HOME INSPECTION REPORT
By Patrick Y Tan
NJHI # 24GI00103200

Client(s):  Mr. XYZ (Sample)
Property address:  123, ABC Street
Town, NJ 012345
Inspection date:  Sunday, September 18, 2011

This report published on Friday, July 25, 2014 11:14:00 AM EDT

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information. Concerns are shown and sorted according to these types:
Concern typeSafetyPoses a risk of injury or death
Concern typeMajor defectCorrection likely involves a significant expense
Concern typeRepair/ReplaceRecommend repairing or replacing
Concern typeRepair/MaintainRecommend repair and/or maintenance
Concern typeMinor defectCorrection only involves a minor expense
Concern typeMaintainRecommend ongoing maintenance
Concern typeEvaluateRecommend evaluation by a specialist
Concern typeMonitorRecommend monitoring in the future
Concern typeCommentFor your information
Concern typeInfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.)
Concern typeDamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Concern typeConducive conditionsConditions conducive for wood destroying insects or organisms (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Click here for a glossary of building construction terms.Contact your inspector If there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General Information
Grounds
Exterior / Foundation
Basement
Roof / Attic
Garage / Carport
Electric
Plumbing / Fuel Systems
Water Heater
Heating
Cooling / Heat Pump
Fireplaces / Stoves / Chimneys
Kitchen
Bathrooms / Laundry / Sinks
Interior Rooms / Areas


General Information
Return to table of contents

Report number: Ye20110918
Time started: 3.00 pm
Time finished: 5.30 pm
Inspector: Patrick Y Tan
Present during inspection: Client, Property owner, Realtor
Client present for discussion at end of inspection: Yes
Weather conditions: Clear
Temperature: Cool 68 F
Ground condition: Damp
Inspection fee: 330.00
Payment method: Check
Type of building: Single family
Buildings inspected: Single Family
Age of building(s): 70 +
Source for building age: Property listing
Front of building faces: Southeast
Main entrance faces: Southeast
Occupied: Yes, Furniture or stored items were present
1) Structures built prior to 1980 may contain lead-based paint and/or asbestos in various building materials such as insulation, siding, and/or floor and ceiling tiles. Both lead and asbestos are known health hazards. Evaluating for the presence of lead and/or asbestos is not included in this inspection. The client should consult with specialists as necessary, such as industrial hygienists, professional labs and/or abatement contractors for this type of evaluation. For information on lead, asbestos and other hazardous materials in homes, visit:
http://www.epa.gov
http://www.cpsc.gov
http://www.cdc.gov
2) Many wall and floor surfaces were obscured by furniture, stored items and couldn't be fully evaluated.
Photo
Photo 2-1
Photo
Photo 2-2
Photo
Photo 2-3
Photo
Photo 2-4


Grounds
Return to table of contents

Limitations: The following items are not included in this inspection: swimming pools, spas, hot tubs, water features and related equipment; playground, recreation or leisure equipment; landscape lighting; areas below exterior structures with less than three feet of vertical clearance; irrigation systems; invisible fencing; sea walls, docks and boathouses. Any comments made regarding these items are as a courtesy only. Note that the inspector does not test or determine the adequacy of drainage systems for grounds, walkways, below-grade stairs and roof downspouts. The inspector does not provide an evaluation of geological conditions and/or site stability, compliance of pool or spa fencing with municipal requirements, or determination that deck, balcony and/or stair membranes are watertight.
Site profile: Minor slope
Condition of driveway: Required repair, replacement and/or evaluation (see comments below)
Driveway material: Asphalt
Condition of sidewalks and/or patios: Appeared serviceable
Sidewalk material: Poured in place concrete
Condition of deck, patio and/or porch covers: Appeared serviceable
Deck, patio, porch cover material and type: Open
Condition of exterior stairs: Required repairs, replacement and/or evaluation (see comments below)
Exterior stair material: Masonry
3) One or more large trees on the property may be likely to fall on the building, and are a potential safety hazard. Recommend consulting with a qualified arborist to determine if tree(s) need to be removed and/or pruned.
Photo
Photo 3-1
Photo
Photo 3-2
Photo
Photo 3-3
Photo
Photo 3-4
Photo
Photo 3-5
 

4) Exterior stairs were deteriorated. A qualified person should evaluate and repair or replace as necessary.
Photo
Photo 4-1
 

5) Conducive conditions Vegetation such as trees, shrubs and/or vines was in contact with or less than one foot from the building exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the building exterior.
Photo
Photo 5-1
Photo
Photo 5-2
Photo
Photo 5-3
Photo
Photo 5-4

6) Conducive conditions Trees were in contact with or were close to the building in one or more areas. Damage may result, especially during high winds. Vegetation can also act as a conduit for wood destroying insects. Vegetation should be pruned back and/or removed as necessary to prevent damage and infestation by wood destroying insects.
Photo
Photo 6-1
 

7) Conducive conditions Firewood was stored so that it was either in contact with the building or very close to it. This is a conducive condition for wood destroying insects. Recommend storing firewood outdoors in an open area, as far away from the building as practical, to keep away insects. For more information visit:
http://www.google.com/search?q=firewood+insects
Photo
Photo 7-1
 

8) Minor cracks, settlement, heaving and/or deterioration were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
Photo
Photo 8-1
 


Exterior / Foundation
Return to table of contents

Limitations: The following items are not included in this inspection: below-grade foundation walls and footings, or those obscured by vegetation or building components; exterior building surfaces or components obscured by vegetation, stored items or debris. Any comments made regarding these items are as a courtesy only. Some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determination the adequacy of sump pumps, seismic reinforcement, nor determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing.
Condition of wall covering: Required repairs, replacement and/or evaluation (see comments below)
Apparent wall structure: Wood frame
Wall covering: Vinyl
Condition of foundation and footings: Appeared serviceable
Foundation type: Finished basement
Foundation material: Concrete block
Footing material: Not determined
Condition of floor substructure: Appeared serviceable
Pier or support post material: Wood, Masonry, Steel
Beam material: Solid wood
Floor structure: Solid wood joists
Condition of concrete slab floor(s): Appeared serviceable
Condition of the basement: Appeared serviceable
9) Based on the age of this structure, some of the exterior siding material may contain asbestos. The client should be aware of this when considering repairs to or replacement of this siding, and consult with qualified testing labs and/or abatement contractors as necessary. For more information on asbestos in the home, visit:
http://www.cpsc.gov/cpscpub/pubs/453.html
10) Conducive conditions Evidence of prior water intrusion was found in one or more sections of the basement. For example, water stains at support post bases, efflorescence on the foundation etc. Accumulated water is a conducive condition for wood destroying insects and organisms and should not be present in the basement. The client should review any disclosure statements available and ask the property owner about past accumulation of water in the basement. The basement should be monitored in the future for accumulated water, especially after heavy and/or prolonged periods of rain. If water is found to accumulate, a qualified contractor who specializes in drainage issues should evaluate and repair as necessary. Typical repairs for preventing water from accumulating in basements include:

Ideally, water should not enter basements, but if water must be controlled after it enters the basement, then typical repairs include installing a sump pump.
Photo
Photo 10-1
 

11) Some sections of siding and/or trim were loose, warped and algaed. A qualified person should evaluate and repair, replace or install siding, trim or wash as necessary.
Photo
Photo 11-1
Photo
Photo 11-2

12) Some concrete slab floor sections were obscured by furniture, stored items, flooring and couldn't be fully evaluated.
Photo
Photo 12-1
Photo
Photo 12-2
Photo
Photo 12-3
 


Basement
Return to table of contents

Insulation material underneath floor above: None visible
Pier or support post material: Bearing wall, Steel
Beam material: Solid wood
Floor structure above: Solid wood joists
13) Guardrails are loose and/or wobbly in one or more areas. This is a safety hazard. A qualified contractor should evaluate and make repairs as necessary, such as installing new fasteners or hardware, installing additional fasteners and/or installing additional railing components as necessary so they are securely attached.
Photo
Photo 13-1
 

14) One or more open ground, three-pronged grounding type receptacles were found. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and make repairs as necessary.

Grounding type receptacles were first required in residential structures during the 1960s. Based on the age of this structure and/or the absence of 2-pronged receptacles, repairs should be made by correcting wiring circuits as necessary so all receptacles are grounded as per standard building practices. Replacement of three-pronged receptacles with 2-pronged receptacles is not an acceptable solution.
Photo
Photo 14-1
 

15) Cover plate(s) are missing from one or more electric boxes, such as for receptacles, switches and/or junction boxes. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plates should be installed where missing.
Photo
Photo 15-1
 

16) InfestationDamageConducive conditions Evidences of past termite/wood destroying insects damaged to floor boards was observed near and above the washing machine. Recommend checking with the seller for any past termite/wood destroying insects treatments/or certifications/warranties etc.
Photo
Photo 16-1
 


Roof / Attic
Return to table of contents

Limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation; solar roofing components; any comments made regarding these items are as a courtesy only. Note that the inspector does not determination if rafters, trusses, joists, beams, etc. are of adequate size, spanning or spacing. The inspector does not provide an estimate of remaining roof surface life, does not determine that the roof has absolutely no leaks at the time of the inspection, and does not determine that the roof won't leak in the future. Only active leaks and evidence of past leaks observed during the inspection are reported on as part of this inspection. To absolutely determine than no leaks exist, complete access to all roof structure areas must be available during a wide variety of weather conditions, including prolonged heavy rain, high wind from varying directions, heavy accumulations of snow and/or ice, and melting snow and ice.
Condition of roof structure: Required repair, replacement and/or evaluation (see comments below)
Roof type: Gable
Age of roof surface(s): 8/9 years
Source for building age: Property owner
Roof inspection method: Viewed from ground with binoculars
Condition of gutters, downspouts and extensions: Required repair, replacement and/or evaluation (see comments below)
Gutter and downspout material: Metal
Attic inspection method: Not inspected
Roof structure type: Rafters
Ceiling structure: Ceiling beams
Ceiling insulation material: None visible
Roof ventilation: Appears serviceable
17) Conducive conditions Flashings at the base of one or more chimneys were missing. Leaks may occur as a result. A qualified contractor should evaluate and repair as necessary.
Photo
Photo 17-1
 

18) Conducive conditions Extensions such as splash blocks or drain pipes for some downspouts were mis-aligned, damaged. Water may accumulate around the building foundation as a result. A qualified person should evaluate and repair, replace or install as necessary
Photo
Photo 18-1
Photo
Photo 18-2

19) Conducive conditions Debris had accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the building exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.
Photo
Photo 19-1
Photo
Photo 19-2

20) Conducive conditions Moss was growing on the roof. As a result, shingles may lift or be damaged. Leaks may result and/or the roof surface may fail prematurely. This is a conducive condition for wood destroying insects and organisms. Efforts should be taken to kill the moss during its growing season (wet months). Typically zinc-based chemicals are used for this, and must be applied periodically. For information on various moss treatment products and their pros and cons, visit:
http://www.google.com/search?q=moss+on+roof
Photo
Photo 20-1
 

21) Many attic and roof structure sections were not evaluated due to lack of access from the following conditions: hatch closed w/ permanent fasteners.
Photo
Photo 21-1
 

22) The attic ventilation fan was not tested and is excluded from this inspection.


Garage / Carport
Return to table of contents

Type: Detached
Condition of detached garage or carport structure: Damaged by fallen trees and was Near, at or beyond service life
Condition of garage vehicle door(s): Not tested
Garage vehicle door type: Roll
Condition of garage interior: Required repair or evaluation (see comments below)
23) Garage structures and roof damaged by fallen trees, and were covered with canvas sheets. Recommend a qualified contractor/person to evaluate the damages and/or contact your lawyer regarding replacement/ or repairs where necessary.
Photo
Photo 23-1
 

24) One or more vehicle doors couldn't be fully evaluated due to lack of access from stored items blocking.
Photo
Photo 24-1
 

25) Many wall, ceiling areas were obscured by stored items, debris and couldn't be evaluated. These areas are excluded from the inspection.
Photo
Photo 25-1
Photo
Photo 25-2
Photo
Photo 25-3
Photo
Photo 25-4


Electric
Return to table of contents

Limitations: The following items are not included in this inspection: generator systems, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, does not determine if this system has an adequate capacity for the client's specific needs, nor determine if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, install or change light bulbs, nor determine the operability of every wall switch.
Electric service condition: Appeared serviceable
Primary service type: Overhead
Number of service conductors: 3
Service voltage (volts): 120/240
Service amperage (amps): 200
Primary service overload protection type: Circuit breakers
Service entrance conductor material: Aluminum
Main disconnect rating (amps): 200
System ground: Ground rod(s) in soil
Condition of main service panel: Appeared serviceable
Branch circuit wiring type: Non-metallic sheathed
Condition of branch circuit wiring: Serviceable
Solid strand aluminum branch circuit wiring present: Not determined
Condition of smoke detectors: Appeared serviceable
Smoke detectors present: Yes
Smoke detector power source: Not determined
26) The service mast was damaged and loose. A qualified electrician should evaluate and replace the mast or make repairs as necessary.
Photo
Photo 26-1
Photo
Photo 26-2

27) One or more ground fault circuit interrupter (GFCI) electric receptacles wouldn't trip at the following "wet" locations: exterior. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate and repair as necessary.
Photo
Photo 27-1
 

28) One or more electric receptacles at the kitchen and Bathrooms had no visible ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. Recommend having a qualified electrician evaluate to determine if GFCI protection exists, and if not, repair as necessary. For more information, visit:
http://www.mikeholt.com/documents/nec/pdf/GFCI_requirement_page2.pdf
Photo
Photo 28-1
Photo
Photo 28-2
Photo
Photo 28-3
Photo
Photo 28-4

29) Branch circuit wiring installed in buildings built prior to the mid 1980s is typically rated for a maximum temperature of only 60 degrees Centigrade. This includes non-metallic sheathed (Romex) wiring, and both BX and AC metal clad flexible wiring. Knob and tube wiring, typically installed in homes built prior to 1950 may be rated for even lower maximum temperatures. Newer electric fixtures including lighting and fans typically require wiring rated for 90 degrees Centigrade. Connecting older, 60 degree-rated wiring to such newer fixtures is a potential safety hazard due to the risk of fire. Repairs for such conditions often involve replacing the last few feet of wiring to newer fixtures with new 90 degree-rated wire. This often requires installing a junction box to join the old and new wiring.

It is beyond the scope of this inspection to determine if such incompatible components are installed, or to determine the extent to which they're installed. Based on the age of this building, the client should be aware that this safety hazard may be present in this building. Recommend consulting with the property owner to determine if and when newer fixtures were installed, and/or to have a qualified electrician evaluate and repair as per standard building practices.
30) All smoke detectors were not tested due to the following conditions: may be integrated with a security system.
Photo
Photo 30-1
Photo
Photo 30-2


Plumbing / Fuel Systems
Return to table of contents

Limitations: The following items are not included in this inspection: private wells and sewage disposal systems; main, side and lateral sewer lines; gray water systems; pressure boosting systems; incinerating or composting toilets; fire suppression sprinkler systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determining the existence or condition of underground or above-ground fuel tanks.
Condition of service and main line: Appeared serviceable
Location of main water meter: Basement
Location of main water shut: Basement
Water service: Public
Water pressure (psi): 50 PSI
Service pipe material: Copper
Condition of supply lines: Appeared serviceable
Supply pipe material: Copper
Condition of waste lines: Appeared serviceable
Waste pipe material: Plastic, Galvanized steel
Condition of fuel system: Appeared serviceable
Location of main fuel shut: Basement
31) Based on gas detector readings, gas appeared to be leaking at one local shut-off valves. This is a safety hazard due to the risk of explosion. A qualified contractor and/or the gas utility company should evaluate and repair immediately. (Its was replaced by PSE & G, later during the Inspection.)
Photo
Photo 31-1
 

32) Copper water supply pipes in buildings built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:

For more information visit:
http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
http://www.epa.gov/safewater/lead/index.html
33) Conducive conditions Stains were found in one or more sections of waste lines. This may indicate that past leaks have occurred. Recommend consulting with the property owner about this, and either monitoring these areas in the future for leaks or having a qualified plumber evaluate and repair as necessary.
Photo
Photo 33-1
 

34) Conducive conditions Minor corrosion was found in some water supply valves, fittings. Leaks may occur as a result. A qualified plumber should evaluate and repair as necessary.
Photo
Photo 34-1
Photo
Photo 34-2

35) Any possible evidence of abandoned underground oil tanks was not found/determined by the inspector during the inspection. The client should ask the seller to/or determine if underground oil tank(s) exist on this property, and if tank(s) have been removed or legally decommissioned.

If the tank(s) haven't been decommissioned or removed, then the client may be liable for decommission and/or cleanup of contaminated soil in the future. Recommend the following:
36) A sump pump was installed in the basement. This may indicate that water accumulates inside or below the structure. Recommend asking the property owner how often the sump pump operates and for how long at different times of the year. Also, the client should be aware that the service life of most sump pumps is between five and seven years, and that the pump may need replacing soon depending on its age and how often it operates.
Photo
Photo 36-1
 


Water Heater
Return to table of contents

Limitations: The following items are not included in this inspection: solar water heating systems; circulation systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit.
Condition of water heater: Appeared serviceable
Type: Tank
Estimated age: 3 years
Energy source: Natural gas
Capacity (in gallons): 66
Manufacturer: Kenmore
Model: Power Miser 6
Location of water heater: Basement
Water temperature (degrees Fahrenheit): warm
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable


Heating
Return to table of contents

Condition of heating system: Appeared serviceable
Location of heating system: Basement
Heating type: Forced air
Fuel type: Natural gas
Manufacturer: Tempstar (2006).
Last service date: Unknown
Model: EDM4X48JA2
Condition of burners: Appeared serviceable
Condition of venting system: Appeared serviceable
Condition of combustion air supply: Appeared serviceable
Condition of distribution system: Appeared serviceable, Required repair, replacement and/or evaluation (see comments below)
Distribution system: Ducts and registers
Condition of controls: Appeared serviceable
Condition of air filters: Appeared serviceable
Location of air filters: At base of air handler
37) Significant amounts of debris, dirt and/or dust were visible in one or more sections of supply and/or return air ducts. This can be a health hazard, especially for those with allergies or respiratory problems. The Environmental Protection Association (EPA) recommends considering having ducts professionally cleaned when "ducts are clogged with excessive amounts of dust and debris and/or particles are actually released into the home from your supply registers". At a minimum, the visible debris should be thoroughly cleaned. Recommend having a qualified contractor clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit:
http://www.epa.gov/iaq/pubs/airduct.html
Photo
Photo 37-1
Photo
Photo 37-2
Photo
Photo 37-3
Photo
Photo 37-4

38) The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified contractor should service this system and make repairs if necessary. This servicing should be performed annually in the future.
39) One or more air filters were dirty. A qualified person should replace, wash filter(s) as necessary. Filters should be checked monthly and maintained as necessary in the future.
Photo
Photo 39-1
Photo
Photo 39-2


Cooling / Heat Pump
Return to table of contents

Limitations: The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; thermostat or temperature control accuracy and timed functions; cooling components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on cooling system components, does not determine if cooling systems are appropriately sized, and does not test coolant pressure. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future.
Condition of cooling system and/or heat pump: Appeared serviceable
Location: Basement
Type: Split system
Estimated age: 5 years (2006)
Approximate tonnage: unknown
Manufacturer: Tempstar Model T4A648KA10 S/No. E064905
Condition of distribution system: Appeared serviceable
Condition of controls: Appeared serviceable
Condition of air filters: Appeared serviceable
Location of air filters: At base of air handler
40) The last service date of this system appeared to be more than one year ago, or the inspector was unable to determine the last service date. The client should ask the property owner when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified contractor should service this system and make repairs if necessary. This servicing should be performed annually in the future.
Photo
Photo 40-1
Photo
Photo 40-2


Fireplaces / Stoves / Chimneys
Return to table of contents

Limitations: The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, nor determine if prefabricated or zero clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit.
Condition of fireplaces, stoves: Appeared serviceable
Location #A: Living Room
Fireplace type: Masonry with metal liner
Stove type: Insert
Fuel type: Wood
Condition of chimneys: Appeared serviceable
Chimney type: Masonry
41) All solid fuel burning appliances (woodstoves and fireplaces, etc.) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
Photo
Photo 41-1
Photo
Photo 41-2
Photo
Photo 41-3
 


Kitchen
Return to table of contents

Limitations: The following items are not included in this inspection: free-standing or portable appliances such as dishwashers, trash compactors, refrigerators, freezers, ice makers; specialty appliances such as hot water dispensers, water filters and trash compactors; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances such as dishwashers, garbage disposals, trash compactors, ovens, broilers, etc.
Condition of counters: Appeared serviceable
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of dishwasher: Appeared serviceable, Near, at or beyond service life
Condition of range, cooktop: Appeared serviceable, Near, at or beyond service life
Range, cooktop type: Natural gas
Condition of refrigerator: Appeared serviceable, Near, at or beyond service life
Condition of built: Appeared serviceable, Near, at or beyond service life
Condition of dishwasher: Required repair, replacement and/or evaluation (see comments below)
42) The estimated useful life for most kitchen appliances is 10 to 15 years. One or more appliances (dishwasher, refrigerator, range, microwave, range hood) appeared to be near, at or beyond their service life. Recommend budgeting for replacements in the near future.
Photo
Photo 42-1
Photo
Photo 42-2
Photo
Photo 42-3
Photo
Photo 42-4

43) The dishwasher drain line was not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The client should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.

Also, no "air gap" was installed. An air gap is another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. They are required in some municipalities for new construction and when remodeling. The client should consult with a qualified contractor to determine if an air gap should be installed.
Photo
Photo 43-1
Photo
Photo 43-2


Bathrooms / Laundry / Sinks
Return to table of contents

Limitations: The following items are not included in this inspection: overflow drains for tubs and sinks; bidets, heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.
Location #A: Common Bath
Location #B: Master Bedroom
Location #C: Basement
Condition of counters: Required repair, replacement and/or evaluation (see comments below)
Condition of cabinets: Appeared serviceable
Condition of sinks and related plumbing: Appeared serviceable
Condition of toilets: Appeared serviceable
Condition of bathtubs and related plumbing: Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing: Appeared serviceable
Condition of ventilation systems: Required repair, replacement and/or evaluation (see comments below)
Condition of laundry facilities: Not Tested
Gas supply for laundry equipment present: Not determined
240 volt receptacle for laundry equipment present: Not determined
44) Counters showed moderate deterioration at location #C.
Photo
Photo 44-1
 

45) Conducive conditions The bathrooms with showers didn't have an exhaust fan installed. Moisture accumulation will occur and may damage the structure. Even if the bathroom has a window that opens, it likely does not provide adequate ventilation, especially during cold weather when the window is closed. A qualified contractor should install exhaust fans as per standard building practices where missing in bathrooms with showers.
Photo
Photo 45-1
Photo
Photo 45-2

46) The bathtub drain stopper mechanism at location #B was missing. A qualified person should repair or replace as necessary.
Photo
Photo 46-1
 

47) Conducive conditions The caulk between the tub and the floor, walls at location #A, B, C was deteriorated. A qualified person should repair as necessary.
Photo
Photo 47-1
Photo
Photo 47-2
Photo
Photo 47-3
Photo
Photo 47-4


Interior Rooms / Areas
Return to table of contents

Limitations: The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; sources of obnoxious odors; cosmetic deficiencies due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause of odors is not within the scope of this inspection.
Exterior door material: Wood, Glass
Condition of exterior entry doors: Appeared serviceable
Condition of interior doors: Appeared serviceable
Type of windows: Aluminum, Wood
Condition of windows: Appeared serviceable
Wall type or covering: Drywall
Condition of walls: Appeared serviceable
Ceiling type or covering: Drywall
Condition of ceilings: Appeared serviceable
Flooring type or covering: Carpet, Wood, Tile
Condition of flooring: Appeared serviceable
48) One or more guardrails were wobbly. This is a safety hazard. Standard building practices require that they:

A qualified contractor should evaluate and repair, replace or install guardrails as necessary, and as per standard building practices.
Photo
Photo 48-1
 

49) ceiling areas in this structure had possibly installed prior to 1980. This material may contain asbestos, which is a known carcinogen and poses a health hazard. Laws were passed in the United States in 1978 prohibiting use of asbestos in residential structures, but stocks of existing materials have been known to be used for some time thereafter. The client may wish to have this ceiling material tested by a qualified lab to determine if it does contain asbestos.

In most cases, when the material is intact and in good condition, keeping it encapsulated with paint and not disturbing it may reduce or effectively eliminate the health hazard. If the client wishes to remove the material, or plans to disturb it through remodeling, they should have it tested by a qualified lab and/or consult with a qualified industrial hygienist or asbestos abatement specialist. For more information, visit:
http://www.cpsc.gov/CPSCPUB/PUBS/453.html
50) This structure was built prior to 1979 and may contain lead paint. Laws were enacted in 1978 in the US preventing the use of lead paint in residential structures. Lead is a known safety hazard, especially to children but also to adults. The paint found in and around this structure appeared to be intact and may be encapsulated by more recent layers of paint that are not lead-based. Regardless, recommend following precautions as described in the following links to Consumer Products Safety Commission website articles regarding possible lead paint:
http://www.cpsc.gov/CPSCPUB/PUBS/5054.html
http://www.cpsc.gov/CPSCPUB/PUBS/5055.html
51) One or more exterior doors were difficult to open or close. A qualified person should evaluate and repair as necessary.
Photo
Photo 51-1
 

52) Some windows were damaged. A qualified person should evaluate and repair or replace as necessary.
Photo
Photo 52-1
Photo
Photo 52-2

53) Screens in some windows were missing or falling apart.
Photo
Photo 53-1
 

54) Thresholds at one or more exterior doors are deteriorated. A qualified person should repair, replace or install as necessary.
Photo
Photo 54-1
 

55) Glass in one or more storm doors was broken. A qualified contractor should replace glass where necessary.
Photo
Photo 55-1
 

56) Some interior door hardware, including locksets, hinges were loose.Some Cabinets' folding doors were wobby. A qualified person should repair or replace as necessary.
Photo
Photo 56-1
Photo
Photo 56-2
Photo
Photo 56-3
Photo
Photo 56-4
Photo
Photo 56-5
 

57) Wood flooring in some areas was significantly worn, deteriorated or damaged. A qualified contractor should refinish wood flooring as necessary.
Photo
Photo 57-1
 

58) Minor paint damages and deterioration were found in ceilings in one or more areas. They do not appear to be a structural concern, but the client may wish to repair these for aesthetic reasons.
Photo
Photo 58-1
Photo
Photo 58-2


End of Report. Any enquiry or explanation needed please contact me.