Inspector: Richard Caputo

 

Sample of real report
Client(s): Mr. Anywho
Property address: Any Street
Greenwood, FL
32443
Inspection date: 2/10/08, 2008
This report published on 5/3/2008 2:36:45 PM CDT

View summary page

This report is the exclusive property of Assurance Home Inspection Group, LLC and the client(s) listed in the report title.
Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Structural Pest Inspection Concerns
Items of concern relating to the structural pest inspection are shown as follows:
WDO/WDI InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
WDO/WDI DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
WDO/WDI Conducive
conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Carport
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Crawl space
Kitchen
Bathrooms
Interior rooms
Electric service
 
General information Return to table of contents
Report number: Anywho 2/10/08
Structures inspected: house and outbuilding
Type of building: Single family
Age of building: 1950
Property owner's name: Anywho
Time started: 10:45 AM
Time finished: 3:00 PM
Inspection Fee: 550.00
Payment method: Cash
Present during inspection: Owner's agent
Occupied: No
Weather conditions: Overcast and rainy
Temperature: Cool, Wet, Very wet.
Ground condition: Very wet.
Front of structure faces: North
Main entrance faces: North
Foundation type: Crawlspace, Post and pier in center of floor joists with CBC footers supporting ends of beams.
The following items are excluded from this inspection: Private sewage disposal system, Security system, Irrigation system, Swimming pool, Hot tub, Private well, Shed, Playground equipment, Sauna, Low voltage outdoor lighting, Central vacuum system, Water filtration system, Water softener system, Built-in sound system, Intercom system, Generator system, Sport court, Sea wall, Outbuildings


1)   There is some old style cloth covered wiring still in use in this home, while this was standard when home was built, it is outdated and a safety concern by today's standards. Modern electrical wiring is a three wire grounded system. There is no evidence of proper grounding of the receptacles in this system. All receptacles should be replaced with 3 wire grounded receptacles and those near wet locations (kitchen, bathrooms and outdoors) should be of Ground Fault Interrupter type or GFCI.
2)   There is a "PushMatic" breaker box in the hall closet that also houses the 2nd air handler and 2nd water heater that contains old and unusual breakers. Unable to assess safety of these items as this location was wet during inspection.
PushMatic breakers have been plagued with problems and we highly recommend having a qualified electrician look at this.

3)   While no asbestos or lead was noted during the inspection you should be aware of the following. Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:
  • The Environmental Protection Association (http://www.epa.gov)
  • The Consumer Products Safety Commission (http://www.cpsc.gov)
  • The Center for Disease Control (http://www.cdc.gov)
    4) The 'moat' at entry to home on N side is a major drainage problem because it drains under the house via crawlspace vents. This area actually funnels runoff from roof and driveway directly under home and is a major issue. As the continually wet conditions under the home serve as producers of mold and mildew and are conducive to pest problems.
     
    Exterior Return to table of contents
    Footing material: Masonry, CBC footings, not able to see base of footings.
    Foundation material: Post and pier, CBC piers across center of house support beams under floor joists.
    Apparent wall structure: Wood frame, Concrete block. Wood frame on original house and CBC walls on first floor.
    Wall covering: Wood panels, Brick veneer. Primarily wood panel siding with some brick veneer on addition.
    Driveway material: Asphalt. Noted numerous cracks and humps and some holes in pavement.
    Sidewalk material: None
    Exterior door material: Hollow core wood. Should be replaced at kitchen entry door from carport with steel door for fire rating.
    5)   The driveway has significant cracks and/or deterioration in one or more areas. A qualified contractor should evaluate and repair or replace driveway sections as necessary.

    Photo 15  
    Driveway, carport slab, tripping hazard, safety issue
     

    6)   One or more trip hazards were found in the driveway due to cracks, settlement and/or heaving. Recommend having a qualified contractor evaluate and repair or replace driveway sections as necessary to eliminate trip hazards.
    7)   One or more large trees on the property may be likely to fall on the structure, and are a potential safety hazard. Recommend consulting with a qualified arborist to determine if tree(s) need to be removed and/or pruned.
    8)   One or more electric receptacles and/or the boxes they are installed in are loose and/or not securely anchored or placed or wired correctly. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.

    Photo 9  
    Electrical safety issue, "head out" towards outbuilding
     

    9)   One or more light fixtures are loose or installed in a substandard way. A qualified contractor or electrician should evaluate and make repairs as necessary so light fixtures are securely mounted and installed in accordance with the manufacturer's installation instructions.
    The light fixture with fan and heater in bathroom is not vented and is a safety hazard.

    10)   One or more light fixtures located in "wet" or "damp" locations have no visible rating for use in wet locations. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and replace light fixtures as necessary and as per standard building practices.
    11)   One or more sections of wiring that weren't terminated were found. This is a potential safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary. For example, cutting the wire to length and terminating the wire with wire nuts in a securely anchored, covered, properly sized junction box.
    Some loose wires found in crawlspace which may or may not be hot.

    12)   Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.
    13)   One or more plumbing vent pipes terminate less than 10 feet horizontally from a window or door that opens. This is a safety hazard due to the risk of sewer gases entering the structure. A qualified contractor should make repairs as necessary so vent pipes terminate at least 10 feet horizontally from openings into living spaces, but preferably above the roof surface.
    14)   Waterproof cover(s) over one or more electric receptacles are damaged or broken. This is a safety hazard due to the risk of shock and fire. Damaged covers should be replaced where necessary.
    15)   Cover plate(s) are broken at one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be replaced where necessary.
    16)   One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

    Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079

    17) The perimeter grading slopes towards the structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Wet soil may also cause the foundation to settle and possibly fail over time. Recommend grading soil so it slopes down and away from the structure with a slope of at least 5% (10% or better is optimal) for at least 6 feet.
    This house would require extensive grading to correct drainage problems.

    Photo 11  
    Negative slope toward wall, East side of home

    Photo 13  
    West end of home with negative slope towards wall, drainage problem

    Photo 78  
     

    18)   Rot was found at one or more rafter and/or barge board ends supporting the deck.. A qualified contractor should evaluate and make repairs as necessary, replacing or removing rotten wood.
    Several of the support beam ends have rot beneath the deck.
    Unable to assess all roof support beams without removing metal end caps.
    Gaps larger than four inches were found in one or more guardrails. This is a safety hazard, especially for small children. Railing on deck has balusters space too far apart.
    A qualified contractor should make modifications as necessary so gaps in guardrails do not exceed four inches. For example, installing additional balusters or railing components.

    Photo 50  
    De-lamination and rot.

    Photo 51  
    De-lamination and rot.

    19)   One or more crawl space vents are below or near grade with inadequate wells. This can lead to water entering and accumulating in the crawl space, and is a conducive condition for wood destroying insects and organisms. A qualified contractor should replace and/or repair wells where necessary.
    The moat at entry side drains through crawlspace vents and creates ponding and runoff erosion beneath the house. This is a serious problem and will cause foundation failure and continual wood rot in floor supports.

    Photo 77  

    Photo 78  

    20)   Fascia boards are damaged or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary.
    21)   One or more landscaping timbers are rotten or damaged by wood destroying insects. Landscaping timbers should be replaced as necessary.
    22)   Siding is damaged and/or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs and/or replace siding as necessary to prevent water and vermin intrusion.
    23)   Rot was found in one or more areas on soffit boards. A qualified contractor should evaluate and make repairs as necessary, replacing all rotten wood.
    24)   One or more outside faucets appeared to be inoperable. No water came out of the faucet(s) when turned on. This may be due to a (winterizing) shut-off valve being turned off. As per the NACHI and ASHI Standards of Practice, the inspector did not attempt to turn on or off any water supply shut-off valves. Recommend that the client(s) ask the seller about outside faucets with no water, and/or have a qualified plumber evaluate and repair faucet(s) as necessary.
    25)   Water supply pipes are routed outside and are subject to freezing. The client(s) should ask the property owner(s) if inside shut-off valves exist for these supply pipes. If unable to determine if shut-off valve(s) exist, or if none do, then a qualified plumber should evaluate and install interior shut-off valves as necessary to prevent pipes from freezing and bursting.

    Photo 17  
    PVC piping needs metal attachment fitting, balusters overspaced, safety issue for children
     

    26)   One or more large trees are very close the foundation. Tree roots can cause significant structural damage to foundations. Recommend having a qualified tree service contractor or arborist remove trees as necessary to prevent damage to the structure's foundation.
    Tree roots are beneath the footings and cause some heaving in driveway.

    Photo 2  
    Service head too close to roof, safety issue

    Photo 5  
    Overhanging tree

    Photo 7  
    Too many trees next to home or more maintenance needed
     

    27)   One or more large tree stumps are close to the structure's exterior. Wood destroying insects such as carpenter ants nest in such stumps and are more likely to infest the structure as a result. Recommend having large tree stumps within a few feet from the structure removed, by a qualified tree service contractor if necessary.
    28)   Perimeter pavement slopes towards structure in one or more areas. This can result in water accumulating around the structure's foundation, or in basements and crawl spaces if they exist. Accumulated water is a conducive condition to wood destroying insects and organisms. Recommend having a qualified contractor make repairs as necessary so perimeter pavement slopes down and away from the structure.

    Photo 53  
    Wet debris at threshold, back door. Indicating water at threshold.

    Photo 54  
    Slight negative slope towards back door

    29)   One or more outside faucets aren't anchored securely to the structure's exterior. Fasteners should be installed or replaced as necessary so faucets are securely anchored to prevent stress on plumbing supply lines and possible leaks.
    Faucet on deck should have metal portion fastened to rail.

    Photo 17  
    PVC piping needs metal attachment fitting, balusters overspaced, safety issue for children
     

    30)   Trees and/or shrubs are in contact with or are close to the roof edge(s) in one or more areas. Damage to the roof may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.
    Vegetation is in contact with fascia and will cause damage. Overhanging limbs may fall and penetrate roof. Debris accumulates on roof from trees.

    Photo 5  
    Overhanging tree

    Photo 6  
    Overhanging touching tree

    31)   Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.
    Vines have been growing up walls, causing cosmetic damage.
    Shrubs are too close to structure.

    32)   Minor cracks and/or deterioration were found in one or more retaining walls. Recommend repairing cracks with mortar, elastomeric sealant, or other suitable material to prevent water intrusion and further deterioration. The client(s) should monitor such walls in the future for continued deterioration (cracking, leaning, bowing, etc.). Repairs and/or replacement by a qualified contractor may be necessary in the future.
    33)   Minor cracks were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
    34)   Recommend cleaning deck(s) and railing(s) and treating with a preservative claiming to waterproof, block ultraviolet light, and stop mildew. Consumer Reports recommends these products:

  • Cabot Decking Stain and PTW Stain
  • Olympic Water Repellent Deck Stain
  • Thompson's House and Deck Stain
  • Wolman PTW Deck Stain
  • Akzo Sikkens Cetol DEK
  • Benjamin Moore Moorwood Clear Wood Finish
  • DAP Woodlife Premium
  • Olympic Natural Look Protector Plus
    35)   The finish on the deck(s) is worn and/or deteriorated. Recommend cleaning and refinishing as necessary.
    36)   The exterior finish in some areas is failing. A qualified contractor should prep (pressure wash, scrape, sand, prime caulk, etc.) and repaint or restain areas as needed and as per standard building practices.
    Minor rot noted at low end of siding.

    37)   One or more light fixtures appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.
    38)   One or more sections of foundation and/or exterior walls are excluded from this inspection due to lack of access from vegetation, debris and/or stored items.
    The foundation includes a moat on the N side of house which presents several hazards. The moat is 2 feet deep and presents a falls hazard. The walkways over the moat have no railings. The walkways over the moat are of wood and need repair. The moat presents a drainage problem under the house and diverts water under the foundation causing wash outs.
    Cost estimate: $ 3000.00

    39)   One or more sections of retaining walls are excluded from this inspection due to lack of access from vegetation, debris and/or stored items.
    The retaining wall part of the moat has at least one crack in it.
     
    Roof Return to table of contents
    Roof inspection method: Traversed
    Roof type: Flat
    Roof covering: Rolled
    Estimated age of roof: 7 yr
    Gutter & downspout material: None
    Roof ventilation: Inadequate, soffit not ventilated. No access to roof interior. No roof insulation noted.
    40)   One or more plumbing vent pipes terminate less than six inches above the roof surface below. Debris or snow may block openings, and may result in sewer gases entering living spaces. A qualified contractor should evaluate and make repairs as necessary so vent pipes terminate at least six inches above roof surfaces.
    41)   The roof surface material appears to be near the end of its service life and will likely need replacing in the near future, even with repairs. The client(s) should budget for a replacement roof surface, and may want to have a qualified roofing contractor evaluate and attempt to issue a "5 year roof certificate".
    42)   Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.

    Photo 2  
    Service head too close to roof, safety issue

    Photo 7  
    Too many trees next to home or more maintenance needed

    43)   Gaps were found in one or more roof surface seams. These may result in leaks. A qualified roofing contractor should evaluate and repair as necessary.

    Photo 4  
    At least one spot where roofing not sealed
     

    44)   One or more chimneys are wider than two feet and no cricket is installed. A cricket is a small peaked saddle on top of the basic roof and behind the chimney that sheds water off to the sides. Debris such as leaves, needles, moss, etc. is likely to accumulate above the chimney because of the wide chimney. Leaks may occur as a result. The client(s) should monitor this area for accumulated debris in the future. If debris is found to accumulate above the chimney, then a qualified contractor should install a cricket.
    45)   Debris such as leaves, needles, seeds, etc. have accumulated on the roof. This is a conducive condition for wood destroying insects and organisms since water may not flow easily off the roof, and may enter gaps in the roof surface. Leaks may occur as a result. Debris should be cleaned from the roof now and as necessary in the future.
    See Pictures in 42.

    46)   Trees and/or shrubs are in contact with or are close to the roof edge(s) in one or more areas. Damage to the roof may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.
    See Pictures in 42.

    47)   The roof was partially obscured by accumulated debris and couldn't be fully evaluated.
    See Pictures in lines 42, 43.
     
    Carport Return to table of contents
    :
    48)   One or more sections of wiring that weren't terminated were found. This is a potential safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary. For example, cutting the wire to length and terminating the wire with wire nuts in a securely anchored, covered, properly sized junction box.
    49)   Wire splices are exposed due to not being contained in a covered junction box. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and make repairs as necessary. For example, install securely mounted junction boxes with cover plates where needed to contain wiring splices.
    50)   Some wiring is loose, unsupported, or inadequately supported. Standard building practices require non-metallic sheathed wiring to be trimmed to length, attached to runners or to solid backing with fasteners at intervals of 4-1/2 ft. or less. Fasteners should be installed within 12 inches of all enclosures. A qualified, licensed electrician should evaluate and repair as necessary. For example, trim wire to length and/or install staples as needed.
    51)   One or more exterior entrance doors are of hollow-core construction rather than solid core. This may represent a security hazard since these doors are easily broken. Hollow-core, exterior entrance doors should be replaced with solid core doors by a qualified contractor.
    52)   Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.
     
    Water heater Return to table of contents
    Estimated age: 8 years
    Type: Tank
    Energy source: Electricity
    Capacity (in gallons): 40, 52
    Manufacturer: A.O. Smith
    53)   Substandard wiring was found for the water heater #2 power supply. Exposed non-metallic sheathed (Romex) wiring is used and is subject to damage. Both the insulation and conductors can be damaged by repeated movement or contact with objects such as stored items. This is a safety hazard for both fire and shock. A qualified electrician should evaluate and repair as necessary. Typically, flexible conduit with bushings is used in this application.
    Wiring to water heater in hall closet is not secured or closed into box.

    Photo 44  
    2nd water heater in hall, water on floor, 240 electric also on floor. This is a safety issue. Electrician should replace and repair.
     

    54)   No drain line is installed for the temperature-pressure relief valve, water heater #1. This is a potential safety hazard due to the risk of scalding if someone is standing next to the water heater when the valve opens. A qualified plumber should install a drain line as per standard building practices. For example, extending to 6 inches from the floor, or routed so as to drain outside.

    Photo 34  
    Pressure relief valve not piped, lower level, safety issue.
     

    55)   The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
    56)   The water heater was turned off at the time of the inspection. For example, circuit breaker turned off, gas supply turned off or pilot light turned off. The inspector was unable to fully evaluate the water heater.
     
    Heating and cooling Return to table of contents
    Estimated age: 7 yr
    Primary heating system energy source: Electric
    Primary heat system type: Heat pump
    Primary A/C energy source: Electric
    Primary Air conditioning type: Split system, Heat pump
    Distribution system: Sheet metal ducts
    Manufacturer: American Standard
    57) Significant amounts of what appears to be mold is visible in one or more sections of supply and/or return air ducts. If it is mold, it can be a health hazard, especially for those with allergies or respiratory problems. The Environmental Protection Association (EPA) recommends considering having ducts professionally cleaned when "there is substantial visible mold growth inside hard surface (e.g., sheet metal) ducts or on other components of your heating and cooling system". The client may wish to have a qualified industrial hygienist or indoor air quality specialist evaluate the ducts and/or have a qualified contractor clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit: http://www.epa.gov/iaq/pubs/airduct.html

    Photo 41  
    The ductwork for this register was lying in water in crawl space at the time of inspection, water has penetrated the ductwork and has been blowing moisture laden air in for some time. Area is moist and moldy.

    Photo 74  
    Ponding in crawl space. Note submerged objects.

    58) One or more heating/cooling ducts are lying on the ground. Ducts should be supported (typically with straps or hangers) so that they are not in contact with the ground and subject to damage from moisture. A qualified contractor should evaluate and make repairs as necessary so ducts are suspended as per standard building practices, and not in contact with the ground.
    Water in crawl space is soaking insulation on ductwork and causing mold problem in bedroom above it.

    59)   Insulation is missing on one or more heating/cooling ducts in unconditioned spaces. A qualified contractor should evaluate and install insulation as necessary and as per standard building practices.
    Poor duct insulation in crawlspace.

    60)   The outdoor air temperature was below 60 degrees Fahrenheit during the inspection. Because of this, the inspector was unable to operate and fully evaluate the heating/cooling system.
     
    Plumbing and laundry Return to table of contents
    Water service: Public
    Service pipe material: Galvanized steel
    Supply pipe material: Copper, Galvanized steel, CPVC
    Vent pipe material: Plastic
    Drain pipe material: Cast ironNoted minor leaks in drain and waste pipes in crawlspace.
    Waste pipe material: Cast iron
    61)   Copper water supply pipes in homes built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client(s) should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client(s) should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:

  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than six hours.
  • Install appropriate filters at points of use.
  • Use only cold water for cooking and drinking. Hot water dissolves lead more quickly than cold water.
  • Use bottled or distilled water.
  • Treat well water to make it less corrosive.
  • Have a qualified plumbing contractor replace supply pipes and/or plumbing components as necessary.

    For more information visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
    http://www.epa.gov/safewater/lead/index.html
    62)   Some, most, or all of the water supply pipes in this structure are made of galvanized steel. Based on the age of this structure, these pipes may be nearing or may have exceeded their estimated useful life of 40 to 60 years. Internal corrosion and rust can reduce the inside diameter of these pipes over time, resulting in reduced flow and eventually, leaks. The inspector performed a "functional flow test" during the inspection where multiple fixtures were run simultaneously, and found the flow to be adequate. For example, the shower flow didn't decrease substantially when the toilet was flushed. Despite this, and because of their apparent age, these pipes may need replacing at any time.
    63)   Galvanic corrosion observed at several locations.
    Galvanic corrosion
    Is an electrochemical process in which one metal corrodes preferentially when it is in contact with a different type of metal and both metals are in an electrolyte (water). When two or more different sorts of metal come into contact in the presence of an electrolyte a galvanic couple is set up as different metals have different electrode potentials. The electrolyte provides a means for ion migration whereby metallic ions can move from the anode to the cathode. This leads to the anodic metal corroding more quickly than it otherwise would; the corrosion of the cathodic metal is retarded even to the point of stopping. The presence of electrolyte and a conducting path between the metals may cause corrosion where otherwise neither metal alone would have corroded.

    Photo 31  
    Bathroom, main, leaking and corroded. One of several areas observed.
     

    64)   One or more active leaks were found in drain and/or waste pipes or fittings. A qualified plumber should evaluate and repair as necessary.
    65)   Stains were found in one or more sections of drain and/or waste pipes. Recommend monitoring these areas in the future, and if leaks are found, have a qualified plumber evaluate and repair as necessary. Alternatively, the client(s) may wish to have a qualified plumber evaluate now and repair if necessary.
    Lower level bath has apparent leak causing stains in carpet outside bath.
     
    Fireplaces, woodstoves and chimneys Return to table of contents
    Fireplace type: Masonry
    Chimney type: Masonry
    66)   One or more wood burning appliances such as fireplaces or woodstoves use an unlined masonry chimney for a flue. Standard building practices require that liners, such as terracotta flue tiles, be installed in masonry chimneys used for venting wood burning appliances. Exhaust gases may seep through gaps in masonry without a liner. This is a safety hazard. A qualified chimney service contractor should evaluate and make repairs as necessary.

    Photo 19  
    Fireplace has no smoke shelf or throat, unlined, straight flue, no hearth dining room side, safety issue.

    Photo 26  
    Water puddle and drip, fireplace, lower.

    67)   One or more chimney flue openings do not have a screen installed. Screens prevent the following:

  • Fire hazard from wood fire sparks and embers exiting flues
  • Wildlife (birds, rodents, raccoons, etc.) entering flues

    A qualified chimney service contractor should install screening where missing. Screens should have holes 1/4 inch or larger.

    Photo 62  
    Unlined flue in chimney.

    Photo 63  
    Damper open, trash fell in, no screen at top.

    68)   This fireplace is not properly set up for wood or gas logs and should not be used until converted by a qualified contractor.
    69)   No damper is visible in one or more fireplaces. This can result in increased energy costs due to unconditioned air entering living spaces, or due to conditioned air exiting living spaces through the chimney. A qualified chimney service contractor should evaluate and make modifications as necessary, such as installing a closeable damper.
    70)   One or more chimney flues do not have a rainproof cover installed. They prevent the following:

  • Rainwater entering flues and mixing with combustion deposits, creating caustic chemicals which can corrode flues and/or masonry.

    A qualified chimney service contractor should install rainproof cover(s) where missing.
    Rain cap is rusted out.

    Photo 26  
    Water puddle and drip, fireplace, lower.

    Photo 28  
    Chimney cap rusted out
     
    Crawl space Return to table of contents
    Inspection method: Could not enter crawlspace due to electrical wires lying in water posing a significant safety hazard.
    Insulation material underneath floor above: None visible
    Pier or support post material: Masonry
    Beam material: Solid wood
    Floor structure above: Solid wood joists
    Vapor barrier present: No
    71)   One or more floor joists are undersized for their span. Sagging and/or bouncing floors may result. In extreme circumstances, floors may collapse. A qualified contractor should evaluate and make repairs as necessary.
    *Indications from upper bedroom is one or more joists are either rotted, totally disconnected from floor or missing. Immediate attention to floor joists highly recommended. This area not inspected due to the water and observed electric wires lying in water. Suggest qualified contractor evaluate immediately.

    72)   One or more pier or foundation footings are undermined, where soil has either eroded out from underneath, or has been excavated too close to the footing. Structural engineers typically require undisturbed soil to extend at least a foot horizontally out from the edge of footings, and then slope down no more steeply than 45 degrees. Otherwise soil may collapse from beneath the footing(s). A qualified structural engineer should evaluate and determine what repairs if any should be made. If repairs are prescribed, then a qualified contractor should perform them in accordance with the engineer's recommendations.
    Water from moat runs under footings and washes out supports.

    73)   Standing water was found in one or more sections of the crawl space. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the crawl space. A qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in crawl spaces include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter crawl spaces, but if water must be controlled after it enters the crawl space, then typical repairs include installing trenches, drains and/or sump pump(s) in the crawl space.

    Photo 12  
    220/240 wire laying in wet crawl space, safety issue

    Photo 68  
    240 volt line lying in water, safety issue.

    Photo 71  
    Ponded water to the left of crawl space entrance. Note water pipe lying in water. This could be a safety issue due to cross connection.

    Photo 72  
    Ponded water to the right of crawl space entrance. Note submerged objects.

    Photo 73  
    Opposite wall, toward front of home, uncovered soil.

    Photo 74  
    Ponding in crawl space. Note submerged objects.

    74)   No insulation is installed under the floor in the crawl space. Recommend that a qualified contractor install R19 or better (6" thick fiberglass batt) insulation under the floor for better energy efficiency.

    Photo 66  
    Plastic crawl space covering stops short of piers, typical both sides.
     

    75)   The crawl space ventilation is substandard, or none exists. This may result in high levels of moisture in the crawl space and can be a conducive condition for wood destroying insects and organisms. Standard building practices require one square foot of vent area for 150 to 200 square feet of crawl space. Vents should be evenly distributed and within a few feet of corners to promote air circulation. A qualified contractor should evaluate and install vents as per standard building practices.
    76)   The vapor barrier needs repair. Exposed soil was found in some areas. This is a conducive condition for wood destroying insects and organisms due to the likelihood of water evaporating into the structure from the soil. A qualified contractor should make repairs as necessary so no exposed soil exists. Standard building practices require the following:

  • The soil below the vapor barrier should be smooth and free from sharp objects.
  • Seams should overlap a minimum of 12 inches.
  • The vapor barrier should lap up onto the foundation side walls.

    Better building practices require that:

  • Seams and protrusions should be sealed with a pressure sensitive tape.
  • The vapor barrier should be caulked and attached tightly to the foundation side walls. For example, with furring strips and masonry nails.

    Photo 73  
    Opposite wall, toward front of home, uncovered soil.
     

    77)   No vapor barrier is installed in some areas. This is a conducive condition for wood destroying insects and organisms due to the likelihood of water evaporating into the structure from the soil. A qualified contractor should install a vapor barrier where missing. Standard building practices require the following:

  • The soil below the vapor barrier should be smooth and free from sharp objects.
  • Seams should overlap a minimum of 12 inches.
  • The vapor barrier should lap up onto the foundation side walls.

    Better building practices require that:

  • Seams and protrusions should be sealed with a pressure sensitive tape.
  • The vapor barrier should be caulked and attached tightly to the foundation side walls. For example, with furring strips and masonry nails.
    78)   Water supply pipes are uninsulated. Recommend insulating pipes as necessary for better energy efficiency and to prevent water pipes from freezing.
    79)   Some crawl space areas were inaccessible due to low height (less than 18 inches), ductwork or pipes blocking, standing water, and/or stored items. These areas are excluded from this inspection.

    Photo 74  
    Ponding in crawl space. Note submerged objects.
     
     
    Kitchen Return to table of contents

    80)   One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    Photo 21  
    Grounding corrosion and wood rot.

    Photo 22  
    Under kitchen sink, leakage and rot, galvanic corrosion noted at most dissimilar metal joints throughout plumbing system.

    Photo 46  
    Sub-standard wiring and galvanic corrosion at grounding wire, repair and replace.

    Photo 47  
    Water leak at washer sink.

    Photo 48  
    Under washer sink, wet shelf
     

    81)   Tile, stone and/or grout countertops are damaged and/or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary. For example, replacing broken tiles and deteriorated grout, and resealing grout.
     
    Bathrooms Return to table of contents

    82)   Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.

    Photo 40  
    This is a safety issue
     

    83)   Lighting fixtures in shower area may constitute a safety issue depending on wiring structure. Since most all observed wiring terminates in two pronged outlets there well may be an electrical shock hazard here.
    *Recommend evaluation by qualified electrician.

    Photo 80  

    Photo 81  

    84)   One or more wall-mounted electric switches are within reach of shower stalls. This is a safety hazard due to the risk of shock. At a minimum, the client(s) should be aware of the shock hazard this represents and never operate such switches while showering. Ideally, a qualified electrician should evaluate and move switches as necessary, or a qualified contractor should make modifications as necessary so wall switches are unreachable from shower stalls.
    85)   One or more electric receptacles and/or the boxes they are installed in are loose and/or not securely anchored. Wire conductors may be damaged due to repeated movement and/or tension on wires, or insulation may be damaged. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary.
    86)   One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    Photo 32  
    GFCI needed
     

    87) One or more leaks were found at water supply lines. A qualified plumber should evaluate and repair as necessary.
    88) Tile and/or grout in one or more showers is damaged and/or deteriorated. For example, deteriorated or missing grout, cracked, missing or loose tiles, etc. A qualified contractor should evaluate and repair tile and/or grout as necessary.
    89)   One or more bathrooms with a shower do not have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
    90)   Tile and/or grout in one or more showers is damaged and/or deteriorated. For example, deteriorated or missing grout, cracked, missing or loose tiles, etc. A qualified contractor should evaluate and repair tile and/or grout as necessary.
    91)   Tile, stone and/or grout flooring is damaged and/or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary. For example, replacing broken tiles and deteriorated grout, and resealing grout.

    Photo 55  
    Grout/caulk needed. Since prolonged exposure to moisture leads to rot in floor below and inspector was unable to evaluate from below due to water and safety conditions, it is strongly recommended that a qualified contractor evaluate and repair as necessary.

    Photo 58  
    Grout/caulk needed. Since prolonged exposure to moisture leads to rot in floor below and inspector was unable to evaluate from below due to water and safety conditions, it is strongly recommended that a qualified contractor evaluate and repair as necessary.

    92)   One or more faucets leak or drip when turned off. A qualified plumber should evaluate and repair as necessary.
    93)   One or more faucets leak by handle(s) or at their base when turned on. A qualified plumber should evaluate and repair as necessary.
    94)   The shower diverter valve for one or more bathtub faucets is defective. A significant amount of water comes out of the bathtub spout when the shower is turned on. Water will be wasted as a result. A qualified plumber should evaluate and replace components or make repairs as necessary.
    95)   One or more toilet tank lids are cracked or broken. Lid(s) should be replaced as necessary.
    96)   One or more handles are missing from water shut-off valves. Handles should be replaced where missing.
    97)   One or more faucet handles are loose or missing and should be repaired or replaced as necessary.
    98)   One or more sink stopper mechanisms are missing, or need adjustment or repair. Stopper mechanisms should be installed where missing and/or repairs should be made so sink stoppers open and close easily.
    99)   Caulk is missing or deteriorated along the base of one or more bathtubs, where flooring meets the tub. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the floor structure.
    100)   Caulk is missing or deteriorated above one or more bathtubs, where the tub surround meets the tub. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the wall structure.
    101)   Caulk is missing or deteriorated around the base of one or more bathtub spouts. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to wall structures.
    102)   Caulk is missing and/or deteriorated at one or more bathtubs. For example, where the tub base meets the floor below, where the tub surround meets the tub, and/or around the base of the tub spout. Caulk should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to wall and floor structures.
    103)   Caulk is missing or deteriorated along the base of one or more showers, where flooring meets the shower. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the floor structure.
    104)   Caulk is missing or deteriorated around one or more shower surrounds. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the wall structure.
    105)   Minor damage and/or deterioration was found at countertops in one or more areas. The client(s) should evaluate and consider having repairs made, and/or countertops replaced where necessary.
    106)   One or more toilets have no water supply and could not be fully evaluated. The shut-off valve(s) may be turned off, or repairs may be necessary. The client(s) should ask the property owner(s) about this, and have a qualified plumber evaluate and repair if necessary.
     
    Interior rooms Return to table of contents

    107)   Two-pronged electric receptacles rather than three-pronged, grounded receptacles are installed in one or more interior rooms. They are considered to be unsafe by today's standards and limit the ability to use appliances that require a ground in these rooms. Examples of appliances that require grounded receptacles include:

  • Computer hardware
  • Refrigerators
  • Freezers
  • Air conditioners
  • Clothes washers
  • Clothes dryers
  • Dishwashers
  • Kitchen food waste disposers
  • Information technology equipment
  • Sump pumps
  • Electrical aquarium equipment
  • Hand-held motor-operated tools
  • Stationary and fixed motor-operated tools
  • Light industrial motor-operated tools
  • Hedge clippers
  • Lawn mowers

    This list is not exhaustive. A qualified electrician should evaluate and install grounded receptacles as per the client(s)' needs and standard building practices.

    Photo 40  
    This is a safety issue
     

    108)   No smoke alarms are visible. This is a safety hazard. A qualified electrician should install smoke alarms as per standard building practices (functioning one exists in hallways leading to bedrooms, and in each bedroom, etc.). For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
    109)   This structure was built prior to 1979 and may contain lead paint. Laws were enacted in 1978 in the US preventing the use of lead paint in residential structures. Lead is a known safety hazard, especially to children but also to adults. The paint found in and around this structure appeared to be intact and may be encapsulated by more recent layers of paint that are not lead-based. Regardless, recommend following precautions as described in the following links to Consumer Products Safety Commission website articles regarding possible lead paint.

    What You Should Know About Lead Based Paint in Your Home: Safety Alert - CPSC Document #5054

    CPSC Warns About Hazards of "Do lt Yourself" Removal of Lead Based Paint: Safety Alert - CPSC Document #5055

    110)   Carpeting in one or more rooms is damaged and/or significantly deteriorated. Recommend replacing carpeting where necessary.
    111)   Carpeting in one or more rooms is soiled and/or stained. Recommend having carpeting professionally cleaned as necessary.
     
    Electric service Return to table of contents
    Primary service type: Overhead
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120/240
    Location of main service switch: lower level
    Location of sub panels: hall and kitchen
    Location of main disconnect: Breaker at top of main service panel
    Service entrance conductor material: Aluminum
    System ground: Ground rod(s) in soil, Cold water supply pipes
    Main disconnect rating (amps): 200
    Branch circuit wiring type: Non-metallic sheathedsome cloth covered wiring present in branch lines.
    Solid strand aluminum branch circuit wiring present: Yes
    Smoke detectors present: No
    Primary service type: Overhead
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120/240
    Location of main service switch: lower level
    Location of sub panels: hall and kitchen
    Location of main disconnect: Breaker at top of main service panel
    Service entrance conductor material: Aluminum
    System ground: Ground rod(s) in soil, Cold water supply pipes
    Main disconnect rating (amps): 200
    Branch circuit wiring type: Non-metallic sheathed, some cloth covered wiring present in branch lines. This is not up to todays construction standards.
    Solid strand aluminum branch circuit wiring present: Yes
    Smoke detectors present: No
    112)   The service drop wires are less than 3 feet from one or more doors, balconies, decks and/or windows that open. This is a safety hazard due to the risk of shock. A qualified electrician and/or the utility company should evaluate and repair as necessary.

    Photo 70  
    Service line, safety issue. Too close to edge.
     

    113)   The service drop wires are less than three feet above one or more sections of roof with a slope of 3/12 (three inches vertical for every 12 inches horizontal) or more. This is a safety hazard for shock since people on the roof may come into contact with the service drop wires. The utility company and/or a qualified electrician should evaluate and repair as necessary.

    Photo 69  
    Fascia has been cut for service to pass under, safety issue.

    Photo 70  
    Service line, safety issue. Too close to edge.

    114)   One or more connections with aluminum wires in the main service panel lack anti-oxidant paste. Oxidation usually occurs without it, and may result in poor connections, overheating, and possibly fires. A qualified electrician should evaluate and apply anti-oxidant paste as necessary.

    Photo 49  
    Aluminum branch wiring, cracked insulation, no anti oxidant, safety issue.
     

    115)   The service drop wires are less than 3 feet from one or more doors, balconies, decks and/or windows that open. This is a safety hazard due to the risk of shock. A qualified electrician and/or the utility company should evaluate and repair as necessary.

    Photo 70  
    Service line, safety issue. Too close to edge.
     

    116)   The service drop wires are less than three feet above one or more sections of roof with a slope of 3/12 (three inches vertical for every 12 inches horizontal) or more. This is a safety hazard for shock since people on the roof may come into contact with the service drop wires. The utility company and/or a qualified electrician should evaluate and repair as necessary.
    117)   One or more bushings are missing from where wires enter holes in the main service panel. This is a safety hazard since the wiring insulation can be cut or abraded on the metal edge of the hole(s). A qualified electrician should install bushings where missing.
    118)   Sub panel in kitchen has no strain relief clamps attached to box . All branch wiring is loosely run into box through main feed hole.
    119)   The inspector didn't remove the lower sub-panel cover due to water leaking into the panel. This is a shock hazard. This panel wasn't fully evaluated. Repairs should be made as necessary to prevent water from leaking into the panel.
    The main breaker panel appears to have water intrusion also , apparently coming in from the weather head or pull beneath the weather head.

    Photo 35  
    Large puddle under sub-panel, not inspected

    Photo 36  
    Water stains, appears to be leaking from inside sub-panel.

    Photo 37  
    Bottom of sub-panel above showing corrosion, suspect water leakage into panel, not inspected due to water on floor.
     

    120)   One or more bushings are missing from where wires enter holes in the main service panel. This is a safety hazard since the wiring insulation can be cut or abraded on the metal edge of the hole(s). A qualified electrician should install bushings where missing.
    121)   Sub panel in kitchen has no strain relief clamps attached to box . All branch wiring is loosely run into box through main feed hole.
    122)   One or more knockouts have been removed inside the main service panel where no wires and bushings are installed, and no cover(s) have been installed to seal the hole(s). This is a safety hazard due to the risk of fire. A qualified electrician should install knockout covers where missing.
    123)   One or more knockouts have been removed inside the main service panel where no wires and bushings are installed, and no cover(s) have been installed to seal the hole(s). This is a safety hazard due to the risk of fire. A qualified electrician should install knockout covers where missing.
    124)   Sub panel in hall closet has unusual push button breakers.

    Photo 43  
    Floor shot of floor below PushMatic electric panel.
     
     

    Photo 1  
    BB hole, living room window

    Photo 3  
    Mast to outbuilding from roof

    Photo 8  
    Showing roof leak from under roofing

    Photo 10  
    Service entrance wires frayed, safety issue

    Photo 14  
    Driveway holes

    Photo 16  
    Window at bottom of stairs needs a guard, safety issue

    Photo 18  
    Under deck rusty, leaking hole

    Photo 20  
    GFCI needed

    Photo 23  
    This glass should be a safety type. Any area that a person or child may break and fall through should be a safety type of glass.

    Photo 24  
    Wash sink area, some leakage and rot.

    Photo 25  
    De-lamination of of deck support beam with some rot showing

    Photo 27  
    Carpet wet next to wall of bathroom, main bath.

    Photo 29  
    Main bath, safety issue

    Photo 30  
    Shower/tub handle broken

    Photo 33  
    Lower level floor puddles

    Photo 38  
    Fireplace clean out door missing, lower level

    Photo 39  
    Air return, bottom of stairs closet, filter was noticed not to fit correctly.

    Photo 42  
    AC unit, hall, water on floor, corner and wall.

    Photo 45  
    "Moat" filled w/water

    Photo 52  
    Unable to ascertain connection of this "beam" appears to "float".
    Have carpenter look into it.

    Photo 56  
    GFCI needed.

    Photo 57  
    Moisture damage, under sink, bathroom

    Photo 59  
    Moisture damage

    Photo 60  
    Moisture damage

    Photo 61  
    Moisture damage

    Photo 64  
    Indoor planter area, certain amount of mold noticed in this area.

    Photo 65  
    Puddle by front door after rain.

    Photo 67  
    Different service lines lying in water filled trench.

    Photo 75  
    Water running down drive after rain. This will eventually lead to serious erosion. Recommended maintenance, "French" or trench style drainage system needed.

    Photo 76  
    Drive in need of heavy maintenance and repair.

     