The objective of this report is to provide the client with reliable and accurate information on the various systems that make up the building envelope that is your home. This information is gathered by conducting a visual inspection that will meet or exceed the standards set forth by the State of Oklahoma in Title 158 Construction Industries Board Chapter 70 of the Home Inspection Industry Regulations. This report is intended for the exclusive use of the Contracted Client and Aardvark Home Inspection and Services.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a safety hazard
Concern typeMajor DefectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor DefectCorrection likely involves only a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
Grounds
Exterior and Foundation
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
General Information
Crawl Space
Basement
Wood Destroying Organism Findings

View summary


Grounds
Return to table of contents

Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
The home sets on the top of a small hill:
Site profile: Moderate slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Gravel
Condition of sidewalks and/or patios: Required repairs, replacement and/or evaluation (see comments below)
Sidewalk material: Stones
Condition of decks, porches and/or balconies: Appeared serviceable
Deck, porch and/or balcony material: Concrete
Condition of stairs, handrails and guardrails: Required repairs, replacement and/or evaluation (see comments below), back porch handrail rotted, replace
Exterior stair material: Concrete

1) Hand Rail on rear porch seems to have rotted wood and has separated from the stairs. As per IRC and local standards handrails are required when there are 4 or more risers including the bottom and top risers.
Photo
Photo 1-1
Seriously dangerous rotted handrail. This should be replaced immediately.
Photo
Photo 1-2
Seriously rotted upright support for the rotten handrail.

2) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the sidewalks or patios. For safety reasons, recommend that a qualified contractor repair as necessary to eliminate trip hazards.

3) evidence of standing water along the perimeter of the foundation wall. water infiltration into the basement/crawl space is possible.
Photo
Photo 3-1
Evidence of moisture retention at the footing.
 

Exterior and Foundation
Return to table of contents

Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Wall inspection method: Viewed from ground, from a ladder
Condition of wall exterior covering: Required repairs, replacement and/or evaluation (see comments below), some of the exterior siding on south side faded
Apparent wall structure: Wood frame
Condition of foundation and footings: Required repairs, replacement and/or evaluation (see comments below), Not determined, shearing of foundation block at fireplace
Apparent foundation type: Crawl space, Unfinished basement
Footing material (under foundation stem wall): Poured in place concrete

4) Major cracks (more than 3/4-inch wide) and/or leaning was found in the foundation. These appear to be a structural concern and may indicate that settlement is ongoing. Recommend hiring qualified contractors and/or engineers as necessary for further evaluation. Such contractors may include:
  • Foundation repair contractors who may prescribe repairs, and will give cost estimates for such repairs
  • Masonry contractors who repair and/or replace brick veneer
  • Geotechnical engineers who attempt to determine if settlement is ongoing, and the cause of the settlement
  • Structural engineers who determine if repairs are necessary, and prescribe those repairs
Repairs should be made by a qualified contractor.
Photo
Photo 4-1
Crack with differential settlement on the west side of the fireplace chimney. Other evidence shows some cracks in the mortar of the fireplace chimney.
 

5) the concrete block foundation Has cracked and has begun a differential settling on the lower south side of the fireplace.

6)   evidence of water penetrating the exterior foundation wall on the northwest side with a green algae growth.
Photo
Photo 6-1
Evidence of moisture wicking into the porous surface of the concrete wall. The green is an algae type of growth.
 

Roof
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Required repair, replacement and/or evaluation (see comments below)
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable, Hipped
Apparent number of layers of roof surface material: One
Condition of exposed flashings: Appeared serviceable
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)

7) The roof surface appeared to be near the end of its service life and will likely need replacing in the near future even if repairs are made now. Recommend discussing replacement options with a qualified contractor, and budgeting for a replacement roof surface in the near future. The client may also wish to consider having a qualified contractor attempt to issue a "5 year roof certificate."

8) areas of the roof are missing shingles with edges of the deck exposed.
Photo
Photo 8-1
Photo
Photo 8-2
Photo
Photo 8-3
 

9) Flashings at the base of one or more chimneys were loose and/or damaged. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.
Photo
Photo 9-1
 

10) Many composition shingles were missing. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.
Photo
Photo 10-1
Photo
Photo 10-2
Photo
Photo 10-3
Photo
Photo 10-4

11) Extensions such as splash blocks or drain pipes for one or more downspouts were damaged. Water can accumulate around the building foundation or inside crawl spaces or basements as a result. Recommend that a qualified person install, replace or repair extensions as necessary so rainwater drains away from the structure.
Photo
Photo 11-1
Damaged down spout extension. Water should be directed away from the foundation.
 

12) counter flashing has pulled away from the chimney.

13) the gutter has pulled away from the fascia board with spikes and ferrells hanging.
Photo
Photo 13-1
Gutter pulling away from the fascia. Both nails and ferrells have pulled free.
Photo
Photo 13-2
Gutter pulling away from the fascia.
Photo
Photo 13-3
 

14) One or more gutters and/or downspouts were loose and/or damaged. Rainwater can come in contact with the building exterior or accumulate around the building foundation as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.

Attic and Roof Structure
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Partially traversed
Condition of roof structure: Required repair, replacement and/or evaluation (see comments below)
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.): Required repair, replacement and/or evaluation (see comments below)
Ceiling insulation material: Fiberglass loose fill
Approximate attic insulation R value (may vary in areas): Not determined (inaccessible or obscured)
Vapor retarder: None visible
Condition of roof ventilation: Required repair, replacement and/or evaluation (see comments below)
Roof ventilation type: Box vents (roof jacks), Enclosed soffit vents

15) The ceiling insulation in one or more areas of the attic was compacted or uneven, missing and/or substandard. Heating and cooling costs may be higher due to reduced energy efficiency. Recommend that a qualified person repair, replace or install insulation as necessary and per standard building practices (typically R-38).

16) One or more attic access hatches or doors were not insulated, or had substandard insulation. Recommend installing insulation as necessary and per current standards at hatches or doors for better energy efficiency. For more information, visit:
http://www.reporthost.com/?ATTACC

17) One or more attic or roof vent screens were clogged with paint. This can reduce air flow through the roof structure or attic and result in reduced service life for the roof surface materials because of high temperatures. Moisture from condensation is also likely to accumulate in the roof structure and/or attic. Recommend that a qualified person repair as necessary so air flows freely through all vents. For example, by cleaning screens or replacing screens with 1/8-inch to 1/4-inch wire mesh.

18) One or more sections of the roof structure appeared to have substandard ventilation, there were too few vents. This can result in high attic and roof surface temperatures, reduce the life of the roof covering materials, and/or increase cooling costs. High levels of moisture are also likely to accumulate in the roof structure or attic, and can be a conducive condition for wood-destroying organisms. Standard building practices require one free square foot of ventilation for every 150 square feet of attic space, and that vents be evenly distributed between the lowest points of the roof structure and the highest points to promote air circulation. Often this means that both soffit vents and ridge or gable end vents are installed. Recommend that a qualified contractor evaluate and repair per standard building practices.

19) The home has had multiple phases of construction and some of the framing is questionable and should be evaluated.

20) insulation has compressed and the R value is greatly reduced. Recommend evaluation by a qualified contractor

Garage or Carport
Return to table of contents

Limitations: The inspector cannot reasonably determine the integrity of all elements of limited fire resistance at residential construction or verify firewall ratings at multi unit construction. Requirements for ventilation in garages vary between municipalities.
Type: Detached
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Roll
Number of vehicle doors: 2
Condition of garage floor: Appeared serviceable
Condition of garage interior: Appeared serviceable
Garage ventilation: Inadequate

21) The frame of the exterior wall shows signs of weathering and water damage. The siding has deteriorated to the point of allowing pests and vermin to infiltrate the space.

22) The carport structure was unstable due to missing or substandard bracing or attachment to the main building. This is a potential safety hazard since severe movement may cause it to collapse. A qualified contractor should repair as necessary.

23) One or more garage vehicle doors weren't balanced. The door(s) wouldn't stay in place when opened half-way, and fell to the ground instead. This is a potential safety hazard since the door(s) can fall when open and cause injury. A qualified contractor should repair as necessary. For more information on garage door safety issues, visit:
http://www.reporthost.com/?GDBAL

Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Underground
Number of service conductors: 3
Estimated service amperage: 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 200
System ground: Not determined, not readily apparent
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Building exterior
Location of main disconnect: Breaker at top of main service panel
Condition of branch circuit wiring: Serviceable
Branch circuit wiring type: non-metallic sheathed
Ground fault circuit interrupter (GFCI) protection present: No
Arc fault circuit interrupter (AFCI) protection present: No

24) One or more electric receptacles at the kitchen, bathroom(s) and/or laundry area had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
  • Outdoors (since 1973)
  • Bathrooms (since 1975)
  • Garages (since 1978)
  • Kitchens (since 1987)
  • Crawl spaces and unfinished basements (since 1990)
  • Wet bar sinks (since 1993)
  • Laundry and utility sinks (since 2005)
For more information, visit:
http://www.reporthost.com/?GFCI

25) One or more receptacles were worn. Worn receptacles can work intermittently or when the plug is wiggled. They can overheat or arc and spark due to loose connections. This is a potential fire hazard. Recommend that a qualified electrician replace such receptacles as necessary.

26) The light fixture at one or more sets of stairs with living spaces at both ends was controlled by a single switch at one end. This is a safety hazard due to inadequate lighting. The light should be controlled by 3-way switches at the top and bottom of the stairs so it can be easily operated on both floors. Recommend that a qualified electrician repair per standard building practices.

27) One or more electric receptacles at the bedroom(s), kitchen, family room, dining room, living room, hallway(s) and/or laundry area had no visible arc fault circuit interrupter (AFCI) protection, or the inspector was unable to determine if AFCI protection was present. This is a potential safety hazard. Recommend that a qualified electrician evaluate and install AFCI protection if necessary and per standard building practices. General guidelines for AFCI-protected receptacles include the following locations:
  • Bedrooms (since 1999)
  • Kitchens, laundry areas, family rooms, dining rooms, living rooms, parlors, libraries, dens and recreation rooms, sunrooms, closets and hallways (since 2014)
For more information, visit:
http://www.reporthost.com/?AFCI

28) Smoke alarms were missing from one or more bedrooms. Smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM

29) One or more cover plates for switches, receptacles or junction boxes were missing or broken. These plates are intended to contain fire and prevent electric shock from occurring due to exposed wires. Recommend that a qualified person install cover plates where necessary.

Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Water service: Public
Location of main water shut-off: Building exterior
Condition of supply lines: Appeared serviceable
Supply pipe material: CPVC plastic, PVC plastic
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Near, at or beyond service life
Waste pipe material: Lead
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Sump pump installed: Yes
Condition of sump pump: Required repairs, replacement and/or evaluation (see comments below)

30) Insulation for one or more water supply pipes in the crawl space and/or basement was missing. Recommend replacing or installing insulation on pipes per standard building practices to prevent them from freezing during cold weather, and for better energy efficiency with hot water supply pipes.

31) The inspector heard gurgling sounds when plumbing fixtures (e.g. faucets, tubs, showers) were operated. Venting may be substandard or missing. Adequate venting is required to allow waste materials and water to drain freely, and to allow sewer gases to escape from the system. Recommend that a qualified plumber evaluate and repair if necessary.

32) The sump pump appeared to be inoperable. Water may accumulate in the building substructure during periods of heavy rain. Recommend that a qualified contractor evaluate and repair or replace the sump pump as necessary.

33) One or more plastic PVC or CPVC water supply pipes had substandard support or were loose. Leaks may occur as a result. PVC and CPVC supply pipes should have supports every 4 feet. Special hangers that allow movement from expansion and that won't damage the soft plastic piping should be used. Recommend that a qualified person install supports or secure pipes per standard building practices.

34) The inspector was unable to determine the output location for the sump pump's discharge pipe. Consult with the property owner or evaluate further to determine the location of the sump pump discharge pipe. Discharge pipes should terminate well away from foundations to soil sloping down and away so water doesn't accumulate around the foundation or in crawl spaces or basements. If it does terminate close to the foundation, recommend that a qualified person repair per standard building practices.

Water Heater
Return to table of contents

Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Appeared serviceable
Type: Tank
Energy source: Electricity
Capacity (in gallons): 50
Location of water heater: Basement
Hot water temperature tested: No

35)   water tank was manufactured in 2012

Heating, Ventilation and Air Condition (HVAC)
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air, Heat pump
General heating distribution type(s): Ducts and registers
Last service date of primary heat source: 2013
Source for last service date of primary heat source: Property owner
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Electric
Location of forced air furnace: Closet
Forced air system capacity in BTUs or kilowatts: 40000 btus
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At top of air handler
Condition of forced air ducts and registers: Required repair, replacement and/or evaluation (see comments below)
Type of combustion air supply: Vent(s) to exterior
Condition of venting system: Appeared serviceable
Condition of cooling system and/or heat pump: Appeared serviceable
Cooling system and/or heat pump fuel type: Electric
Location of heat pump or air conditioning unit: west
Condition of controls: Appeared serviceable

36) The estimated useful life for most heat pumps and air conditioning condensing units is 10-15 years. This unit appeared to be near this age and/or its useful lifespan and may need replacing or significant repairs at any time. Recommend budgeting for a replacement in the near future.

37) The last service date of the forced air heating/cooling system appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than 1 year ago, recommend that a qualified HVAC contractor service this system and make repairs if necessary. Because this system has a compressor and refrigerant system, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the contractor when it's serviced.

38) ducts are compressed in the attic laying on top of each other.

39) One or more sections of flex duct used for heating or cooling were sagging or had substandard support. Energy efficiency can be reduced due to restricted flow. Manufacturers typically recommend that flex duct be supported with the following guidelines:
  • Ducts should not sag more than 1/2 inch every foot between supports
  • Support straps should be spaced no farther apart than 5 feet
  • Support straps should be soft, webbed nylon and at least 1 1/2 inches wide
Recommend that a qualified person repair per the manufacturer's specifications.

40) Insulation on the heat pump or air conditioning condensing unit's refrigerant lines was deteriorated or missing in some areas. This may result in reduced efficiency and increased energy costs. Recommend that a qualified person replace or install insulation as necessary.

Fireplaces, Stoves, Chimneys and Flues
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Required repair, replacement and/or evaluation (see comments below)
Wood-burning fireplace type: Masonry with metal liner
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Masonry

41) One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA

42) Soot deposits were found above the fireplace. This often indicates an inadequate draw, and can be caused by a variety of problems including an incorrect chimney configuration or a chimney blocked by creosote or debris. Recommend that a qualified chimney service contractor evaluate and repair or perform maintenance as necessary.

43) Mortar at the brick chimney was deteriorated (e.g. loose, missing, cracked). As a result, water is likely to infiltrate the chimney structure and cause further damage. Recommend that a qualified contractor repair as necessary. For example, by repointing the mortar.

Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of under-sink food disposal: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of ranges, cooktops and/or ovens: Appeared serviceable
Type of ventilation: Hood or built into microwave over range or cooktop
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable

Bathrooms, Laundry and Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Full bath, Master bath
Location #B: Full bath
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom and laundry ventilation type: Spot exhaust fans
Gas supply for laundry equipment present: No
240 volt receptacle for laundry equipment present: Yes

44) Gaps, no caulk, or substandard caulking were found between the bathtub and the walls at location(s) #A and B. Water may penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.

45) Gaps, no caulk, or substandard caulking were found between the shower enclosure and the floor and/or walls at location(s) #A. Water can penetrate these areas and cause damage. Recommend that a qualified person re-caulk or install caulking as necessary.

46) Caulk around the base of the toilet at location(s) #A and B was missing, substandard and/or deteriorated. Modern standards require caulk to be installed around the entire toilet base where it meets the floor for sanitary reasons. Without it, soiled water can soak into flooring and sub-floor materials if the toilet overflows. Condensation from the toilet can also soak into the flooring. Recommend that a qualified person caulk around toilet bases per standard building practices.

47) The sink at location(s) #A and B was worn, blemished or deteriorated.

48) The bathtub at location(s) #B was worn, blemished or deteriorated.

Interior, Doors and Windows
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Wood
Condition of interior doors: Appeared serviceable
Condition of windows and skylights: Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows: Metal
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
Condition of flooring: Appeared serviceable
Flooring type or covering: Carpet, Wood or wood products

49) Condensation or staining was visible between multi-pane glass in one or more windows. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's U-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.

old aluminum windows.

50) One or more entry doors wouldn't latch when closed. This is a security concern if no deadbolt is installed. A qualified person should repair as necessary.

51) Some exterior door hardware, including locksets and/or deadbolts were inoperable. Recommend that a qualified person repair or replace as necessary.

52) One or more window screens were damaged or deteriorated. These window(s) may not provide ventilation during months when insects are active. Recommend replacing window screens as necessary.

53) One or more interior doors wouldn't latch or were difficult to latch. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets.

54) Minor cracks, nail pops and/or blemishes were found in walls and/or ceilings in one or more areas. Cracks and nail pops are common, are often caused by lumber shrinkage or minor settlement, and can be more or less noticeable depending on changes in humidity. They did not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons. For recurring cracks, consider using an elastic crack covering product:
http://www.reporthost.com/?ECC

55) Carpeting in one or more areas was significantly stained or soiled. Recommend having carpeting professionally cleaned as necessary.

56) One or more exterior doors had minor damage and/or deterioration. Although serviceable, the client may wish to repair or replace such doors for appearances' sake.

General Information
Return to table of contents

Report number: 2
Present during inspection: Client, Property owner
Client present for discussion at end of inspection: Yes
Weather conditions during inspection: Dry (no rain), Windy, Sunny
Temperature during inspection: Hot
Inspection fee: 0.00
Payment method: Cash
Type of building: Single family
Buildings inspected: One house, One detached garage
Number of residential units inspected: 1
Age of main building: 60
Source for main building age: Property owner, Inspector's estimate
Front of building faces: West
Main entrance faces: West
Occupied: Yes, Furniture or stored items were present

57) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC

58) Based on non-standard construction observed, modifications to this property may have been made without the owner having attained permits or inspections from the municipality. Work may have been performed by someone other than a qualified contractor or person. Consult with the property owner about this, and if necessary research permits.

At worst case, if substantial work was performed without permits, this knowledge must be disclosed when the building is sold in the future. This can adversely affect future sales. Also, the local municipality could require costly alterations to bring the building into legal compliance or even require that the additions or modifications be removed.

59) Many areas and items at this property were obscured by furniture. This often includes but is not limited to walls, floors, windows, inside and under cabinets, under sinks, on counter tops, in closets, behind window coverings, under rugs or carpets, and under or behind furniture. Areas around the exterior, under the structure, in the garage and in the attic may also be obscured by stored items. The inspector in general does not move personal belongings, furnishings, carpets or appliances. When furnishings, stored items or debris are present, all areas or items that are obscured, concealed or not readily accessible are excluded from the inspection. The client should be aware that when furnishings, stored items or debris are eventually moved, damage or problems that were not noted during the inspection may be found.

Crawl Space
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.
Crawl space inspection method: Partially traversed, a substantial portion was unavailable for viewing. sealed off.
Condition of floor substructure above: Required repairs, replacement and/or evaluation (see comments below), support
Pier or support post material: Concrete block
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Condition of vapor barrier: Not applicable, none installed
Vapor barrier present: None visible
Condition of crawl space ventilation: Required repairs, replacement and/or evaluation (see comments below)
Ventilation type: Unconditioned space, with vents

60) One or more support posts appear to have been added since the original construction based on the inspector's observations. Such posts may have been added to reduce bounce or sag in floors above. Consult with the property owner about this, or have a qualified contractor evaluate and make repairs if necessary.
Photo
Photo 60-1
Photo
Photo 60-2
Photo
Photo 60-3
 

61) No under-floor insulation was installed in the crawl space and/or unheated basement. Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.

62) The vapor barrier in many areas of the crawl space was missing. Soil was exposed as a result and will allow water from the soil to evaporate up into the structure. This is a conducive condition for wood-destroying organisms. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified person replace or repair the vapor barrier where necessary and per standard building practices.

63) No vapor barrier was installed in the crawl space. This is a conducive condition for wood-destroying organisms due to the likelihood of water evaporating from the soil below up into the structure. A 6 mil black plastic sheet should be placed over all exposed soil with seams overlapped to 24 inches, and not in contact with any wood structural components. The sheeting should be held in place with bricks or stones, not wood. Recommend that a qualified contractor install a vapor barrier per standard building practices.
Photo
Photo 63-1
 

64) One or more exhaust ducts (e.g. bathroom fan, clothes dryer) in the attic were not insulated. This can result in moisture forming inside the duct or "sweating" on the outside of the duct depending on the surrounding air temperature and the exhaust air temperature. Recommend that a qualified person install insulation on exhaust ducts per standard building practices (typically R-4 rating), or replace uninsulated ducts with insulated ducts.

65) One or more crawl space vents were intentionally blocked (e.g. removable panels, rigid foam). This restricts ventilation in the crawl space and can result in increased levels of moisture inside. This is a conducive condition for wood-destroying organisms. Such vents should be left open at all times except during severe freezing weather. Recommend removing materials or items blocking vents as necessary.

66) Trash, debris, and piles of dirt located in crawl space areas. Should be removed in order to facilitate repairs and inspections on interior components.
Photo
Photo 66-1
 

67)   One or more indoor crawl space access hatches or doors were not insulated, or had substandard insulation. Weatherstripping was also missing or substandard. Recommend installing weatherstripping and insulation per current standards at hatches or doors for better energy efficiency and to prevent dust or odor-laden air from the crawl space entering living spaces.

Basement
Return to table of contents

Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity.
Condition of floor substructure above: Required repairs, replacement and/or evaluation (see comments below), water damage to floor joist
Pier or support post material: Bearing wall, Concrete block
Beam material: Solid wood
Floor structure above: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed

68) one of the support piers is tilted and appears to be absent of a concrete footing under the piers.

69) The ceiling height over stairs at one or more locations was too low and poses a safety hazard, especially for tall people. Ceilings over stairs should be at least 6 feet 8 inches high. At a minimum, be aware of this hazard, especially when guests who are not familiar with the stairs are present. Recommend that a qualified contractor repair per standard building practices.

70) sections of the crawl space were sealed off from view due to the foundation vents being sealed and access doors being locked.

71) Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains or rust at support post bases, efflorescence on the foundation, etc. Accumulated water is a conducive condition for wood-destroying organisms and should not be present in the basement. Recommend reviewing any disclosure statements available and ask the property owner about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, then recommend that a qualified contractor who specializes in drainage issues evaluate and repair as necessary. Typical repairs for preventing water from accumulating in basements include:
  • Repairing, installing or improving rain run-off systems (gutters, downspouts and extensions or drain lines)
  • Improving perimeter grading
  • Repairing, installing or improving underground footing and/or curtain drains
Ideally, water should not enter basements, but if water must be controlled after it enters the basement, then typical repairs include installing a sump pump.
Photo
Photo 71-1
Photo
Photo 71-2
Photo
Photo 71-3
Photo
Photo 71-4
Photo
Photo 71-5
Drain hose from a basement portable sump pump extending from the basement window.
 

72) Fungal rot was found at one or more sill plates and/or joists. Recommend that a qualified contractor evaluate and repair as necessary. All rotten wood should be replaced.

73) One or more support posts were not positively secured to the beam above. While this is common in older homes, current standards require positive connections between support posts and beams above for earthquake reinforcement. Recommend that a qualified contractor repair per standard building practices. For example, by installing metal plates, plywood gussets or dimensional lumber connecting posts and beams.

74) The basement floor drain appeared to be clogged. Water may accumulate in the basement as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person evaluate and clean, repair or replace as necessary.

75) One or more support posts appear to have been added since the original construction based on the inspector's observations. Such posts may have been added to reduce bounce or sag in floors above. Consult with the property owner about this, or have a qualified contractor evaluate and make repairs if necessary.

Wood Destroying Organism Findings
Return to table of contents

Limitations: This report only includes findings from accessible and visible areas on the day of the inspection. In addition to the inaccessible areas documented in this report, examples of other inaccessible areas include: sub areas less than 18 inches in height; attic areas less than 5 feet in height, areas blocked by ducts, pipes or insulation; areas where locks or permanently attached covers prevent access; areas where insulation would be damaged if traversed; areas obscured by vegetation. All inaccessible areas are subject to infestation or damage from wood-destroying organisms. The inspector does not move furnishings, stored items, debris, floor or wall coverings, insulation, or other materials as part of the inspection, nor perform destructive testing. Wood-destroying organisms may infest, re-infest or become active at any time. No warranty is provided as part of this inspection.

This report includes only the building/buildings and systems of those buildings as prescribed by the State of Oklahoma Title 158 Construction Industries Board Chapter 70 Home Inspection Industry Regulations. Additional buildings or systems will be visually inspected as agreed to by contract.

This report excludes all buildings and systems of those same buildings as prescribed by the State of Oklahoma Title 158 Construction Industries Board Chapter 70 Home Inspection Regulation.

These regulations may be viewed at cib.ok.gov.

Aardvark Home Inspection and Services appreciates the opportunity inspect your home. Our never ending goal is to exceed your expectations in a friendly, knowledgeable and professional manner.