Property Inspection Report
Client(s): J Rong
Property address: 6257 Friends Ave
Whittier, CA
Inspection date: Tuesday, August 04, 2009
This report published on 8/5/2009 8:57:38 AM PDT

View summary page

This report is the exclusive property of ALLISON CONSULTING GROUP and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Structural Pest Inspection Concerns
Items of concern relating to the structural pest inspection are shown as follows:
WDO/WDI InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
WDO/WDI DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
WDO/WDI Conducive
conditions
Conditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Crawl space
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Report number: 2009
Age of building: Built 1964
Time started: 0900
Time finished: 1200
Inspection Fee: 700.00
Payment method: Check
Present during inspection: Client(s), Property owner(s), Tenant(s), Realtor(s)
Occupied: Yes
Weather conditions: Clear
Temperature: Warm
Front of structure faces: South
Foundation type: Crawlspace, Slab on grade, Post and pier
The following items are excluded from this inspection: Security system, Irrigation system, Low voltage outdoor lighting, Built-in sound system, Intercom system
1)   Structures built prior to 1979 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client(s) should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit these websites:
  • The Environmental Protection Association (http://www.epa.gov)
  • The Consumer Products Safety Commission (http://www.cpsc.gov)
  • The Center for Disease Control (http://www.cdc.gov)
     
    Exterior Return to table of contents
    Footing material: Poured in place concrete
    Foundation material: Poured in place concrete, Post and pier
    Wall covering: Stucco
    Driveway material: Poured in place concrete
    Sidewalk material: Poured in place concrete
    Exterior door material: Solid core wood
    2)   Fire caulking missing from pipe penetration. Recommend repair by licensed contractor.


    *Overhead piping in garagr area*

    Photo 12  
     

    3) Cracks, deterioration and/or damage were found in one or more areas of the stucco siding. A qualified contractor should evaluate and make repairs and/or replace stucco siding as necessary.

    Photo 5  

    Photo 11  

    Photo 14  
     

    4)   Cracks, deterioration, leaning and/or bowing were found in one or more retaining walls. A qualified contractor should evaluate and repair or replace wall(s) as necessary.

    Photo 9  
     

    5)   The driveway has significant cracks and/or deterioration in one or more areas. A qualified contractor should evaluate and repair or replace driveway sections as necessary.

    Photo 10  
     

    6) Water stains on concrete indicate ponding issue in this area of the garage. Recommend sealing joint and verticle wall and concrete slab junction.

    Photo 15  
     

    7) One or more minor cracks (1/8 inch or less) were found in the foundation. These don't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitoring them in the future. Numerous products exist to seal such cracks including:
  • Hydraulic cement. Requires chiseling a channel in the crack to apply. See http://www.quickrete.com/catalog/HydraulicWater-StopCement.html for an example.
  • Resilient caulks (easy to apply). See http://www.quickrete.com/catalog/GrayConcreteRepair.html for an example.
  • Epoxy sealants (both a waterproof and structural repair). See http://www.mountaingrout.com/ for examples of these products.
    8) Trees and/or shrubs are in contact with or are close to the roof edge(s) in one or more areas. Damage to the roof may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.

    Photo 30  
     

    9)   Minor cracks were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
     
    Roof Return to table of contents
    Roof inspection method: Traversed
    Roof type: Flat
    Roof covering: Rolled
    Estimated age of roof: 5 years
    10) Nail protruding from underside of roof. This is a possible avenue for water intrusion. Recommend repair by livensed contractor.

    Photo 28  
     

    11)   Previous roof repairs noted.

    Photo 27  
     

    12) The coating on the flat roof has deteriorated and may result in a shortened service life. A qualified roofing contractor should apply a new roof coating now and as necessary in the future. Typically this is done every four to five years.

    Photo 29  
     
     
    Electric service Return to table of contents
    Primary service type: Overhead
    Primary service overload protection type: Circuit breakers
    Service amperage (amps): 400
    Service voltage (volts): 120/240
    Location of main service switch: South side
    Location of main disconnect: Breaker at bottom of main service panel
    Service entrance conductor material: Copper
    System ground: Ground rod(s) in soil, Cold water supply pipes
    Main disconnect rating (amps): 2002 - 200 amp breakers used for disconnect.
    Branch circuit wiring type: Non-metallic sheathed, Copper
    Solid strand aluminum branch circuit wiring present: No
    Smoke detectors present: Yes
    13)   One or more screws are missing from the main service panel cover and should be replaced. Because energized wiring may exist behind the holes with the missing screws, recommend that a qualified, licensed electrician replace these screws, or that care be taken to ensure that the new screws do not come in contact with wiring inside the panel when they are installed. Stock screws from the panel manufacturer should be used, or their equivalent.
    14)   Panel rating plate.

    Photo 3  
     

    15)     Electrical enclosure has dryrot present (consult termit report), debris present, telephone wiring in dissaray, abandones cable TV coax in disarray. Recommend replacement of enclosure by licensed contractor, repair and or removal of any abandoned wiring.

    Photo 1  

    Photo 2  

    Photo 4  
     
     
    Water heater Return to table of contents
    Estimated age: < 1 year
    Type: Tank
    Energy source: Natural gas
    Capacity (in gallons): 100 gal
    16)   Nomenclature plate for W/H.

    Photo 34  
     

    17)   W/H plumbing properly installed.

    Photo 31  

    Photo 32  

    Photo 33  
     
     
    Heating and cooling Return to table of contents
    Primary heating system energy source: Natural gas
    Primary heat system type: Fan assisted, in-wall units
     
    Plumbing and laundry Return to table of contents
    Location of main water shut-off valve: North side
    Location of main water meter: Street
    Location of main fuel shut-off: North side
    Water service: Public
    Service pipe material: Galvanized steel
    Supply pipe material: Galvanized steel
    Vent pipe material: Cast iron
    Drain pipe material: Galvanized steel
    Waste pipe material: Cast iron
    18)   Neither the clothes washer nor dryer were operated or evaluated. They are excluded from this inspection.
    19)   Water supply shut offnorth side.

    Photo 19  
     

    20)   Natural gas shut off north side.

    Photo 6  
     

    21)   Natural gas pressure regulator.

    Photo 7  
     

    22)   Natural gas meters.

    Photo 8  
     
     
    Crawl space Return to table of contents
    Inspection method: Partially traversed, Viewed from hatch
    Insulation material underneath floor above: None visible
    Pier or support post material: Wood, Bearing wall, Concrete
    Beam material: Solid wood
    Floor structure above: Solid wood joists
    Vapor barrier present: No
    23)   No insulation is installed under the floor in the crawl space. Recommend that a qualified contractor install R19 or better (6" thick fiberglass batt) insulation under the floor for better energy efficiency.

    Photo 17  
     

    24) Evidence of prior water intrusion was found in one or more sections of the crawl space. For example, sediment stains on the vapor barrier or foundation, and/or efflorescence on the foundation. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the crawl space. The client(s) should review any disclosure statements available and ask the property owner(s) about past accumulation of water in the crawl space. The crawl space should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in crawl spaces include:

  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains

    Ideally, water should not enter crawl spaces, but if water must be controlled after it enters the crawl space, then typical repairs include installing trenches, gravity drains and/or sump pump(s) in the crawl space.

    Photo 18  
     

    25) No vapor barrier is installed. This is a conducive condition for wood destroying insects and organisms due to the likelihood of water evaporating into the structure from the soil. A qualified contractor should install a vapor barrier. Standard building practices require the following:

  • The soil below the vapor barrier should be smooth and free from sharp objects.
  • Seams should overlap a minimum of 12 inches.
  • The vapor barrier should lap up onto the foundation side walls.

    Better building practices require that:

  • Seams and protrusions should be sealed with a pressure sensitive tape.
  • The vapor barrier should be caulked and attached tightly to the foundation side walls. For example, with furring strips and masonry nails.
    26)   Water supply pipes are uninsulated. Recommend insulating pipes as necessary for better energy efficiency and to prevent water pipes from freezing.
    27)   Post , peer, and cross bracing functional. Sewer drain has corrosion present.

    Photo 16  
     
     
    Kitchen Return to table of contents

    28)   One or more faucets leak or drip when turned off. A qualified plumber should evaluate and repair as necessary.
    29)   One or more faucet handles are loose or missing and should be repaired or replaced as necessary.

    Replace kitchen faucet in Apt G.

    30) One or more sink drains leak.


    Apt. E
     
    Bathrooms Return to table of contents

    31) One or more sink drains have an active leak. For example, at pipe fittings and/or junctions between pipe and sink. A qualified plumber should evaluate and repair as necessary.
    32)   One or more faucet handles are loose or missing and should be repaired or replaced as necessary.


    Apt C.

    33)   One or more bathtub drains are clogged or drain slowly. Drain(s) should be cleared as necessary, and by a qualified plumber if necessary.


    Apt A.

    Apt H.

    34) Rust and mildew present in tub. Caulking deteriorated. Recommend evaluation and repair by licensed contractor.

    Photo 23  
    Apt B.
     

    35) Improper sealingof hot and cold water valves. Valves not properly secured to framing behind wall. Recommend reapir by licensed contractor.

    Photo 24  
    Apt D.
     

    36) Caulk is missing or deteriorated along the base of one or more bathtubs, where flooring meets the tub. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the floor structure.
    37) Ceramic tile crack at window ledge.

    Photo 21  
    Apt C.
     

    38)   The enamel coating on one or more bathtubs is damaged and/or deteriorated. For example, chipped or worn, and/or rust on some exposed steel. However, no leaks were found due to the deterioration. The client(s) should evaluate to determine if the bathtub(s) should be refinished or replaced.

    Photo 20  
     
     
    Interior rooms Return to table of contents

    39)   Some ceiling areas in this structure have "popcorn" textured surfaces possibly installed prior to 1979. This material may contain asbestos, which is a known carcinogen and poses a health hazard. Laws were passed in the United States in 1978 prohibiting use of asbestos in residential structures, but stocks of existing materials have been known to be used for some time thereafter. The client(s) may wish to have this ceiling material tested by a qualified lab to determine if it does contain asbestos.

    In most cases, when the material is intact and in good condition, keeping it encapsulated with paint and not disturbing it may reduce or effectively eliminate the health hazard. If the client wishes to remove the material, or plans to disturb it through remodeling, they should have it tested by a qualified lab and/or consult with a qualified industrial hygienist or asbestos abatement specialist. For more information, visit: http://www.cpsc.gov/CPSCPUB/PUBS/453.html

    40)   Cracks in popcorn cieling coating common through out structure.

    Photo 25  
     

    41)   Stain present at ceiling o living room. Previous repair noted, this appears to be a crrent problem. No evidence recent roof repair above area. Recommend repair by licensed contractor.

    Photo 26  
    Apt H.
     

    42)   Cracks noted at wall in bedroom. recommend repair by licensed contractor.

    Photo 22  
     

    43)   Minor cracks were found in walls in one or more areas. They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.
     