Property Inspection Report

Client(s):  Brandon Naylor
Property address:  14986 County Road 181
Limon CO 80828-8812
Inspection date:  Friday, October 02, 2015

This report published on Saturday, October 03, 2015 9:47:36 AM MDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Basement
Roof
Attic and Roof Structure
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows


General Information
Return to table of contents

Time started: 0900
Time finished: 1100
Present during inspection:
Client present for discussion at end of inspection: No
Weather conditions during inspection: Rain, Windy
Temperature during inspection: Cold, Cool
Inspection fee: 275.00
Payment method: Credit card
Type of building: Single family
Buildings inspected: One house
Number of residential units inspected: 1
Age of main building: 1920+
Source for main building age: Inspector's estimate
Front of building faces: Southeast
Main entrance faces: Northwest
Occupied: No

1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC

2) Evidence of rodent infestation was found in the form of feces and/or poison in the garage. Consult with the property owner about this. A qualified person should make repairs to seal openings in the structure, set traps, and clean rodent waste as necessary. Recommend following guidelines in these Center for Disease Control articles:
http://www.reporthost.com/?SEALUP
http://www.reporthost.com/?TRAPUP
http://www.reporthost.com/?CLEANUP

3) Microbial growths were found at one or more locations in the basement. It is beyond the scope of this inspection to identify what substance or organism this staining is. However such staining is normally caused by excessively moist conditions, which in turn can be caused by plumbing or building envelope leaks and/or substandard ventilation. These conducive conditions should be corrected before making any attempts to remove or correct the staining. Normally affected materials such as drywall are removed, enclosed affected spaces are allowed to dry thoroughly, a mildewcide may be applied, and only then is drywall reinstalled. For evaluation and possible mitigation, consult with a qualified industrial hygienist or mold/moisture mitigation specialist. For more information, visit:
http://www.reporthost.com/?MOLDCDC
http://www.reporthost.com/?MOLDEPA
Photo
Photo 3-1
 

4) The client should be aware that prior to 1976, factory-built homes in America were built only according to voluntary standards. Because this building was built prior to 1976, it may be significantly substandard in safety, efficiency, quality, durability, etc. Factory-built homes since 1976 have been required to comply with federal construction and safety standards (the HUD Code). This code is administered by the U.S. Department of Housing and Urban Development (HUD), and standardizes design, construction, energy efficiency, fire resistance, transportability, strength, and durability. It also mandates performance standards for the electrical, plumbing, air conditioning, thermal, and heating systems.

Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Unpaved, dirt
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Wood
Condition of stairs, handrails and guardrails: Appeared serviceable
Exterior stair material: Wood

5) Cracks, holes, settlement, heaving and/or deterioration were found in the driveway. Recommend that qualified contractor repair as necessary.
Photo
Photo 5-1
Photo
Photo 5-2

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground, from a ladder
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Wood
Condition of foundation and footings: Appeared serviceable
Apparent foundation type: Finished basement
Foundation/stem wall material: Concrete block
Footing material (under foundation stem wall): Not determined (inaccessible or obscured)

6) Many and/or all sections of siding and/or trim were damaged. Recommend that a qualified person repair, replace or install siding or trim as necessary.
Photo
Photo 6-1
Photo
Photo 6-2
Photo
Photo 6-3
Photo
Photo 6-4

7) Fungal rot was found at one or more sections of siding or trim. Conducive conditions for rot should be corrected (e.g. wood-soil contact, reverse perimeter slope). Recommend that a qualified person repair as necessary. All rotten wood should be replaced.
Photo
Photo 7-1
Photo
Photo 7-2

8) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
Photo
Photo 8-1
 

9) The paint or stain finish over much of the entire structure was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture. Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the entire building exterior per standard building practices. Any repairs needed to the siding or trim should be made prior to this.
Photo
Photo 9-1
Photo
Photo 9-2
Photo
Photo 9-3
 

Basement
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below), need to replace storm door
Exterior door material: Wood, Fiberglass or vinyl
Condition of floor substructure above: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Required repairs, replacement and/or evaluation (see comments below)
Insulation material underneath floor above: None visible

10) One or more adjustable steel columns were found. Some adjustable steel columns are rated for permanent use, but some are not. Based on the inspector's observations, columns in this building may not be rated for permanent use and may pose a safety risk for collapse. Recommend that a qualified contractor familiar with regulations surrounding use of such columns evaluate and repair if necessary, and per standard building practices.
Photo
Photo 10-1
 

11) One or more exterior doors were significantly damaged or deteriorated. Recommend that a qualified person replace door(s) as necessary.
Photo
Photo 11-1
Photo
Photo 11-2

12) One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.
Photo
Photo 12-1
Photo
Photo 12-2

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions: Appeared serviceable

13) The roof surface appeared to be near the end of its service life and will likely need replacing in the near future even if repairs are made now. Recommend discussing replacement options with a qualified contractor, and budgeting for a replacement roof surface in the near future. The client may also wish to consider having a qualified contractor attempt to issue a "5 year roof certificate."
Photo
Photo 13-1
Photo
Photo 13-2

14) Substandard repairs were found at one or more locations on the roof surface. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair per standard building practices.
Photo
Photo 14-1
 

15) Flashings at the base of one or more chimneys were corroded. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 15-1
 

16) One or more roof flashings were corroded. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.
Photo
Photo 16-1
Photo
Photo 16-2

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es), Traversed
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Trusses
Condition of insulation in attic (ceiling, skylight chase, etc.): Required repair, replacement and/or evaluation (see comments below)
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): Less than R-11, R-11
Vermiculite insulation present: None visible
Vapor retarder: None
Condition of roof ventilation: Required repair, replacement and/or evaluation (see comments below)
Roof ventilation type: Ridge vent(s)

17) The roof decking was spongy, soft or springy in one or more areas when the inspector walked on those areas. This may be caused by deteriorated sheathing, damaged rafters or trusses, and/or otherwise substandard construction. Recommend that a qualified contractor evaluate and repair as necessary.

18) The ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.

19) No vapor retarder was visible in the attic. Such vapor retarders reduce the flow of moisture from living spaces below, up into the attic, and prevent damage from moisture. For example, fungal rot, mold, and ice dams on the roof. Vapor retarders are not a standard recommendation except for very cold regions and in cases where there is high humidity in the house during the winter. Based on conditions found during this inspection, recommend that a qualified contractor install a vapor barrier.

20) One or more attic access hatches or doors were not insulated, or had substandard insulation. Recommend installing insulation as necessary and per current standards at hatches or doors for better energy efficiency. For more information, visit:
http://www.reporthost.com/?ATTACC

21) One or more attic access hatches or doors had no weatherstripping, or the weatherstripping was substandard. Weatherstripping should be installed around hatches or doors as necessary to prevent heated interior air from entering the attic. For more information, visit:
http://www.reporthost.com/?ATTACC

22) One or more attic access hatches or doors were not insulated, or had substandard insulation. Weatherstripping was also missing or substandard. Recommend installing weatherstripping and insulation per current standards at hatches or doors for better energy efficiency. For more information, visit:
http://www.reporthost.com/?ATTACC

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Required repair, replacement and/or evaluation (see comments below)
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120-240
Estimated service amperage: 100
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 100
System ground: Ground rod(s) in soil, Copper
Condition of main service panel: Required repair, replacement and/or evaluation (see comments below)
Condition of sub-panel(s): Not determined (inaccessible or obscured, or panels not opened)
Location of main service panel #A: Bedroom
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: None visible
Ground fault circuit interrupter (GFCI) protection present: Yes
Arc fault circuit interrupter (AFCI) protection present: No
Smoke alarms installed: Yes, but not tested
Carbon monoxide alarms installed: Yes, but not tested

23) One or more receptacles (outlets) were scorched. The wiring for these receptacles may be damaged due to overheating. Recommend that a qualified electrician replace such receptacles, evaluate related wiring and repair if necessary.
Photo
Photo 23-1
 

24) One or more electric receptacles (outlets) at the kitchen, laundry sink, exterior and/or basement had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI

25) The service drop wires were less than 10 feet above the ground, a deck or walkways. This is a shock hazard. A qualified electrician or the utility company should repair per standard building practices.
Photo
Photo 25-1
 

26) One or more circuit breakers in panel(s) #A were "double tapped," where two or more wires were installed in the breaker's lug. Most breakers are designed for only one wire to be connected. This is a safety hazard since the lug bolt can tighten securely against one wire but leave other(s) loose. Arcing, sparks and fires can result. Recommend that a qualified electrician repair as necessary. For more information, visit:
http://www.reporthost.com/?DBLTAP
Photo
Photo 26-1
 

27) One or more electric receptacles (outlets) were incorrectly wired with an open neutral. Recommend that a qualified electrician repair as necessary.
Photo
Photo 27-1
 

28) One or more cover plates for switches, receptacles (outlets) or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.
Photo
Photo 28-1
 

29) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.reporthost.com/?SMKALRMLS

30) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. Consult with a qualified electrician for repairs as necessary.

31) 2-slot receptacles (outlets) rather than 3-slot, grounded receptacles were installed in one or more areas. These do not have an equipment ground and are considered unsafe by today's standards. Appliances that require a ground should not be used with 2-slot receptacles. Examples of such appliances include computers and related hardware, refrigerators, freezers, portable air conditioners, clothes washers, aquarium pumps, and electrically operated gardening tools. The client should be aware of this limitation when planning use for various rooms, such as an office. Upgrading to grounded receptacles typically requires installing new wiring from the main service panel or sub-panel to the receptacle(s), in addition to replacing the receptacle(s). Consult with a qualified electrician about upgrading to 3-wire, grounded circuits.

32) The electric service to this property appeared to be rated at substantially less than 200 amps and may be inadequate. Depending on the client's needs, recommend consulting with a qualified electrician about upgrading to a 200 amp service. Note that the electric service's rating is based on the lowest rating for the meter base, the service conductors, the main service panel and the main disconnect switch. One or more of these components may need replacing to upgrade.
Photo
Photo 32-1
 

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public, Private well
Water pressure (psi): 45
Location of main water shut-off: Basement
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: No
Condition of fuel system: Appeared serviceable
Visible fuel storage systems: propane tank
Location of main fuel shut-off valve: At propane tank, At building exterior

33) Copper water supply pipes were installed. Copper pipes installed prior to the late 1980s may be joined with solder that contains lead, which is a known health hazard especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained approximately 50% lead. The client should be aware of this, especially if children will be using this water supply system. Note that the inspector does not test for toxic materials such as lead. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions include:
  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than 6 hours
  • Install appropriate filters at points of use
  • Use only cold water for cooking and drinking, as hot water dissolves lead more quickly than cold water
  • Use bottled or distilled water
  • Treat well water to make it less corrosive
  • Have a qualified plumber replace supply pipes and/or plumbing components as necessary
For more information visit:
http://www.reporthost.com/?LEADDW
http://www.reporthost.com/?LEAD

34) Based on visible components or information provided to the inspector, this property appeared to have a private sewage disposal (septic) system. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Generally, septic tanks should be pumped and inspected every 3 years. Depending on the type of system and municipal regulations, inspection and maintenance may be required more frequently, often annually. Recommend the following:
  • Consult with the property owner about this system's maintenance and repair history
  • Review any documentation available for this system
  • Review inspection and maintenance requirements for this system
  • That a qualified specialist evaluate, perform maintenance and make repairs if necessary
For more information, visit:
http://www.reporthost.com/?SEPTIC

35) A water softener system was installed on the premises. These are specialty systems and are excluded from this inspection. Comments in this report related to this system are made as a courtesy only and are not meant to be a substitute for a full evaluation by a qualified specialist. Water softeners typically work by removing unwanted minerals (e.g. calcium, magnesium) from the water supply. They prevent build-up of scale inside water supply pipes, improve lathering while washing, and prevent spots on dishes. Recommend consulting with the property owner about this system to determine its condition, required maintenance, age, expected remaining life, etc. For more information, visit:
http://www.reporthost.com/?WTRSFT
http://www.reporthost.com/?HRDWTR

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Near, at or beyond service life
Type: Tank
Energy source: Electricity
Estimated age: Old
Capacity (in gallons): 50
Temperature-pressure relief valve installed: Yes
Location of water heater: Basement
Hot water temperature tested: No
Condition of venting system: Appeared serviceable

36) The water heater did not have earthquake straps or struts installed. This is a potential safety hazard in the event of an earthquake due to the risk of the water heater tipping over, gas lines breaking if it's gas-fired, or electric wiring being damaged if powered by electricity. Leaks can also occur in water-supply pipes. Recommend that a qualified person install earthquake straps or struts as necessary and per standard building practices.

37) The estimated useful life for most water heaters is 8-12 years. This water heater appeared to be beyond this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.
Photo
Photo 37-1
Photo
Photo 37-2

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: unknown
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas, Propane
Estimated age of forced air furnace: unknown
Location of forced air furnace: Basement
Condition of furnace filters: Required washing or cleaning
Location for forced air filter(s): At base of air handler
Condition of forced air ducts and registers: Appeared serviceable
Condition of burners: Appeared serviceable
Type of combustion air supply: Intake duct, Vent(s) to exterior
Condition of venting system: Appeared serviceable
Condition of controls: Appeared serviceable

38) The last service date of the gas or oil-fired forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC contractor when it's serviced. For more information visit:
http://www.reporthost.com/?ANFURINSP

39) Recommend replacing or washing HVAC filters upon taking occupancy depending on the type of filters installed. Regardless of the type, recommend checking filters monthly in the future and replacing or washing them as necessary. How frequently they need replacing or washing depends on the type and quality of the filter, how the system is configured (e.g. always on vs. "Auto"), and on environmental factors (e.g. pets, smoking, frequency of house cleaning, number of occupants, the season).

40) The estimated useful life for most forced air furnaces is 15-20 years. The inspector was unable to determine the age of the furnace. Be aware that this furnace may be near, at, or beyond its useful life and may need replacing or significant repairs at any time. Recommend attempting to determine the furnace's age (ask property owner or service technician), and budgeting for a replacement if necessary.
Photo
Photo 40-1
 

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Natural gas, Propane
Type of ventilation: Wall or ceiling mounted fan
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: N/A (none installed)

41) The sink was damaged or significantly deteriorated. Recommend that a qualified contractor replace the sink.

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath
Condition of counters: Required repair, replacement and/or evaluation (see comments below)
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Windows
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: No

42) Countertops and/or backsplashes at location(s) #A were damaged or deteriorated. Recommend repairing or replacing as necessary.

43) Gaps, no caulk, or substandard caulking were found between the bathtub and the floor and/or walls at location(s) #A. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.

44) The bathtub at location(s) #A was worn, blemished or deteriorated.

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Required repair, replacement and/or evaluation (see comments below)
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below), broken window and also missing window in bedroom
Type(s) of windows: Vinyl
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Condition of concrete slab floor(s): Appeared serviceable
Flooring type or covering: Carpet
Condition of stairs, handrails and guardrails: Appeared serviceable

45) One or more exterior doors were significantly damaged or deteriorated. Recommend that a qualified person replace door(s) as necessary.
Photo
Photo 45-1
Photo
Photo 45-2

46) One or more exterior doors were difficult to open or close. Recommend that a qualified person repair as necessary.

47) No window screens were installed. Windows may not provide ventilation during months when insects are active.
Photo
Photo 47-1
 

48) Screens were missing from many windows. These windows may not provide ventilation during months when insects are active.


Photo
Photo X-1
Photo
Photo X-2
Photo
Photo X-3
Photo
Photo X-4
Photo
Photo X-5
Photo
Photo X-6
Photo
Photo X-7
Photo
Photo X-8
Photo
Photo X-9
Photo
Photo X-10
Photo
Photo X-11
Photo
Photo X-12
Photo
Photo X-13
Photo
Photo X-14
Photo
Photo X-15
Photo
Photo X-16
Photo
Photo X-17
Photo
Photo X-18
Photo
Photo X-19
Photo
Photo X-20
Photo
Photo X-21
Photo
Photo X-22
Photo
Photo X-23
Photo
Photo X-24
Photo
Photo X-25
Photo
Photo X-26
Photo
Photo X-27
Photo
Photo X-28
Photo
Photo X-29
Photo
Photo X-30
Photo
Photo X-31
Photo
Photo X-32
Photo
Photo X-33
Photo
Photo X-34
Photo
Photo X-35
Photo
Photo X-36
Photo
Photo X-37
Photo
Photo X-38
Photo
Photo X-39
Photo
Photo X-40
Photo
Photo X-41
Photo
Photo X-42
Photo
Photo X-43
Photo
Photo X-44
Photo
Photo X-45
Photo
Photo X-46
Photo
Photo X-47
Photo
Photo X-48
Photo
Photo X-49
Photo
Photo X-50
Photo
Photo X-51
Photo
Photo X-52
Photo
Photo X-53
Photo
Photo X-54
Photo
Photo X-55
Photo
Photo X-56
Photo
Photo X-57
Photo
Photo X-58
Photo
Photo X-59
Photo
Photo X-60
Photo
Photo X-61
Photo
Photo X-62
Photo
Photo X-63
Photo
Photo X-64
Photo
Photo X-65
Photo
Photo X-66
Photo
Photo X-67
Photo
Photo X-68
Photo
Photo X-69
Photo
Photo X-70
Photo
Photo X-71
Photo
Photo X-72
Photo
Photo X-73
Photo
Photo X-74
Photo
Photo X-75
Photo
Photo X-76
Photo
Photo X-77
Photo
Photo X-78
Photo
Photo X-79
Photo
Photo X-80
Photo
Photo X-81
Photo
Photo X-82
Photo
Photo X-83
Photo
Photo X-84
Photo
Photo X-85
Photo
Photo X-86
Photo
Photo X-87
Photo
Photo X-88
Photo
Photo X-89
Photo
Photo X-90
Photo
Photo X-91
Photo
Photo X-92
Photo
Photo X-93
Photo
Photo X-94
Photo
Photo X-95
Photo
Photo X-96
Photo
Photo X-97
Photo
Photo X-98
Photo
Photo X-99
Photo
Photo X-100
Photo
Photo X-101
Photo
Photo X-102
Photo
Photo X-103
Photo
Photo X-104
Photo
Photo X-105
Photo
Photo X-106
Photo
Photo X-107
Photo
Photo X-108
Photo
Photo X-109
Photo
Photo X-110
Photo
Photo X-111
Photo
Photo X-112
Photo
Photo X-113
Photo
Photo X-114
Photo
Photo X-115
Photo
Photo X-116
Photo
Photo X-117
Photo
Photo X-118
Photo
Photo X-119
Photo
Photo X-120
Photo
Photo X-121
Photo
Photo X-122
Photo
Photo X-123
Photo
Photo X-124
Photo
Photo X-125
Photo
Photo X-126
Photo
Photo X-127
Photo
Photo X-128
Photo
Photo X-129
Photo
Photo X-130
Photo
Photo X-131
Photo
Photo X-132
Photo
Photo X-133
Photo
Photo X-134
Photo
Photo X-135
Photo
Photo X-136
Photo
Photo X-137
Photo
Photo X-138
Photo
Photo X-139
Photo
Photo X-140
Photo
Photo X-141
Photo
Photo X-142
Photo
Photo X-143
Photo
Photo X-144
Photo
Photo X-145
Photo
Photo X-146

Your default report footer here...