Property Inspection Report
Client(s): Bill Corbitt
Property address: 3329 Hidden Brook Circle Trussville AL. 35173
Inspection date: 8/20/2011
This report published on Saturday, August 20, 2011 6:27:20 PM CDT

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 
How to Read this Report
This report is organized by the property's functional areas.  Within each functional area, descriptive information is listed first and is shown in bold type.  Items of concern follow descriptive information.
Concerns are shown and sorted according to these types:
SafetyPoses a risk of injury or death 
Major DefectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor DefectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 

Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Kitchen
Bathrooms
Interior rooms
 
General information Return to table of contents
Report number: 2
Inspector's name: Daniel Hollis
Structures inspected: Main House
Type of building: Single family
Age of building: 13 Years
Property owner's name: David Hill
Time started: 9:00 am
Time finished: 12: pm
Inspection Fee: 300.00
Payment method: Cash
Present during inspection: Client(s)
Occupied: No, but furnishings and stored items are present
Weather conditions: Clear
Temperature: Hot
Ground condition: Dry
Front of structure faces: West
Main entrance faces: West
Foundation type: Slab on grade
The following items are excluded from this inspection: Private sewage disposal system, Security system, Water softener system
 
Exterior Return to table of contents
Footing material: Poured in place concrete
Foundation material: Poured in place concrete
Apparent wall structure: Wood frame
Wall covering: Brick veneer
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core wood
1) One or more light fixtures are loose or installed in a substandard way. A qualified contractor or electrician should evaluate and make repairs as necessary so light fixtures are securely mounted and installed in accordance with the manufacturer's installation instructions.

Photo 37  
 

2) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit:
http://edis.ifas.ufl.edu/AE113

Photo 49  
 

3) Fences and/or gates are damaged and/or deteriorated in some areas. A qualified contractor should evaluate and make repairs or replace sections as necessary.

Photo 46  
 

4) Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structure's exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structure's exterior.

Photo 26  

Photo 27  

Photo 28  

Photo 40  

Photo 41  

Photo 43  

5) Minor cracks were found in one or more sidewalk or patio sections. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.
 
Roof Return to table of contents
Roof inspection method: Traversed
Roof type: Gable
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: 1 Year
Gutter & downspout material: Galvanized steel
Roof ventilation: Adequate
6) Counterflashing is missing at the base of one or more chimneys. Leaks may occur as a result. A qualified roofing or chimney service contractor should evaluate and repair as necessary.

Photo 16  

Photo 17  

Photo 18  

Photo 21  

Photo 22  
 

7) The siding on one or more exterior walls above lower roof sections is in contact with or has less than a one inch gap between it and the roof surface below. A gap of at least one inch is recommended so water isn't wicked up into the siding from the shingles below, and also to provide room for additional layers of roofing materials when the current roof surface fails. Recommend having a qualified contractor make repairs as necessary, such as trimming siding, so at least a one inch gap exists between the siding and the roofing below where necessary.

Photo 16  

Photo 17  

Photo 18  
 

8) Two sections of roof surfaces are sloped towards each other. Debris such as leaves or needles are more likely to accumulate in this area than rest of the roof. Leaks may occur as a result. Recommend monitoring such areas for accumulated debris in the future and cleaning as necessary.

Photo 6  

Photo 11  

9) Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris such as leaves or needles are more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Trees should be pruned so they are at least 10 feet above roof, or don't overhang the roof.
 
Garage Return to table of contents

10) The auto-reverse mechanism on the vehicle door opener is inoperable or requires too much force to activate. This is a safety hazard, especially for small children. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit:
http://www.cpsc.gov/cpscpub/pubs/523.html
http://www.ohdstl.com/safety.html

Photo 163  
 

11) Much of the garage, including areas around the interior perimeter and in the center are excluded from this inspection due to lack of access from stored items.
 
Attic Return to table of contents
Inspection method: Traversed
Roof structure type: Rafters
Ceiling structure: Ceiling beams
Insulation material: Fiberglass loose fill
Insulation depth: 10"
Insulation estimated R value: 30
 
Electric service Return to table of contents
Primary service type: Underground
Primary service overload protection type: Circuit breakers
Service amperage (amps): 200
Service voltage (volts): 120/240
Location of main service switch: Inside Breaker Panel
Location of main disconnect: Breaker at top of main service panel
Service entrance conductor material: Aluminum
System ground: Ground rod(s) in soil
Main disconnect rating (amps): 200
Branch circuit wiring type: Copper
Solid strand aluminum branch circuit wiring present: Can't verify
Smoke detectors present: Yes
 
Water heater Return to table of contents
Estimated age: 6 Years
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 40
Manufacturer: Rheem
Model: 21V40-7
Water temperature (degrees Fahrenheit): 110
12) Water stains were found below the water heater. This may be a sign that the water heater is failing. A qualified plumbing contractor should evaluate and replace or repair the water heater if necessary.
 
Heating and cooling Return to table of contents
Estimated age: 13 years
Primary heating system energy source: Natural gas
Primary heat system type: Forced air
Primary A/C energy source: Electric
Primary Air conditioning type: Split system
Distribution system: Sheet metal ducts, Flexible ducts
Manufacturer: Ruud
Model: UAKA-048JAZ
Filter location: In return air duct above furnace
Last service date: Don't Know
13) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. For safety reasons, and because this system is fueled by gas or oil, this servicing should be performed annually in the future. For more information visit:
http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

Photo 41  

Photo 42  

Photo 173  

Photo 175  

Photo 176  

Photo 177  

Photo 178  
 

14) The estimated useful life for most forced air furnaces is 15 to 20 years. This furnace appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
15) The estimated useful life for air conditioning compressors is 8 to 15 years. This unit appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
16) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.
17) Air handler filter(s) are dirty and should be replaced now. They should be checked monthly in the future and replaced as necessary.
18) Air handler filter(s) should be checked monthly in the future and replaced or washed as necessary.
 
Plumbing and laundry Return to table of contents
Water pressure (psi): 80 psi
Location of main water shut-off valve: Garage by the water heater
Location of main water meter: Front yard by the walkway
Location of main fuel shut-off: South side of house by the side door.
Water service: Public
Service pipe material: Copper
Supply pipe material: Copper
Vent pipe material: Plastic
Drain pipe material: Plastic
Waste pipe material: Plastic
19) No drain is visible for the catch pan installed below a washing machine. The catch pan is installed to prevent water damage to finished interior spaces below if or when the washing machine leaks, overflows or is drained. However they typically hold only a couple of gallons and quickly overflow if a drain line is not installed. Recommend consulting with the property owner(s) to determine if one is installed and/or having a qualified contractor evaluate and install one if necessary.
 
Fireplaces, woodstoves and chimneys Return to table of contents
Fireplace type: Metal prefabricated
Chimney type: Metal
20) With a Vented gas fireplace the damper should be locked in the open position. So that the damper will not close accidentally letting gas fumes into the house.

Photo 138  

Photo 139  

21) One or more gas fireplaces and/or stoves did not respond when the controls were operated. This may be due to the pilot light being turned off, the gas supply being turned off, or any number of other reasons. As a result, these appliances were not fully evaluated. As per the Standards of Practice for both the National Association of Certified Home Inspectors (NACHI) and the American Society of Home Inspectors (ASHI) the inspector does not operate gas shut off valves or light pilot lights during inspections. Recommend consulting with the property owner(s) as to how the fireplace(s) and/or stove(s) operate, and/or having a gas appliance contractor evaluate and repair if necessary.
22) All solid fuel burning appliances (woodstoves and fireplaces, etc.) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
 
Kitchen Return to table of contents

23) The range can tip forward, and no anti-tip bracket appears to be installed. This is a safety hazard since the range may tip forward when weight is applied to the open door, such as when a small child climbs on it, or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free standing ranges since 1985. An anti-tip bracket should be installed to eliminate this safety hazard. For more information, visit:
http://www.google.com/search?q=range+anti+tip+device

Photo 83  
 

24) One or more kitchen appliances appear to be near, at, or beyond their intended service life of 10 to 15 years. Recommend budgeting for replacements as necessary.

Photo 76  

Photo 77  

Photo 83  
 
 
Bathrooms Return to table of contents

25) Mirror was detatched from wall. Needs to be repaired . Could fall off the wall and cause injury.

Photo 90  

Photo 110  

26) One or more faucet handles are loose or missing and should be repaired or replaced as necessary.

Photo 116  
 

27) Caulk is missing or deteriorated around one or more shower surrounds. It should be replaced where deteriorated and/or applied where missing to prevent water intrusion and damage to the wall structure.

Photo 93  
 

28) One or more light fixtures appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.

Photo 92  
 
 
Interior rooms Return to table of contents

29) Based on the age of this structure and the appearance of existing smoke alarms, the alarms may be older than 10 years old. According to National Fire Protection Association, aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.google.com/search?q=old+smoke+alarms

30) Seals between double-pane glass in one or more windows appear to have failed based on condensation or stains between the panes of glass. A qualified contractor should evaluate and replace glass where necessary.

The client(s) should be aware that evidence of broken seals may be more or less visible from one day to the next depending on the temperature, humidity, sunlight, etc. Windows or glass doors other than those that the inspector identified may also have failed seals and need glass replaced too.

Photo 55  

Photo 56  

Photo 57  

Photo 119  

Photo 132  
 
 

Photo 2  

Photo 3  

Photo 4  

Photo 5  

Photo 7  

Photo 8  

Photo 9  

Photo 10  

Photo 12  

Photo 13  

Photo 14  

Photo 15  

Photo 19  

Photo 20  

Photo 23  

Photo 24  

Photo 25  

Photo 29  

Photo 30  

Photo 31  

Photo 32  

Photo 33  

Photo 34  

Photo 35  

Photo 36  

Photo 38  

Photo 39  

Photo 44  

Photo 45  

Photo 47  

Photo 48  

Photo 50  

Photo 51  

Photo 52  

Photo 53  

Photo 54  

Photo 58  

Photo 59  

Photo 60  

Photo 61  

Photo 62  

Photo 63  

Photo 64  

Photo 65  

Photo 66  

Photo 67  

Photo 68  

Photo 69  

Photo 70  

Photo 71  

Photo 72  

Photo 73  

Photo 74  

Photo 75  

Photo 78  

Photo 79  

Photo 80  

Photo 81  

Photo 82  

Photo 84  

Photo 85  

Photo 86  

Photo 87  

Photo 88  

Photo 89  

Photo 91  

Photo 94  

Photo 95  

Photo 96  

Photo 97  

Photo 98  

Photo 99  

Photo 100  

Photo 101  

Photo 102  

Photo 103  

Photo 104  

Photo 105  

Photo 106  

Photo 107  

Photo 108  

Photo 109  

Photo 111  

Photo 112  

Photo 113  

Photo 114  

Photo 115  

Photo 117  

Photo 118  

Photo 120  

Photo 121  

Photo 122  

Photo 123  

Photo 124  

Photo 125  

Photo 126  

Photo 127  

Photo 128  

Photo 129  

Photo 130  

Photo 131  

Photo 133  

Photo 134  

Photo 135  

Photo 136  

Photo 137  

Photo 140  

Photo 141  

Photo 142  

Photo 143  

Photo 144  

Photo 145  

Photo 146  

Photo 147  

Photo 148  

Photo 149  

Photo 150  

Photo 151  

Photo 152  

Photo 153  

Photo 154  

Photo 155  

Photo 156  

Photo 157  

Photo 158  

Photo 159  

Photo 160  

Photo 161  

Photo 162  

Photo 164  

Photo 165  

Photo 166  

Photo 167  

Photo 168  

Photo 169  

Photo 170  

Photo 171  

Photo 172  

Photo 174  

Photo 179  

 