Andy's Eagle Eye Home Inspections LLC


Inspector's email: acinspections@yahoo.com
Inspector's phone: (407) 406-8875
907 Robinson Ave 
Saint Cloud FL 34769-2063
Inspector: Andy Christel
Fl License #HI739

 

Property Inspection Report

Client(s):  xxxxxxxxxx
Property address:  xxxx sample dr
St Cloud Fl 34771
Inspection date:  Wednesday, April 17, 2013

This report published on Saturday, May 17, 2014 5:46:22 PM EDT

This report is the exclusive property of.Andy's Eagle Eye Home Inspections LLC,For this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.FL License #HI739
[/b]www.andyseagleeyehomeinspections.com" target="new">http://www.reporthost.com/andyeagleeye,www.andyseagleeyehomeinspections.com



How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyMay cause harm to persons and property.
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior / Foundation
Roof / Attic
Garage / Carport
Electric
Plumbing / Fuel Systems
Water Heater
Cooling / Heat Pump
Kitchen
Bathrooms / Laundry / Sinks
Interior Rooms / Areas
Private Well
Wood Destroying Organism Findings


General Information
Return to table of contents

Report number: 1304
Time started: 1:00 pm
Time finished: 3:00 pm
Inspector: Andy
Present during inspection: Client
Client present for discussion at end of inspection: Yes
Weather conditions: Clear
Temperature: Warm
Ground condition: Dry
Inspection fee: $285.00
Payment method: Invoiced
Type of building: Single family
Buildings inspected: 1
Age of building(s): 8 years
Source for building age: Municipal records
Front of building faces: East
Main entrance faces: East
Occupied: No
Grounds
Return to table of contents

Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
Condition of fences and gates: Appeared serviceable
Fence and gate material: Chain link
Site profile: Minor slope
Condition of driveway: Appeared serviceable
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Covered (Refer to Roof section)
1) Conducive conditions Vegetation such as trees, shrubs and/or vines was in contact with or less than one foot from building exteriors. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and building exteriors.
2) Minor cracks, settlement, heaving and/or deterioration were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
Exterior / Foundation
Return to table of contents

Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of wall covering: Appeared serviceable
Apparent wall structure: Concrete block
Wall covering: Painted concrete block.
Foundation type: Slab on grade
Foundation material: Poured in place concrete
Footing material: Not determined
3) Minor settlement cracking. This is normal do to the structure settling.
Recommend sealing with an approved sealent.
Photo
Photo 3-1
Photo
Photo 3-2

4) concrete slab floor sections were obscured by flooring and couldn't be fully evaluated.
Roof / Attic
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
Condition of roof structure: Appeared serviceable
Roof type: Gable
Age of roof surface(s): Approx 4 years
Source for building age: Inspector's estimate
Roof inspection method: Traversed
Condition of shingle and/or shake roof surface materials: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Apparent number of layers of roof surface material: Two
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
Condition of exposed flashings: Appeared serviceable
Gutter and downspout material: None
Condition of attic: Appeared serviceable
Attic inspection method: Partially traversed
Roof structure type: Trusses
Ceiling structure: Trusses
Ceiling insulation material: Fiberglass roll or batt, Cellulose loose fill
Ceiling insulation depth: Average 6 to 8 inch
Ceiling insulation rating: R=30
Roof ventilation: Appears serviceable
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
5) The attic access hatch over the attached garage was not fire-rated. Wall and ceiling surfaces in an attached garage should be fire rated for one hour to prevent or slow the spread of fire from the garage to interior living spaces. A hatch should be installed with a material that has a one hour fire rating, such as 5/8 inch Type X sheetrock.

Recommend installing 5/8 thick drywall, Sheetrock.
Photo
Photo 5-1
 

6) The attic fan was controlled by a thermostat. Because of the ambient temperature at the time of the inspection and/or the thermostat controls, the inspector was unable to evaluate the attic fan. It is excluded from this inspection.
7) Gutters were missing over one or more entrances. People entering and exiting the building are more likely to get wet during periods of rain because of this. Most buildings benefit from having a complete drainage system installed, but at a minimum, recommend installing gutters over entrances.
8) Some attic and roof structure sections were not evaluated due to lack of access from the following conditions: limited height.
Photo
Photo 8-1
 

9) Roofing appears to be in good condition.
Photo
Photo 9-1
Photo
Photo 9-2
Photo
Photo 9-3
 

Garage / Carport
Return to table of contents

Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages varies between municipalities.
Type: Attached
Condition of garage: Appeared serviceable
Type of garage: Solid core
Condition of garage vehicle door(s): Appeared serviceable
Garage vehicle door type: Sectional
Number of vehicle doors: 1
Condition of garage floor: Appeared serviceable
Condition of garage interior: Required repair or evaluation (see comments below)
10) Minor drywall repair needed. Recommend a qualified person repair and seal all wall penatrations.
Photo
Photo 10-1
 

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120, 120
Service amperage (amps): 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Aluminum
Main disconnect rating (amps): 150
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Condition of sub: Appeared serviceable
Location of main service panel #A: Building exterior
Location of main disconnect: Breaker at top of main service panel
Branch circuit wiring type: Non-metallic sheathed, Copper
Condition of branch circuit wiring: Serviceable
Solid strand aluminum branch circuit wiring present: None visible
Condition of smoke detectors: Appeared serviceable
Smoke detectors present: Yes
Carbon monoxide detectors present: No
Smoke detector power source: Battery, Hard wired
11) Non-metallic sheathed wiring was routed in one or more areas so it was subject to damage, such as on wall or ceiling surfaces Attic areas. The insulation can be damaged by objects coming in contact with it and/or it being repeatedly moved. This is a safety hazard due to the risk of shock and fire. A qualified electrician should evaluate and repair as necessary. For example, rewire using conduit, or re-routing through wall cavities.
Photo
Photo 11-1
 

12) Substandard wiring was found in the exterior wall. For example, exposed wiring. This is a safety hazard. A qualified electrician should evaluate and repair as necessary and as per standard building practices.
Photo
Photo 12-1
 

13) light fixtures were damaged. A qualified person should evaluate and repair or replace as necessary.
Photo
Photo 13-1
 

14) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit:
http://www.cpsc.gov/cpscpub/pubs/5077.html
Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
Water service: Private
Service pipe material: Galvanized steel
Condition of supply lines: Appeared serviceable
Supply pipe material: CPVC
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Not determined
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
15) This property has a well pump system. The well pump needed repair at time of inspection. The client was at the property during the inspection. As the client is also a plumber attempted to make some repairs to the well pump had incountered some other problems. A broken water line to the house. This broken water line left the inspector unable to evaluate the water heater, sinks, toilets and tubs/ showers.
Should the well system become repaired the inspector may offer to return to the said property for a reinspection for a fee.
Photo
Photo 15-1
Photo
Photo 15-2

Water Heater
Return to table of contents

Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Appeared serviceable
Type: Tank
Estimated age: According to the inspectors information this water heater appears to have been manufactured in 1988.
Energy source: Electricity
Capacity (in gallons): 40
Manufacturer: Rheem
Model: 81v-40d
Location of water heater: Garage
Water temperature (degrees Fahrenheit): Not determined
16) This water heater was not fully evaluated because the No water supplied. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the appliance is operable. Note that as per the standards of practice for NACHI (http://www.nachi.org) and ASHI (www.ashi.org), the inspector is not required to operate shut-off valves, pilot lights or overcurrent protection devices, or any controls other than "normal controls".

Unable to fully evaluate do to the water supply.
Photo
Photo 16-1
 

Cooling / Heat Pump
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Appeared serviceable
Location: Closet in hallway
Type: Heat pump
Estimated age: According to the inspectors information. This heat pump system appears to be manufactured in 1997.
17) The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified contractor should service this system and make repairs if necessary. This servicing should be performed annually in the future. This system was functioning well at time of inspection.
Photo
Photo 17-1
Photo
Photo 17-2

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of range, cooktop: Appeared serviceable
Range, cooktop type: Electric
18) Minor drywall repair neede under the sink.
Photo
Photo 18-1
 

Bathrooms / Laundry / Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceableUnable to fully evaluate do to no water
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Interior Rooms / Areas
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
Exterior door material: Metal
Condition of exterior entry doors: Appeared serviceable
Condition of interior doors: Appeared serviceable
Type of windows: Aluminum
Condition of windows: Appeared serviceable
Wall type or covering: Drywall
Condition of walls: Appeared serviceable
Ceiling type or covering: Drywall
Condition of ceilings: Appeared serviceable
Flooring type or covering: Vinyl
Condition of flooring: Required repairs, replacement and/or evaluation (see comments below)
19) Trim was missing in areas. A qualified person should repair as necessary.
Photo
Photo 19-1
 

20) Many sections of vinyl flooring had significant deterioration or damage. For example, loose edges or tiles. A qualified person should replace or repair flooring as necessary.
Photo
Photo 20-1
Photo
Photo 20-2

21) The door's doorbell button was loose. A qualified person should repair or install as necessary.
Photo
Photo 21-1
 

22) One or more bifold doors were off their track(s). A qualified person should repair as necessary.
Photo
Photo 22-1
 

23) Minor cracks and/or holes were found in walls in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
Photo
Photo 23-1
 

24) Carpeting in one or more areas was significantly stained or soiled. Recommend having carpeting professionally cleaned as necessary.
25) All exterior doors didn't have a screen door.
Private Well
Return to table of contents

Limitations: The inspector does not test private well water for contamination or pollutants, determine if the supply and/or flow are adequate, or provide an estimate for remaining life of well pumps, pressure tanks or equipment. Only visible components are evaluated. The client should have qualified lab test the well water for bacterial contaminants. A qualified well specialist should evaluate the well and perform a yield test.
Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than five feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood destroying organisms may infest, reinfest or become active at anytime. No warranty is provided as part of this inspection.
Visible evidence of active wood destroying insects: No
Visible evidence of active wood decay fungi: No
Visible evidence of past wood destroying insects: No
Visible evidence of past wood decay fungi: No
Visible evidence of damage by wood destroying insects: No
Visible evidence of damage by wood decay fungi: No
Visible evidence of conditions conducive to wood destroying organisms: No

Photo
Photo X-1
Main service panel. Main breaker at top.
Photo
Photo X-2
Kitchen area.
Photo
Photo X-3
Filters should be cleaned.
 

Important...Read Carefully
This property inspection report may include an inspection agreement (contract) addenda, and other informatiom related to property conditions.If any item or comment is unclear, you should ask the inspector to clarify the findings. It is important that you carefully read ALL of this information upon receipt. This inspection has been performed and this report prepared in accordance with the standards of practice for home inspections. An inspection addresses only those components and conditions that are present,visible and accessible at the time of inspection.While there may be other parts, components or systems present, only those items specifically noted as being inspected were inspected. The inspector is not required to move furnishings or stored items. The inspection report may address issues that are code based or may refer to a particular code; however, this is NOT a code compliance inspection and does NOT verify compliance with manufacturer's installation instructions. The inspection does NOT imply insurability or warrantability of the structure or its components. Although some safety issues may be addressed in this report, this inspection is NOT a safety - code inspection, and the inspector is NOT required to identify all potential hazards, In this report, the inspector will note which systems and components were inspected, and report any deficiencies, safety concerns, maintenance and monitoring requirements, and any items that are deferred.