/catalog/GrayConcreteRepair.html for an example.
  • Epoxy sealants (both a waterproof and structural repair). See http://www.mountaingrout.com/ for examples of these products.

    Photo 1  
    Evidence of Patching a potential crack. Monitor for further cracking.

    Photo 4  
    Minor crack in foundation at NE corner.

    Photo 19  
    Moderate horizontal crack in basement wall. Signs of hydrostatic pressure. Recommend evaluation by structural engineer.
     

    5) Soil is in contact with or less than six inches from siding and/or trim. This is a conducive condition for wood destroying insects and organisms. Soil should be graded and/or removed as necessary so there are at least six inches of space between the siding and trim and the soil below.

    Photo 3  
    Ground within 6 inches of siding.
     

    6)

    Photo 2  
    Sump pump drains directly onto patio. It appears to be fitted for an extension. This should be installed when the sump pump is expected to run.
     

    7) Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
     
    Roof Return to table of contents
    Roof inspection method: Viewed from ground with binoculars
    Roof type: Gable
    Roof covering: Asphalt or fiberglass composition shingles
    Estimated age of roof: 10
    Gutter & downspout material: Aluminum
    Roof ventilation: Adequate
    8) One or more composition shingles have raised, most likely due to nails that have loosened. Leaks may occur as a result. A qualified roofing contractor should evaluate and make repairs as necessary, such as reseating nails.

    Photo 6  
    Raised Shingles
     
     
    Garage Return to table of contents

    9) One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

    Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.

    Photo 7  
    Missing cover plate.
     

    10) One or more garage electric receptacles appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all garage receptacles, except for one for use with a refrigerator or freezer, have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    Photo 7  
    Missing cover plate.
     

    11) Wiring runs directly through the wall to the outdoor light fixture. This happens at the rear garage entrance door as well as above the overhead garage door. The result is that wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

    Photo 8  
    Missing Junction box.
     

    12) Some wiring is loose, unsupported, or inadequately supported. Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.

    This occurs at the rear of the garage as well as above the overhead garage door. Wiring should not be freely draped across open spaces as found above the overhead door

    Photo 9  
    Loose Wiring

    Photo 11  
    Loose wire hanging over trusses.

    13) The infared "photo eye" devices that trigger the vehicle door opener's auto-reverse feature are located higher than 4 to 6 inches from the floor. This is a potential safety hazard. A qualified contractor should relocate these devices so they're 4 to 6 inches from the floor. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
    14) The attic access hatch over the attached garage doesn't have a one-hour fire rating. Wall and ceiling surfaces in an attached garage should be fire rated for one hour to prevent or slow the spread of fire from the garage to interior living spaces. This hatch should be replaced with a material that has a one hour fire rating, such as 5/8 inch Type X sheetrock.

    Photo 32  
    Attic Access Door
     

    15) Non-metallic sheathed wiring is routed in one or more areas so it is subject to damage, such as on wall or ceiling surfaces. The insulation can be damaged by objects coming in contact with it and/or it being repeatedly moved. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary. For example, rewire using conduit, or re-routing through wall cavities. This Improper wiring near the southwest corner of the garage. The electrical wire runs on the north side of the truss, crosses over the top and then continues on the south side of the truss. Materials are stored in direct contact with this wire. This could result in abrasion and damage to the wire. A qualified electrician should evaluate and make repairs as necessary.

    Photo 12  
    Unprotected wire is pinched as it runs over the truss in the garage.

    Photo 13  
    Unprotected wire running over truss in garage.

    16) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

    Photo 7  
    Missing cover plate.
     

    17)

    Photo 10  
    Electrical wire for garage door opener is excessively loose and runs through a hanging bicycle. Secure wire to truss.
     

    18) The interior perimeter of the garage is excluded from this inspection due to lack of access from stored items.
     
    Attic Return to table of contents
    Inspection method: Viewed from hatch
    Roof structure type: Trusses
    Ceiling structure: Trusses
    Insulation material: Fiberglass roll or batt
    Insulation depth: 15
     
    Electric service Return to table of contents
    Primary service type: Overhead
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120/240
    Location of main disconnect: Breaker at top of main service panel
    Service entrance conductor material: Aluminum
    19) The service drop wires are less than 10 feet above ground or walkways. This is a safety hazard due to the risk of shock. A qualified electrician and/or the utility company should evaluate and repair as necessary.

    Photo 31  
    Service Wire
     

    20) One or more overcurrent protection devices (circuit breakers or fuses) are "double tapped", where 2 or more wires are clamped in a terminal designed for only one wire. This is a safety hazard since the bolt or screw may tighten securely against one wire, but leave others loose. Arcing, sparks and fires may result. A qualified electrician should evaluate and repair as necessary.

    Photo 14  
    Double tapped breaker.

    Photo 15  
    Double tapped breakers.

    21) Neutral wires are doubled or bundled together on the neutral bus bar. This is unsafe due to the need to turn off multiple circuit breakers to work on any of the circuits using these wires. A qualified electrician should evaluate and repair as necessary.

    Photo 21  
    Bundled neutrals.
     

    22) The legend for overcurrent protection devices (breakers or fuses) in the main service panel is missing, unreadable or incomplete. Recommend installing, updating or correcting the legend as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.
    23)   Multiple splices were found inside the electrical service panel. Recommend evaluation by a qualified electrician.

    Photo 16  

    Photo 20  
    Multiple splices in electrical service panel.
     
    Water heater Return to table of contents
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 40
    Manufacturer: Rheem
    24) No drain line is installed for the temperature-pressure relief valve. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.

    Photo 23  
    Missing drain pipe on pressure relief valve.
     

    25) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
     
    Heating and cooling Return to table of contents
    Estimated age: 15
    Primary heating system energy source: Natural gas
    Primary heat system type: Forced air
    Primary A/C energy source: Electric
    Manufacturer: Ruud
    26) The estimated useful life for most forced air furnaces is 15 to 20 years. This furnace appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
    27) The estimated useful life for air conditioning compressors is 8 to 15 years. This unit appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
    28) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.
    29) Air handler filter(s) should be checked monthly in the future and replaced or washed as necessary.
    30) The outdoor air temperature was below 60 degrees Fahrenheit during the inspection. Because of this, the inspector was unable to operate and fully evaluate the cooling system.
     
    Plumbing and laundry Return to table of contents
    Location of main water shut-off valve: NW corner of Basement, Behind Box
    Location of main water meter: NW Corner of basement behind box
    Location of main fuel shut-off: SE Corner of house, external
    Water service: Public
    Service pipe material: Copper
    Supply pipe material: Copper
    Vent pipe material: Plastic
    Drain pipe material: Plastic
    Waste pipe material: Plastic
    31) The clothes dryer is equipped with a vinyl or foil, accordion-type, flexible exhaust duct. The U.S. Consumer Product Safety Commission considers these types of ducts to be unsafe, and a fire hazard. These types of ducts can trap lint and are susceptible to kinks or crushing, which can greatly reduce the air flow. This duct should be replaced with a rigid or corrugated semi-rigid metal duct, and by a qualified contractor if necessary. Most clothes dryer manufacturers specify the use of a rigid or corrugated semi-rigid metal duct. For more information on dryer safety issues, see http://www.cpsc.gov/CPSCPUB/PUBS/5022.html
    32) Three sump pumps are installed on the premises. This may indicate that water accumulates inside or below the structure. Recommend asking the property owners how often the sump pump operates and for how long at different times of the year. Also, the clients should be aware that the service life of most sump pumps is between five and seven years, and that the pump may need replacing soon depending on its age and how much it operates.
     
    Basement Return to table of contents
    Insulation material underneath floor above: None visible
    Pier or support post material: Wood
    Beam material: Solid wood
    Floor structure above: Solid wood joists
    33) One or more handrails are not continuous for the entire length of the flight of stairs. This is a safety hazard. Handrails should be continuous, and extend the full length of flights of stairs. A qualified contractor should evaluate and repair as necessary.

    Photo 25  
    Loose and short handrail.
     

    34) One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

    Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.

    35) One or more sections of wiring that weren't terminated were found. This is a potential safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary. For example, cutting the wire to length and terminating the wire with wire nuts in a securely anchored, covered, properly sized junction box.

    Photo 17  
    Unterminated electrical wire.

    Photo 22  
    Improperly terminated electrical wire.

    36) Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

    Photo 18  
    Splice outside junction box.
     

    37) Handrail(s) at some stairs are loose. This is a safety hazard. A qualified contractor should make repairs as necessary. For example, installing new fasteners and/or hardware so handrails are securely attached.
    38) Gaps larger than four inches were found in one or more guardrails. This is a safety hazard, especially for small children. A qualified contractor should make modifications as necessary so gaps in guardrails do not exceed four inches. For example, installing additional balusters or railing components.
    39) Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains and/or efflorescence on the foundation or floor, water stains at bases of support posts, etc. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. The client(s) should review any disclosure statements available and ask the property owner(s) about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in the basement include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter the basement, but if water must be controlled after it enters the basement, then typical repairs include installing sump pump(s) or interior perimeter drains.

    Photo 24  
    Appliances in basement are supported on wood blocks. This shows signs of past water intrusion.
     

    40)

    Photo 28  
    Drain shows signs of past leak. It appears to be repaired, but should be monitored for further leakage.
     

    41)   One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    Photo 27  
    Non- GFCI within 6 ft of sink. This picture is in the basement, but this occurs in the kitchen and both bathrooms.
     
     
    Kitchen Return to table of contents

    42) One or more electric receptacles have reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
    43) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
    44)

    Photo 26  
    Bowing wall leading to basement. Shows signs of inadequate structural support. Recommend evaluation by structural engineer.
     
     
    Bathrooms Return to table of contents

    45) One or more wall-mounted electric switches are within reach of shower stalls. This is a safety hazard due to the risk of shock. At a minimum, the client(s) should be aware of the shock hazard this represents and never operate such switches while showering. Ideally, a qualified electrician should evaluate and move switches as necessary, or a qualified contractor should make modifications as necessary so wall switches are unreachable from shower stalls.
    46) One or more electric receptacles have reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
    47) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
     
    Interior rooms Return to table of contents

    48) One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

    Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.

    49) One or more electric receptacles have reverse-polarity wiring, where the hot and neutral wires are reversed. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.
    50) One or more doors swing outward over stairs without a landing area in front of the door. This a safety hazard, specifically in the case of someone tripping or falling when standing on the stairs and opening the door while someone else walks through the door as it is opened. A qualified contractor should evaluate and make repairs as necessary. For example, installing a door that opens in the other direction (away from the stairs).
    51) An insufficient number of smoke alarms are installed. Additional smoke alarms should be installed as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
    52) Minor cracks were found in walls in one or more areas. They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.

    Photo 29  
    Minor crack in hallway. Shows signs of settling and should be monitored for further spreading.
     

     
    Thank you for choosing Bowman Home Inspections. Feel free to contact me with any questions!