How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Structural Pest Inspection Concerns
Items of concern relating to the structural pest inspection are shown as follows:
WDO/WDI InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
WDO/WDI DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
WDO/WDI Conducive
conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Attached garage
Electric service
Water heater
Heating and air conditioning
Attic
Plumbing and laundry
Basement
Fireplaces and solid fuel burning appliances
Interior rooms
 
General information Return to table of contents
Overview: There are numerous issues with this home. Roof decking is "mushy" all over. Numerous areas of trim on exterior of home have become rotted due to moisture and need to be replaced. Excessive cracking in the walls and ceilings. Windows are cheaply made and one has already been replaced, inspector feels like the windows will be problematic in the future. Overall, home has numerous problems with the potential of there being major repairs in the near future.
Structures inspected: Main dwelling
Report number: marshall6342
Time started: 10:00am
Time finished: 1:00pm
Inspection Fee: 200.00
Occupied: Yes
Type of building: Single family
Weather conditions: Partly cloudy
Temperature: Hot
Ground condition: Wet
Main entrance faces: East
Foundation type: Finished basement
The following items are excluded from this inspection: Security system
1)   Numerous wall, floor and/or ceiling surfaces were obscured by large amounts of furniture and/or stored items, preventing a full evaluation of some areas.
 
Exterior Return to table of contents
Foundation material: Concrete block
Apparent wall structure: Wood frame
Wall covering: Vinyl
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core fiberglass
Water pressure (psi): adequate
2)   There are numerous pieces of wood trim on the back of the house at the kitched nook window that are rotted out due to moisture intake in the wood and need to be replaced. Recommend having a qualified contractor evaluate and make the necessary repairs.

Photo 2  

Photo 11  

Photo 14  

Photo 15  

Photo 16  

Photo 17  

3) One or more wooden deck support posts are in contact with soil. This is a conducive condition for wood destroying insects and organisms. However no damage from wood destroying insects or organisms was found. It's recommended that there be at least 6" of space between any wood and the soil below, even if the wood is treated. If possible, recommend grading soil so a 6" distance to the soil below is maintained. Otherwise recommend installing borate based Impel rods to prevent rot.
4)   Caulk is missing or deteriorated in some areas. Recommend caulking where necessary.

Photo 3  

Photo 12  

Photo 13  

5)   Moderate cracks (1/8" to 3/4") present in foundation. Recommend sealing cracks to prevent water infiltration. Numerous products exist to seal such cracks including:
  • Hydraulic cement. Requires chiseling a channel in the crack to apply. See http://www.quickrete.com/catalog/HydraulicWater-StopCement.html for an example.
  • Resiliant caulks (easy to apply). See http://www.quickrete.com/catalog/GrayConcreteRepair.html for an example.
  • Epoxy sealants (both a waterproof and structural repair). See http://www.mountaingrout.com/ for examples of these products.

    Photo 4  

    Photo 9  

    6)   There are several pieces of wood trim that are starting to come apart from the house and need to be addressed. Recommend having qualified contractor evaluate and make the necessary repairs.

    Photo 5  

    Photo 6  

    7)   There is a piece of siding that appears to be warped and needs to be replaced. Recommend having a qualified contractor evaluate and make the necessary repairs.

    Photo 7  

    8)   Shingles in the front of the house on the overhang appear to be curling up and needs to be replaced. Recommend having a qualified roofing contractor evaluate and make the necessary repairs.

    Back patio concrete has cosmetic crack in the patio. It is only a cosmetic crack and does not require any action.

    Photo 10  

    Photo 19  

    9)   The grating for the ac unit outside appears to be very rusty which leads inspector to believe that there is a significant amount of water dumping on the unit. Inspector recommends having qualifed HVAC technician evaluate and make the necessary recommendations and repairs.

    Photo 8  

    10)   The substructure of the deck is excluded from the inspection due to limited access because of the low height.
     
    Roof Return to table of contents
    Roof inspection method: Traversed
    Roof type: Cross gable
    Roof covering: Asphalt or fiberglass composition shingles
    Estimated age of roof: 10 years
    Gutter & downspout material: Aluminum
    Roof ventilation: Adequate
    11) Significant amounts of debris have accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the roof structure or make water accumulate around the foundation. Recommend cleaning gutters now and as necessary in the future.
    12)   Roof is "mushy" in several areas throughout the entire roof and is consistent with use of inferior wood decking material. Recommend having a qualified roofing contractor evaluate and make the necessary repairs.
     
    Attached garage Return to table of contents

    13)   The garage-house door isn't equipped with an automatic door closing device such as sprung hinges. This door should close and latch automatically to prevent vehicle fumes from entering living spaces and/or to slow the spread of fire from the garage to living spaces. A device should be installed so this door closes and latches automatically.
    14)   The interior perimeter of the garage is excluded from this inspection due to lack of access from stored items.
     
    Electric service Return to table of contents
    Primary service type: Underground
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 200
    Service voltage (volts): 120-240
    Location of main service panel: Garage
    Location of main disconnect: Breaker at top of main service panel
    Service conductor material: Aluminum
    Main disconnect rating (amps): 200
    Branch circuit wiring type: Non-metallic sheathed
    Solid strand aluminum branch circuit wiring present: Can't verify
    Smoke detectors present: Yes
    15)   An insufficient number of smoke detectors are installed. Recommend installing additional smoke detectors as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information on smoke detectors visit http://www.cpsc.gov/cpscpub/pubs/5077.html
     
    Water heater Return to table of contents
    Estimated age: 11 Years
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 50
    Brand & model: Bradford White MI50366N10
    16)   The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be approaching this age. Recommend budgeting for a replacement in the near future.
    17)   The drain line to the water heater's temperature-pressure relief valve is routed directly down over the cement floor with no drain underneath which poses a problem of flooding in an incident that the relief valve is used.

    Photo 55  
     
    Heating and air conditioning Return to table of contents
    Heating system energy source: Natural gas
    Heat system type: Forced air
    A/C energy source: Electric
    Air conditioning type: Split system
    Distribution system: Sheet metal ducts
    Brand & model: Bryant 561C
    18)   The estimated useful life for air conditioning compressors is 8 to 15 years. This unit appears to be approaching this age and may need replacing at any time.
    19)   Recommend that this system be inspected, cleaned, serviced and repaired if necessary by a qualified heating and cooling technician annually in the future.
    20)   This system is equipped with throw-away filter(s). Recommend replacing throw-away filter(s) every 2 months in the future if the thermostat's fan position is set to "Auto", or monthly if it's set to "On".
     
    Attic Return to table of contents
    Inspection method: Partially traversed
    Roof structure type: Trusses
    Ceiling structure: Ceiling beams
    Insulation material: Fiberglass roll or batt, Rockwool loose fill
    21)   Ceiling insulation is uneven in some areas. This is likely due to someone having walked on or through the insulation. Recommend installing additional insulation where necessary to restore the original R rating.
     
    Plumbing and laundry Return to table of contents
    Location of main water shut-off valve: Above water heater
    Location of main water meter: Front yard
    Location of main fuel shut-off: Not visible/At meter
    Water service: Public
    Service pipe material:
    Supply pipe material: Copper
    Vent pipe material: Plastic
    Drain pipe material: Plastic
    Waste pipe material: Plastic
     
    Basement Return to table of contents
    Insulation material underneath floor above: Fiberglass roll or batt
    Pier or support post material: Steel
    Beam material: Steel
    Floor structure above: Solid wood joists
    22)   Cover plate(s) are missing from one or more electric junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard and poses a risk of both fire and shock. Recommend installing cover plates over junction boxes where missing.

    Photo 54  

    23)   The top step going down to the basement needs a piece of trim to cover the exposed and unfinished tile/pad/wood floor.

    Photo 51  

    24)   Not sure what to say about these issues but to show the pictures..........

    Photo 52  

    Photo 53  
     
    Fireplaces and solid fuel burning appliances Return to table of contents
    Fireplace type: Metal prefabricated
    Chimney type: Metal
    25)   All solid fuel burning appliances (woodstoves and fireplaces) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
     
    Interior rooms Return to table of contents

    26)   No ground fault circuit interrupter (GFCI) devices (receptacles or circuit breakers) are visible in one or more bathrooms. GFCI devices help prevent electric shocks in areas that may have water present. Recommend having a qualified, licensed electrician install GFCI protection for receptacles over counter tops and around sinks as per standard building practices.
    27)   All of the windows in the home are inferior quality. Inspector noted that it felt like the windows were going to fall out of the home when testing each one to open vertically and also when testing to see if they would open towards him to clean. One window has already had to be replaced.

    Photo 29  

    28)   Walking on some sections of the floor results in squeaking or creaking noises. This is usually the result of substandard construction practices where the subfloor decking isn't adequately fastened (insufficient glue) to the framing below. In most cases, this is an annoyance only rather than a structural problem. Various solutions such as Squeeeeek No More and Counter Snap fasteners exist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on there being finished hardwood floors, carpeting over the subfloor, and/or clear access to the underside of the subfloor. Recommend having a qualified contractor evaluate and repair as necessary.
    29)   Minor cracks found in ceiling. These are only a cosmetic concern. No action is recommended. Inspector notes that cracking is excessive.

    Photo 34  

    Photo 36  

    Photo 37  

    Photo 41  

    Photo 44  

    Photo 45  

    Photo 48  

    Photo 50  

    30)   Minor cracks found in walls. These are only a cosmetic concern. No action is recommended. Inspector notes that cracking is excessive in nature.

    Photo 20  

    Photo 21  

    Photo 28  

    Photo 33  

    Photo 35  

    Photo 38  

    Photo 46  

    Photo 49  

    Photo 56  

    Photo 57  

    31)   There is numerous caulking that needs to be done throughout the home. Recommend caulking where needed.

    Photo 24  

    Photo 25  

    Photo 26  

    Photo 27  

    Photo 30  

    Photo 31  

    Photo 32  

    Photo 40  

    Photo 42  

    Photo 43  

    Photo 47  

    32)   One or more sink stopper mechanisms are missing, inoperable or in disrepair. Recommend intalling or repairing sink stopper mechanisms as necessary.
    33)   Numerous electrical receptacles were not evaluated because childproof covers were installed at the time of the inspection.
    34)     There are nail pops throughout the home, these are of a cosmetic nature only. On both walls leading down to the basement, it is very evident that the screws or nails that were used to install are coming out and will ALL be popping through the paint sooner than later.

    Photo 22  

    Photo 39  

    35)     Doorbell is button is damaged and needs to be replaced.

    Photo 23  

     
    This report is the exclusive property of A.M.C. HOME INSPECTIONS INC. and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.