At Home Superior Inspections LLC

Website: http://www.inspections-etc.com
Email: rw@inspections-etc.com
Phone: (352) 610-0027
1497 Main ST Suite 121 
Dunedin Fl 34698
Inspector: Rosemarie Werner

  

Property Inspection Report
Client(s): Sample Report
Property address: Spring Hill Fl 34608
Inspection date: 12/26/2011
This report published on Thursday, December 29, 2011 4:01:55 PM EST

View summary page

This report is the exclusive property of At Home Superior Inspections LLC and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Report number: Sample Report 122611
Inspector's name: Rosemarie Werner
Structures inspected: Residential
Type of building: Single family
Age of building: Approximately 15 Years
Property owner's name: Sample Report
Time started: 9:00am
Time finished: 12:00pm
Inspection Fee: N/A
Occupied: No
Weather conditions: Partly cloudy
Temperature: Cool
Ground condition: Damp
Front of structure faces: West
Main entrance faces: West
Foundation type: Slab on grade
The following items are excluded from this inspection: Security system, Irrigation system, Water softener system
1) Some wall, floor and/or ceiling surfaces were obscured by furniture and/or stored items. Some areas couldn't be evaluated.
 
Exterior Return to table of contents
Foundation material: Poured in place concrete
Footing material: Not visible
Apparent wall structure: Concrete block
Wall covering: Stucco
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core steel
2) One or more trip hazards were found in sidewalk and/or patio sections due to cracks, settlement and/or heaving. A qualified contractor should evaluate and repair or replace sidewalk and/or patio sections as necessary to eliminate trip hazards.

Photo 84  
 

3) Waterproof cover(s) over one or more electric receptacles are damaged or broken. This is a safety hazard due to the risk of shock and fire. Damaged covers should be replaced where necessary.

Front West and back East of house recepticles



Photo 100  

Photo 101  

4) One or more electric receptacles are broken or damaged. This is a safety hazard due to the risk of fire and shock. A qualified electrician should replace them as necessary.
5) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit:
http://edis.ifas.ufl.edu/AE113

Photo 59  
 

6) One or more hornet, bee and/or wasp nests were found. These can pose a safety hazard. Nest(s) should be removed as necessary.

Photo 98  
 

7) Weather striping is deteriorating or missing for the exterior doors on the patio/lanai. Recommend replacing to keep bugs/insects from gaining access into screened in area.

Photo 2  

Photo 3  

8) Patio/lanai screening is loose and/or deteriorating and should be repaired or replaced to keep animals from entering the patio/lanai area.

Photo 9  

Photo 10  

Photo 104  

Photo 105  

9) The perimeter grading slopes towards the structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure with a slope of at least 5% (10% or better is optimal) for at least 6 feet.


Photo 1  

Photo 97  

Photo 11  
 

10) One or more downspouts have no extensions, or have extensions that are ineffective. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms, and may also cause the foundation to settle and possibly fail over time. Repairs should be made as necessary, such as installing or repositioning splash blocks, or installing and/or repairing tie-ins to underground drain lines, so rain water is carried at least several feet away from the structure to soil that slopes down and away from the structure.

Photo 5  

Photo 6  

Photo 102  

Photo 103  

11) Caulk is missing or deteriorated in some areas and should be replaced and/or applied where necessary. For more information on caulking, visit:
The Ins and Outs of Caulking.

Photo 7  

Photo 8  

12) Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.

Photo 94  

Photo 95  

Photo 96  
 
 
Roof Return to table of contents
Estimated age of roof: 15 Years
Roof inspection method: Traversed
Roof type: Gable
Roof covering: Asphalt or fiberglass composition shingles
Gutter & downspout material: Aluminum
Roof ventilation: Adequate
13) The roof surface material appears to be near the end of its service life and will likely need replacing in the near future, even with repairs. The client(s) should budget for a replacement roof surface, and may want to have a qualified roofing contractor evaluate and attempt to issue a "5 year roof certificate".

Photo 17  
 

14) Gaps in the roof surface were found at one or more roof penetrations. These may result in leaks. A qualified roofing contractor should evaluate and repair as necessary.

Photo 14  
 

15) One or more composition shingles are damaged, deteriorated and/or missing, and should be replaced. Leaks may occur as a result. A qualified roofing contractor should evaluate and make repairs as necessary.

Photo 92  

Photo 93  

16) Roofing nails in one or more areas have loosened or backed out. Leaks may occur as a result. A qualified roofing contractor should evaluate and make repairs as necessary, such as reseating nails and applying sealant.

Photo 90  

Photo 91  

17) One or more roof ridge vents appear to have been dented and/or damaged. Roof ridge vents should be repaired/replaced by qualified roofer or general contractor.

Photo 89  

Photo 18  

18) One or more "rubber boot" flashings are lifting at the base or are improperly installed so that water or vermin intrusion may occur. A qualified contractor should make repairs as necessary, such as permanently fastening down the lifted edge(s), or reinstalling flashings.

Photo 12  

Photo 13  

Photo 19  
 

19) Debris has accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

Photo 16  

Photo 15  
 
Garage Return to table of contents

20) One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.

Photo 27  
 

21) The pull-down attic stairs in the attached garage ceiling aren't fire-rated. This ceiling should have a one-hour fire rating to slow or prevent the spread of fire from the attached garage to attic spaces above the living areas. A qualified contractor should evaluate and make modifications to these stairs as necessary so they have a one hour fire rating. Other options include removing them or replacing them with commercially made, fire-rated stairs. Examples of possible solutions include:

  • Installing 5/8 inch Type X sheetrock on the lower surface of the stair door and eliminating gaps around the edges of the door.
  • Removing the stairs and installing a traditional hatch made with 5/8 inch Type X sheetrock.
  • Installing a Battic Door and installing sheetrock over it as described at their website.
  • Replacing these stairs with fire-rated stairs such as those from:
    http://www.calvertusa.com/

    Photo 25  
     

    22) The weatherstrip around one or more exterior entry doors is missing and/or deteriorated. Weatherstrip should be installed where missing and/or replaced where deteriorated, and by a qualified contractor if necessary.

    Photo 24  

    Photo 26  

    23) Some of the interior perimeter of the garage is excluded from this inspection due to lack of access from stored items.

    Photo 23  
     
     
    Attic Return to table of contents
    Inspection method: Traversed
    Roof structure type: Trusses
    Insulation material: Fiberglass roll or batt
    Insulation estimated R value: R30
    24) Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.

    Photo 87  
     

    25) The ridge board which is the horizontal framing board at the peak of the roof which rafters are attached appears to be coming loose and should be evaluated and repaired by a qualified roofer.

    Photo 85  

    Photo 86  

    26) No light source was not found for the attic space above the main living areas. Recommend having a light installed by a qualified electrician.
    27) Ceiling insulation is missing in some areas. Recommend installing insulation where missing for better energy efficiency.

    Photo 75  
     

    28) Pull-down stairs are installed for the attic access. No insulation is installed above the stairs and no weatherstripping is installed around the hatch perimeter. To reduce air leakage, recommend installing weatherstripping and an insulated hatch cover. An example of one can be seen at http://www.batticdoor.com/

    Interior air leaking into the attic results in heating and cooling losses, increased energy costs, and a possible increase in moisture levels in the attic due condensation forming on the underside of the roof sheathing during cold weather.

    Photo 83  
     

    29)   One or more 2 x 4 are not property attached. The 2 x 4 should be attached with nails the entire length of the rafter. A qualified roofer/general contractor should be contacted to evaluate/repair.

    Photo 78  
     
     
    Electric service Return to table of contents
    Smoke detectors present: Yes
    Primary service type: Underground
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120/240
    Location of main service switch: Garage
    Location of main disconnect: Breaker at bottom of main service panel
    Service entrance conductor material: Aluminum
    System ground: Cold water supply pipes
    Main disconnect rating (amps): 200
    Branch circuit wiring type: Non-metallic sheathed
    Solid strand aluminum branch circuit wiring present: No
    30) The main service panel cover is installed so it is not flush with the surface of the panel box and disconnect devices. Gaps exist, resulting in exposed wiring. This is a safety hazard due to the risk of shock. A qualified contractor and/or electrician should evaluate and repair so the panel cover fits on the panel box as the manufacturer intended.

    Photo 32  

    Photo 33  

    31) One or more clamps that secure the electric service's grounding electrode and/or bonding conductor(s) to pipe(s) are rusted or corroded. Grounding and/or bonding may be inadequate as a result and may be a safety hazard for shock. A qualified electrician should evaluate and repair as necessary.

    Photo 34  
     

    32) The service panel door does not close properly and the latch appears to be broken. Have qualified electrician repair or replace.

    Photo 29  

    Photo 30  

    33) The legend for overcurrent protection devices (breakers or fuses) in the main service panel is missing, unreadable or incomplete. Recommend installing, updating or correcting the legend as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.

    Photo 28  

    Photo 31  
     
    Water heater Return to table of contents
    Estimated age: 15 Years
    Type: Tank
    Energy source: Electricity
    Capacity (in gallons): 50
    Manufacturer: Rudd
    Model: PES52-2C
    Water temperature (degrees Fahrenheit): Approx 130 degrees
    34) The hot water temperature is greater than 120 degrees Fahrenheit. This is a safety hazard due to the risk of scalding. The thermostat should be adjusted so the water temperature doesn't exceed 120 degrees. For more information on scalding dangers, visit:
    http://www.cpsc.gov/cpscpub/pubs/5098.html

    Photo 36  

    Photo 37  

    35) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age or older and may need replacing at any time, signs of rust were on the top. Recommend budgeting for a replacement in the near future.

    Photo 35  
     

    36) Corrosion was found in one or more areas on the water heater. A qualified plumbing contractor should evaluate and replace water heater if necessary.

    Photo 99  
     

    37) Corrosion was found on fittings and/or water supply lines for the water heater. Leaks may exist. A qualified plumbing contractor should evaluate and repair as necessary.

    Photo 38  
     
     
    Heating and cooling Return to table of contents
    Estimated age: 15 Years
    Primary heating system energy source: Electric
    Primary heat system type: Heat pump
    Primary A/C energy source: Electric
    Primary Air conditioning type: Heat pump
    Distribution system: Flexible ducts
    Manufacturer: Trane
    Model: TWR048C100A3
    38) Exterior disconnect switch was not accessible for the outside condensing unit. These should be accessible to prevent the condensing unit from responding to the thermostat off-season, or during maintenance. A qualified heating and cooling contractor should evaluate and repair as necessary.

    Photo 41  
     

    39) The estimated useful life for most heat pumps is 15 to 20 years. This heat pump appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.

    Photo 39  

    Photo 42  

    40) Insulation for the outside condensing unit's refrigerant lines is damaged, deteriorated and/or missing in one or more areas. This may result in reduced efficiency and increased energy costs. A qualified heating and cooling contractor should replace insulation as necessary.

    Photo 40  

    Photo 43  

    41) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.
    42) Filter(s) are dirty and should be washed now. They should be checked monthly in the future and washed as necessary.

    Photo 44  

    Photo 74  

    43) The outdoor air temperature was below 60 degrees Fahrenheit during the inspection. Because of this, the inspector was unable to operate and fully evaluate the cooling system.
     
    Plumbing and laundry Return to table of contents
    Water pressure (psi): 80 psi
    Location of main water shut-off valve: Outside Garage North Side
    Water service: Public
    Service pipe material: Not visible
    Supply pipe material: Copper
    Vent pipe material: Plastic
    44) The clothes dryer exhaust duct appears to need cleaning. Significant amounts of lint build up was found. This is a safety hazard due to the risk of fire from decreased air flow. This duct should be cleaned now and annually, or more often if necessary in the future. Some chimney sweeps or heating/cooling duct cleaners perform this service. For more information, visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5022.html
    http://chimneykeepers.com/dryerclean.html

    Photo 79  

    Photo 80  
     
    Kitchen Return to table of contents

    45) Tile, stone and/or grout flooring is damaged and/or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary. For example, replacing broken tiles and deteriorated grout, and resealing grout.

    Photo 63  

    Photo 64  

    46) One or more cabinet edges are damaged and/or deteriorated. A qualified contractor should evaluate and repair or replace cabinets as necessary.

    Photo 67  

    Photo 68  

    47) The range hood fan vents into the kitchen rather than outdoors. Ventilation may be inadequate and moisture may accumulate indoors. Recommend having a qualified contractor make modifications as necessary as per standard building practices so the range hood fan vents outdoors.
    48) The oven and/or broiler door handle(s) are loose and/or missing. Repairs should be made as necessary, and by a qualified appliance technician if necessary, such as tightening or replacing handles.

    Photo 66  
     

    49) Hardware such as hinges, latches or pulls are loose and/or missing on one or more cabinets. Repairs should be made and/or hardware should be replaced as necessary, and by a qualified contractor if necessary.

    Photo 65  
     

    50) Caulk is missing and/or deteriorated where countertops meet backsplashes in wet areas, such as around sinks. Caulk should be replaced where deteriorated and/or applied where missing to prevent water damage.

    Photo 69  
     

    51) One or more kitchen appliances appear to be near, at, or beyond their intended service life of 10 to 15 years. Recommend budgeting for replacements as necessary.

    Photo 62  
     

    52) The microwave oven does not have a built in turntable. The client(s) may want to purchase a manually wound turntable such as a "Micro-go-round" for better cooking performance. For more information, visit:
    http://www.google.com/search?q=micro-go-round
     
    Bathrooms Return to table of contents

    53) Tile and/or grout in one or more showers is damaged and/or deteriorated. For example, deteriorated or missing grout, cracked, missing or loose tiles, etc. A qualified contractor should evaluate and repair tile and/or grout as necessary.

    Photo 54  

    Photo 55  

    Photo 71  

    Photo 72  

    Photo 73  
     

    54) One or more sinks are clogged or drain slowly. Drain(s) should be cleared as necessary, and by a qualified plumber if necessary.
    55) One or more toilet tank handles are cracked or broken. Handle(s) should be replaced as necessary.

    Photo 70  
     

    56) Hardware such as hinges, latches or pulls are loose and/or missing on one or more cabinets or shower doors. Repairs should be made and/or hardware should be replaced as necessary, and by a qualified contractor if necessary.

    Photo 52  

    Photo 53  

    Photo 50  
     

    57) Water damage was found in the shelving or cabinet components below one or more sinks. A qualified contractor should evaluate and make repairs as necessary.

    Photo 51  

    Photo 57  

    58) Caulk is missing or deteriorated along the base of one or more showers, where flooring meets the shower. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the floor structure.

    Photo 56  
     
     
    Interior rooms Return to table of contents

    59) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
    http://www.google.com/search?q=old+smoke+alarms

    60) One or more sliding glass doors are difficult to open or close. A qualified contractor should evaluate and repair or replace door(s) as necessary.

    Photo 60  

    Photo 61  

    61) The lock mechanisms on one or more sliding glass doors are inoperable and/or difficult to operate. A qualified contractor should evaluate and repair as necessary.

    Photo 58  
     

    62) The handle(s) on one or more sliding glass doors are loose and/or missing. Repairs should be made and/or handles replaced as necessary, and by a qualified contractor if necessary.
    63) Carpeting in one or more rooms is damaged and/or significantly deteriorated. Recommend replacing carpeting where necessary.

    Photo 45  

    Photo 46  

    64) Fixtures such as door stops, towel bars and/or toilet paper holders are damaged and/or deteriorated in one or more areas. Recommend having a qualified contractor replace or repair fixtures as necessary.

    Photo 48  

    Photo 49  

    65) Drywall is damaged and/or deteriorated in one or more areas. Recommend having qualified contractor replace or repair drywall as neccessary.

    Photo 47  
     
     

    Photo 20  

    Photo 22  

    Photo 76  

    Photo 77  

    Photo 81  

    Photo 82  

     
    It is important that you carefully read ALL of the information in your inspection report upon receipt. This inspection has been performed and this report prepared in accordance with the standards of practice for home inspections.
    • A home inspection is intended to assist in the evaluation of the overall condition of the dwelling. The inspection is based on observations of the visible and apparent condition of the structure and its components on the date of the inspection, and not the prediction of future conditions. 

    • A home inspection will not reveal every concern that exists or ever could exist, but only those material defects observed on the day of the inspection.

    A complete Standards of Practice can be found at
    http://www.nachi.org/sop.htm