Property Inspection Report
Client(s):  Linda Hammontree
Property address:  21575 SW Augusta St Aloha, Oregon
Inspection date:  Sunday, December 08, 2013

This report published on Sunday, December 08, 2013 5:18:21 PM PST

View summary

[b] “THIS REPORT IS INTENDED ONLY FOR THE USE OF THE PERSON PURCHASING THE HOME INSPECTION SERVICES. NO OTHER PERSON, INCLUDING A PURCHASER OF THE INSPECTED PROPERTY WHO DID NOT PURCHASE THE HOME INSPECTION SERVICES, MAY RELY UPON ANY REPRESENTATION MADE IN THE REPORT.”[b]

Oregon Inspections LLC CCB#199806 Inspector License #1614

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a safety hazard 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
CommentFor your information 

Wood Destroying Organism Concerns
Concerns relating to wood destroying organisms are shown as follows:
InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.) 
DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.) 
Conducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.) 

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior and Foundation
Crawl Space
Roof
Attic and Roof Structure
Garage or Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating, Ventilation and Air Condition (HVAC)
Fireplaces, Stoves, Chimneys and Flues
Kitchen
Bathrooms, Laundry and Sinks
Interior, Doors and Windows
Additional Photos


 
General Information Return to table of contents
Report number: 13-12072013
Time started: 10:30
Time finished: 12:30
Present during inspection: Client
Weather conditions during inspection: Dry (no rain)
Temperature during inspection: Cold
Inspection fee: 300
Payment method: Check
Type of building: Duplex
Buildings inspected: One house
Number of residential units inspected: 1
Front of building faces: East
Main entrance faces: East
Occupied: No
1) Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement specialists for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.reporthost.com/?EPA
http://www.reporthost.com/?CPSC
http://www.reporthost.com/?CDC
 
Grounds Return to table of contents
Limitations: Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.
Site profile: Minor slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Poured in place concrete
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Deck, porch and/or balcony material: Wood
2) One or more deck or porch beams were not positively secured to the support posts below. Decks and porches are subject to movement under live loads and require a positive connection between their support posts and beams. Recommend that a qualified contractor repair per standard building practices. For example, by installing metal plates, plywood gussets or dimensional lumber to connect posts and beams.

See the IRC Chapter 5 for post to beam gusset diagram.


Photo 38  
Front of home
 

3) Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the driveway, For safety reasons, recommend that a qualified contractor repair as necessary.
 
Exterior and Foundation Return to table of contents
Limitations: The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.
Condition of wall exterior covering: Appeared serviceable
Apparent wall structure: Wood frame
Wall covering: Wood
Apparent foundation type: Crawl space
Foundation/stem wall material: Poured in place concrete
Footing material (under foundation stem wall): Poured in place concrete
4) Flashing at one or more locations was missing. Leaks can occur as a result. Recommend that a qualified person repair, replace or install flashing as necessary, and per standard building practices.

Chimney at eves and roof connection of attached garden shed.

Permits were not obtained for this shed likely as many non code conforming conditions exist.

5) Soil was in contact with or less than 6 inches from siding, trim or structural wood. This is a conducive condition for wood-destroying organisms. Recommend grading or removing soil as necessary to maintain a 6-inch clearance. If not possible, then recommend replacing untreated wood with pressure-treated wood. Installation of borate-based products such as Impel rods can also reduce the likelihood of rot or infestation if soil cannot be removed. Note that damage from fungal rot and/or insects may be found when soil is removed, and repairs may be necessary.

Photo 12  
Need 6" clearance to the siding.

Photo 20  
Vegetation close to siding.

6) Fence(s) were attached to or in contact with the building exterior. Such attachments can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary so there is at least a 2-inch gap between fences and building exteriors.

Photo 39  
Fence attached to home.
 

7) One or more minor cracks (1/8 inch or less) were found in the foundation. These didn't appear to be a structural concern, but recommend sealing them to prevent water infiltration and monitor them in the future. Numerous products exist to seal such cracks including hydraulic cement, non-shrinking grout, resilient caulks and epoxy sealants.
8) Vegetation such as trees, shrubs and/or vines was in contact with or close to the building exterior. Vegetation can serve as a pathway for wood-destroying insects and can retain moisture against the exterior after it rains. This is a conducive condition for wood-destroying organisms. Recommend pruning, moving or removing vegetation as necessary to maintain at least 6 inches of space between it and the building exterior. A 1-foot clearance is better.

Photo 20  
Vegetation close to siding.
 

9) The paint or stain finish in some areas was failing (e.g. peeling, faded, worn, thinning). Siding and trim with a failing finish can be damaged by moisture.Recommend that a qualified contractor prep (e.g. clean, scrape, sand, prime, caulk) and repaint or restain the building exterior where necessary and per standard building practices. Any repairs needed to the siding or trim should be made prior to this.

Photo 36  
Provide exterior caulking here.

Photo 43  
Flashing and sealing at chimney is substandard.

10) Caulk was in some areas. For example, at siding butt joints, at siding-trim junctions, chimney. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
http://www.reporthost.com/?CAULK
 
Crawl Space Return to table of contents
Limitations: Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.

The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so.

The inspector attempts to locate all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings or stored items. In such cases, the client should ask the property owner where all access points are that are not described in this inspection, and have those areas inspected. Note that crawl space areas should be checked at least annually for water intrusion, plumbing leaks and pest activity.

Crawl space inspection method: Traversed
Condition of floor substructure above crawl space: Appeared serviceable
Pier or support post material: Wood
Beam material: Solid wood
Floor structure: Solid wood joists
Condition of insulation underneath floor above: Not applicable, none installed
Insulation material underneath floor above: None visible
Condition of vapor barrier: Appeared serviceable
Vapor barrier present: Yes
Condition of crawl space ventilation: Appeared serviceable
Ventilation type: Unconditioned space, with vents
11) One or more indoor crawl space access hatches or doors were not insulated, or had substandard insulation. Recommend installing insulation as necessary and per current standards at hatches or doors for better energy efficiency.
12) No insulation was installed under the floor above the . Recommend that a qualified person install insulation for better energy efficiency and per standard building practices. Typically this is R-19 rated fiberglass batt with the attached facing installed against the warm (floor) side.

Photo 4  
Gussets not on post and beam connections.

Photo 9  
No gusset as required.

13) One or more crawl space vents were intentionally blocked (e.g. removable panels, rigid foam). This restricts ventilation in the crawl space and can result in increased levels of moisture inside. This is a conducive condition for wood-destroying organisms. Such vents should be left open at all times except during severe freezing weather. Recommend removing materials or items blocking vents as necessary.
14)   One or more indoor crawl space access hatches or doors were not insulated, or had substandard insulation. Weatherstripping was also missing or substandard. Recommend installing weatherstripping and insulation per current standards at hatches or doors for better energy efficiency and to prevent dust or odor-laden air from the crawl space entering living spaces.
 
Roof Return to table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions performed adequately or were leak-free.
Roof inspection method: Traversed
Condition of roof surface material: Appeared serviceable
Roof surface material: Asphalt or fiberglass composition shingles
Roof type: Gable
 
Attic and Roof Structure Return to table of contents
Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.
Attic inspection method: Viewed from hatch(es)
Condition of roof structure: Appeared serviceable
Roof structure type: Rafters
Ceiling structure: Ceiling joists
Roof ventilation type: Box vents (roof jacks), Gable end vents
15) The ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.
16) One or more attic access hatches or doors were not insulated, or had substandard insulation. Recommend installing insulation as necessary and per current standards at hatches or doors for better energy efficiency. For more information, visit:
http://www.reporthost.com/?ATTACC
 
Garage or Carport Return to table of contents
Limitations: The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.
Type: Attached
Condition of door between garage and house: Appeared serviceable
Type of door between garage and house: Metal
Condition of garage vehicle door(s): Appeared serviceable
Type of garage vehicle door: Sectional
Number of vehicle doors: 1
Condition of garage floor: Appeared serviceable
Condition of garage interior: Required repair or evaluation (see comments below)
17) One or more gaps, holes were found in the attached garage walls or ceilings. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. Recommend that a qualified person repair per standard building practices. For example, by patching openings or holes, firestopping holes or gaps with fire-resistant caulking, and/or installing fire-resistant wall covering (e.g. Type X drywall). For more information, visit:
http://www.reporthost.com/?AGFR

Photo 6  
Holes in garage ceiling not sealed as required for fire safety.
 

18) One or more gaps, holes, areas with missing or substandard surface materials were found in the attached garage walls or ceilings. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. Recommend that a qualified person repair per standard building practices. For example, by patching openings or holes, firestopping holes or gaps with fire-resistant caulking, and/or installing fire-resistant wall covering (e.g. Type X drywall). For more information, visit:
http://www.reporthost.com/?AGFR

Photo 6  
Holes in garage ceiling not sealed as required for fire safety.
 

19) The attic access hatch cover in the attached garage ceiling was missing. Current standard building practices call for wooden-framed ceilings and walls that divide the house and garage to provide limited fire-resistance rating to prevent the spread of fire from the garage to the house. This includes having an access hatch cover installed that is in good condition, with similar fire-resistance. Recommend that a qualified person replace or repair hatch cover(s) per standard building practices. For more information, visit:
http://www.reporthost.com/?AGFR
 
Electric Return to table of contents
Limitations: The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 2
Service voltage (volts): 120-240
Estimated service amperage: 60
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Stranded aluminum
Main disconnect rating (amps): 60
System ground: Concrete encased electrode
Condition of main service panel: Appeared serviceable
Location of main service panel #A: Garage
Location of main disconnect: Breaker at top of main service panel
Branch circuit wiring type: Non-metallic sheathed
Smoke alarms installed:
Carbon monoxide alarms installed: No, recommend install
20) One or more electric receptacles (outlets) at the kitchen had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:For more information, visit:
http://www.reporthost.com/?GFCI

21) Wire splices were exposed and were not contained in a covered junction box. This is a potential shock or fire hazard. Recommend that a qualified electrician repair per standard building practices. For example, by installing permanently mounted junction boxes with cover plates where needed to contain wiring splices.

Photo 49  
Wires not terminated properly.
 

22) Smoke alarms were missing from bedrooms. Additional smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom, on each level and in any attached garage. For more information, visit:
http://www.reporthost.com/?SMKALRM

23) No carbon monoxide alarms were visible. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed for new construction and/or for homes being sold. Recommend installing approved CO alarms outside of each separate sleeping area in the immediate vicinity of the bedrooms on each level and in accordance with the manufacturer's recommendations. For more information, visit:
http://www.reporthost.com/?COALRM

Oregon REQUIRED:
OAR: 837-047-0120
Carbon Monoxide Alarm Requirements
(1) Properly functioning carbon monoxide alarms shall be required when:
(a) A person conveys fee title to a one and two family dwelling or multifamily housing containing a carbon monoxide source on or after April 1, 2011; or
(b) A person transfers possession under a land sale contract of a one and two family dwelling or multifamily housing containing a carbon monoxide source on or after April 1, 2011; or
(c) A person transfers ownership of a manufactured dwelling containing a carbon monoxide source on or after April 1, 2011; or
(d) A landlord enters into a rental agreement for a dwelling unit containing a carbon monoxide source on or after July 1, 2010.

24) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Celsius. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal-clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950, may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Celsius. Connecting newer fixtures to older, 60-degree-rated wiring is a potential fire hazard. Repairs for such conditions may involve replacing the last few feet of wiring to newer fixtures with new 90-degree-rated wire, and installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware of this safety hazard, both for existing fixtures and when planning to upgrade with newer fixtures. Consult with a qualified electrician for repairs as necessary.

25) No arc fault circuit interrupter (AFCI) breakers were installed for bedroom circuits. These are relatively new devices, and reduce the risk of fire by protecting against overheated or arcing receptacles (outlets) or light fixtures. Consult with a qualified electrician about upgrading circuits to AFCI protection per standard building practices. For more information, visit:
http://www.reporthost.com/?AFCI


Since NOT REQUIRED at time of construction and installation this item should be considered optional.
 
Plumbing / Fuel Systems Return to table of contents
Limitations: The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.
Water service: Public
Location of main water shut-off: Building exterior
Condition of supply lines: Appeared serviceable
Supply pipe material: Not determined (inaccessible or obscured)
Condition of drain pipes: Appeared serviceable
Drain pipe material: Plastic
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic
Vent pipe condition: Appeared serviceable
Vent pipe material: Plastic
Condition of fuel system: Appeared serviceable
Location of main fuel shut-off valve: At gas meter
26) Room containing gas water heater does not have enough space for adequate combustion air. An alternate louver or source for combustion air is needed and added but not to todays code. Ensure air vent in garage door is not closed.
27) The water supply to some plumbing system fixtures appeared to be shut off during the inspection and these were not fully evaluated. They are excluded from the inspection.

Toilet
 
Water Heater Return to table of contents
Limitations: Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.
Condition of water heater: Required repair, replacement and/or evaluation (see comments below)
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 40
Temperature-pressure relief valve installed: Yes
Location of water heater: Garage
Hot water temperature tested: Yes
Water temperature (degrees Fahrenheit): 115
Condition of burners: Appeared serviceable
Condition of venting system: Required repair, replacement and/or evaluation (see comments below)
28) Venting for the Water Heater is done with incorrect single wall materials. Ensure all components of the venting system of unconditioned spaces are double wall..

Photo 24  
Single wall connector at water heater connection in garage.
 
 
Heating, Ventilation and Air Condition (HVAC) Return to table of contents
Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).
General heating system type(s): Forced air
General heating distribution type(s): Ducts and registers
Condition of forced air heating/(cooling) system: Appeared serviceable
Forced air heating system fuel type: Natural gas
Location of forced air furnace: Garage
Condition of furnace filters: Appeared serviceable
Location for forced air filter(s): At top of air handler
Condition of forced air ducts and registers: Appeared serviceable
 
Fireplaces, Stoves, Chimneys and Flues Return to table of contents
Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.
Condition of wood-burning fireplaces, stoves: Appeared serviceable
Wood-burning fireplace type: Masonry
Condition of chimneys and flues: Appeared serviceable
Wood-burning chimney type: Masonry
29) One or more wood-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all wood-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA
 
Kitchen Return to table of contents
Limitations: The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: Appeared serviceable
Condition of range, cooktop or oven: Appeared serviceable
Range, cooktop or oven type: Natural gas
Condition of refrigerator: Appeared serviceable
Condition of built-in microwave oven: Appeared serviceable
 
Bathrooms, Laundry and Sinks Return to table of contents
Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of flooring: Appeared serviceable
Condition of toilets: Not determined (water supply off, obscured by stored items, etc.)
Condition of bathtubs and related plumbing: Appeared serviceable
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Appeared serviceable
Bathroom ventilation type: Spot fans
Gas supply for laundry equipment present: Not determined
240 volt receptacle for laundry equipment present: Yes
30) Dryer Duct termination damper is clogged. Recommend cleaning dryer Duct.

Photo 54  
 
 
Interior, Doors and Windows Return to table of contents
Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.
Condition of exterior entry doors: Appeared serviceable
Exterior door material: Metal
Type(s) of windows: Vinyl
Condition of walls and ceilings: Appeared serviceable
Wall type or covering: Drywall
Ceiling type or covering: Drywall
 
Additional Photos Return to table of contents

31)   Rafter was damaged and laying on the ground in this area. Replace and repair.

Photo 44  
Shed attached to home at left was not constructued to code and should be repaired to prevent further damage to home. Water intrusion and mold was present.
Rafter missing at blue arrow.
 
 

Photo 1  
All circuits tested OK

Photo 2  
Kitchen

Photo 5  
Entry Door

Photo 7  
Visqueen in good condition but no floor insulation was installed.

Photo 8  

Photo 10  

Photo 11  
Holes in garage ceiling need repaired.

Photo 13  
Main Entry.

Photo 14  
Monitor tree roots for damage over time.

Photo 15  
Plumbing good condition, no leaks.

Photo 16  

Photo 17  

Photo 18  
Closet doors missing.

Photo 19  
Laundry Room

Photo 21  

Photo 22  

Photo 23  
Dishwasher

Photo 25  
Chimney penetration was not flashed properly.

Photo 26  
60 Amp Disconnect

Photo 27  
Driveway damage from old roots is a trip hazard.

Photo 28  
Protect exterior faucets or install vacuum type to prevent freeze damage.

Photo 29  
Improper water heater stand. Recommend replacement when water heater is replaced.

Photo 30  
Attic Access

Photo 31  
Fridge in excellent working order.

Photo 32  
Laundry

Photo 33  
All faucets tested no leaks.

Photo 34  
Cabinets in counters all in good condition

Photo 35  

Photo 37  
Gas meter.

Photo 40  
Cover missing

Photo 41  
Toilet valve was off at time of inspection.

Photo 42  
Switch and plug covers missing at garage. Safety hazard.

Photo 45  
Stove

Photo 46  
Missing plug cover

Photo 47  
Plugged dryer duct needs cleaned

Photo 48  
Main disconnects

Photo 50  
Water Heater

Photo 51  
Garage vehicle barrier in place

Photo 52  
Knobs Missing.

Photo 53  

Photo 55  
Fireplace was clean and free of damage or soot build up.
 

 