Bayside Inspections

Website: http://www.baysideinspections.com
Email: mark@baysideinspections.com
Phone: (727) 243-6764
FAX: (727) 848-1341
7881 Sycamore Dr 
New Port Richey FL 34654-5636
Inspector: Mark Hamm
CGC1514276

 

Property Inspection Report
Client(s): Sample Report
Property address: Lutz FL. 33559
Inspection date: Monday, January 25, 2010
This report published on 2/11/2010 1:10:39 PM EST

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Well
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Report number: 1103
Inspector's name: Mark S. Hamm
Structures inspected: 1
Type of building: Single family
Age of building: 2005
Property owner's name: N/A
Time started: 11:00 am
Time finished: 01:45 pm
Inspection Fee: $240.00
Payment method: Check
Present during inspection: Client(s), Realtor(s)
Occupied: Yes
Weather conditions: Partly cloudy
Temperature: Cool
Ground condition: Damp
Front of structure faces: East
Main entrance faces: East
Foundation type: Slab on grade
The following items are excluded from this inspection: Private sewage disposal system, Security system, Irrigation system, Private well, Low voltage outdoor lighting, Central vacuum system, Water filtration system, Water softener system, Built-in sound system, Intercom system, Outbuildings
1) Some wall, floor and/or ceiling surfaces were obscured by furniture and/or stored items. Some areas couldn't be evaluated.

Photo 28  

Photo 37  

Photo 44  

Photo 45  

2)   Real estate agent requested inspector to check for "chinese Drywall"
As this is a non invasive visual inspection only, i can only conclude my findings visually. they are as follows,
I did not find any evidence of corroding, or tarnished wires.
I did however find an inprint from the drywall manufacturer which was,
" National Gypsum " N.C.
This company is not known to have imported, purchased, manufactured, or distributed Tainted drywall.
The only way to be 100% sure is to have a sample sent to a lab for testing.

Photo 23  

Photo 24  
 
Exterior Return to table of contents
Footing material: Poured in place concrete
Foundation material: Poured in place concrete
Apparent wall structure: Wood frame, Concrete block
Wall covering: Stucco
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core steel
3) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit:
http://edis.ifas.ufl.edu/AE113

4) Cracks, deterioration and/or damage were found in one or more areas of the stucco siding. A qualified contractor should evaluate and make repairs and/or replace stucco siding as necessary.

Photo 7  
 

5) Water supply pipes are routed outside and are subject to freezing. The client(s) should ask the property owner(s) if inside shut-off valves exist for these supply pipes. If unable to determine if shut-off valve(s) exist, or if none do, then a qualified plumber should evaluate and install interior shut-off valves as necessary to prevent pipes from freezing and bursting.

Photo 2  
 

6) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.

Photo 9  
 

7) There are no gutters installed on home.
Recomend having gutters installed as this will help the flow of water away from the foundation of the home.

Photo 3  
Back of house

Photo 4  

8) Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.

Photo 12  
 
 
Roof Return to table of contents
Roof inspection method: Viewed from ground with binoculars
Roof type: Pyramidal
Roof covering: Asphalt or fiberglass composition shingles
Gutter & downspout material: None
Roof ventilation: Adequate
9) Because of the roof covering type and/or the configuration of the roof, the inspector was unable to traverse the roof and wasn't able to fully evaluate the entire roof.

Photo 5  
 

10)   Home is only 5 years old.
Roof appears to be in good condition.
 
Garage Return to table of contents

11) Appliances such as the water heater and/or furnace are subject to damage from vehicles because no protective barrier is installed in front of them. A qualified contractor should install an adequate barrier as per standard building practices (steel post anchored in concrete, wood partition, etc.).

Photo 14  
 

12) Did not have remote controls for garage vehicle doors.
 
Attic Return to table of contents
Inspection method: Viewed from hatch
Roof structure type: Trusses
Ceiling structure: Trusses
Insulation material: Cellulose loose fill
Insulation depth: 8"
Insulation estimated R value: 30
13)   Could not enter attic due to lack of space.
No visable problems.
Noted, use of O.S.B. 32/16 1/2" sheathing, roof trusses @ 24" O.C.
All look to be braced properly.

Photo 20  
Off ridge roof vent.

Photo 21  

Photo 22  
 
 
Electric service Return to table of contents
Primary service type: Underground
Primary service overload protection type: Circuit breakers
Service amperage (amps): 200
Service voltage (volts): 120/240
Location of main service switch: Panel box in garage
Location of main disconnect: No single main disconnect, use all breakers in main service panel
Service entrance conductor material: Aluminum
System ground: Ground rod(s) in soil
Main disconnect rating (amps): Not applicable, no single main disconnect
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: Can't verify
Smoke detectors present: Yes
14) All electrical appears to be in good working order.

Photo 6  

Photo 10  

Photo 15  

Photo 16  

Photo 17  
 
 
Water heater Return to table of contents
Estimated age: 2005
Type: Tank
Energy source: Electricity
Capacity (in gallons): 50
Manufacturer: Rheem
Model: Rheemglas Fury
Water temperature (degrees Fahrenheit): 100
 
Heating and cooling Return to table of contents
Estimated age: 2005
Primary heating system energy source: Electric
Primary heat system type: Heat pump
Primary A/C energy source: Electric
Primary Air conditioning type: Split system
Distribution system: Flexible ducts
Manufacturer: Tempstar
Model: smart comfort 2200
Filter location: In return air duct below furnace
Last service date: None listed recommend service.
15) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.

Photo 25  
disconnect

Photo 26  

Photo 34  
 

16) Dissconnects appear to be in good working order.

Photo 8  
 
 
Plumbing and laundry Return to table of contents
Water pressure (psi): 60
Location of main water shut-off valve: well pump
Location of main fuel shut-off: garage, (electric panel)
Water service: Private
Service pipe material: Not visible
Supply pipe material: Not visible
Vent pipe material: Plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
17) Recommend having the septic tank inspected. Recommend having the tank pumped if it was last pumped more than 3 years ago.
18) Neither the clothes washer nor dryer were operated or evaluated. They are excluded from this inspection.

Photo 27  
 
 
Well Return to table of contents
Location of well equipment: S.W. corner of lot
Location of tank shut off valve: Garage
 
Kitchen Return to table of contents

19)   Could not fully evaluate cabinets as they were still in use.

Photo 31  

Photo 32  

20)   Noticed an odor when running the kitchen island sink.
Recommend water test.

Photo 30  
 
 
Bathrooms Return to table of contents

21)   Ran all sinks, and flushed all toilets. no visible signs of problems.
Could not access all due to cabinets still in use.

Photo 38  

Photo 39  

Photo 41  

Photo 42  
restricted access.

Photo 43  
 
 
Interior rooms Return to table of contents

22)

Photo 29  

Photo 36  

Photo 40  
 

23)

Photo 29  

Photo 36  

Photo 40  
 
 

Photo 11  
Termit sticker on electric panel box. (standard)

Photo 13  
Water heater info.

Photo 18  
Corner of drywall broken. noted before inspector removed.

Photo 19  
Attic access in hall on 2nd floor.

Photo 33  
New return air filters.

Photo 35  
Upstairs hall bath

Photo 46  
Minor water damage noted at entry door.
 

 
Thank you for choosing "Bayside Inspections" for your home inspection.