Website: http://www.reporthost.com/freshstart
Email: afreshstart@comcast.net
Phone: (720) 480-3222
6549 W. Portland Ave. 
Littleton, CO 80128
Inspector: Gregg Stanley

  

Home Pre-Purchase Inspection Report
Client(s): John & Cindy Peters
Property address: 1215 W. Sample Ave.
Denver, CO 81234
Inspection date: Friday, December 30, 2006
This report published on 12/30/2006 1:13:55 AM MST

View summary page

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.


How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and shown in bold type. Items of concern follow descriptive information and are shown as follows:
SafetyPossibly poses a risk of injury or death 
Major defectCorrection likely involves a significant expense 
Repair/ReplaceRecommend repairing or replacing 
Repair/MaintainRecommend repair and/or maintenance 
Minor defectCorrection likely involves only a minor expense 
MaintainRecommend ongoing maintenance 
EvaluateRecommend evaluation by a specialist 
MonitorRecommend monitoring in the future 
CommentFor your information 
Concern items are sorted by the types listed above.  Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp

Structural Pest Inspection Concerns
Items marked with the following icons relate to the structural pest inspection
InfestationEvidence of infestation of wood destroying insects or organisms (Live or dead insect bodies, fungal growth, etc.)
DamageDamage caused by wood destroying insects or organisms (Rot, carpenter ant galleries, etc.)
Conducive
conditions
Conducive conditions for wood destroying insects or organisms. (Wood-soil contact, shrubs in contact with siding, roof or plumbing leaks, etc.)

Table of Contents
General information
Exterior
Roof
Garage
Attic
Electric service
Water heater
Heating and cooling
Plumbing and laundry
Fireplaces, woodstoves and chimneys
Kitchen/Dining Room
Lower Level Bathroom
Master Bathroom
"Emma's" Bedroom
Downstairs Bedroom
Downstairs Den
Master Bedroom
Upstairs Livingroom


General information Return to table of contents  
Report number: SAMPLE
Structures inspected: HOUSE & ATTACHED GARAGE
Type of building: Single family
Age of building: x25 Yrs
Time started: 1033
Time finished: 1400
Inspection Fee: $125.00
Payment method: Check
Present during inspection: Realtor gave access, client stopped by periodically.
Occupied: No, but some furnishings and stored items are present in garage.
Weather conditions: Clear
Temperature: Cold, x 25'
Ground condition: Damp, Frozen
Front of structure faces: South
Main entrance faces: South
Foundation type: Slab on grade
  1) This property has one or more fuel burning appliances, and two carbon monoxide alarms are visible; one above the furnace/water heater room entrance, and the other on the attic access panel between the upstairs bedrooms. The one in the basement is battery operated and tests correctly. The one in the upsatiars hallway has no batteries. This is a safety hazard. Recommend installing batteries in current alarm or install a new carbon monoxide alarm as necessary and as per the manufacturer's instructions. For more information, visit http://www.cpsc.gov/CPSCPUB/PREREL/prhtml05/05017.html

Photo 70  
ATTIC ACCESS

Photo 98  
BASEMENT HALL
  2) Some wall, floor and/or ceiling surfaces were obscured by furniture and/or stored items. Some areas couldn't be evaluated.

Photo 37  
W WALL OF GARAGE
 
 
Exterior Return to table of contents  
Footing material: Not visable.
Foundation material: Poured in place concrete
Apparent wall structure: Wood frame
Wall covering: Composition wood clapboard
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core steel
  3) One or more large trees on the property may be likely to fall on the structure, and are a potential safety hazard. Recommend consulting with a qualified arborist to determine if tree(s) need to be removed and/or pruned.

Photo 102  

Photo 103  
  4) The rear set of stairs are wobbly. A qualified contractor should evaluate and repair as necessary, such as installing additional supports and/or diagonal bracing.
  5) Bottom step on rear stairs missing one cross brace. This should be replaced immediately as it presents a fall hazard.

Photo 27  
REAR STAIRS ON PORCH
 
  6) One or more wall-mounted exterior light fixtures have wiring that's subject to water intrusion due to caulk not being installed around the light fixture's back plate. Caulk should be applied around the perimeter of back plates where missing. A gap should be left at the bottom for condensation to drain out.

Photo 30  
REAR PORCH LIGHT
 
  7) One or more outside faucets are missing backflow prevention devices. These devices reduce the likelihood of polluted or contaminated water entering the potable water supply. This condition can occur when an outside faucet is left in the "on" position with a hose connected and the sprayer head turned off. When pressure in the system fluctuates, water can be drawn back into the water supply pipes from the house. If a chemical sprayer is being used with the hose, those chemicals can enter the water supply pipes.

Recommend installing backflow prevention devices on all exterior hose bibs where missing. They are available at most home improvement stores and are easily installed. For more information, visit: http://edis.ifas.ufl.edu/BODY_AE079
  8) Although the rear deck was covered with snow, the inspector did notice several loose planks. It is recomended that the client look closely at the deck planks after the snow has melted to determine if there is a need for maitenance or repair.

Photo 26  
SLAT ON REAR PORCH
 
  9) Fences and/or gates are damaged and/or deteriorated in some areas. A qualified contractor should evaluate and make repairs or replace sections as necessary.

Photo 1  
FENCE NEXT TO W SIDE OF GARAGE

Photo 2  
FENCE ALONG W SIDE OF BACKYARD

Photo 3  
FENCE AT REAR OF BACKYARD, NW CORNER

Photo 4  
FENCE AT REAR OF BACKYARD, NE CORNER

Photo 5  
GATE ALONG E SIDE OF HOUSE IN BACKYARD
 
  10) Fascia boards are damaged or deteriorated in one or more areas. A qualified contractor should evaluate and make repairs as necessary.

Photo 7  
OLD SATELLITE DISH MOUNTING LOCATION ON SW CORNER OF TOP FLOOR ROOF/WALL

Photo 8  
WOOD TRIM ON TOP FLOOR AT ROOF, SW CORNER

Photo 29  
GUTTER/FACIA ABOVE PATIO DOOR
 
11) Soffits at one or more cantilever or overhang sections are unvented. This can result in moisture accumulation in floor cavities and rot. A qualified contractor should install screened vents in soffits where missing and as per standard building practices.
  12) One or more large trees are very close the foundation. Tree roots can cause significant structural damage to foundations. Recommend having a qualified tree service contractor or arborist remove trees as necessary to prevent damage to the structure's foundation.

Photo 102  
 
  13) Gaps exist at one or more openings around the exterior, such as those where outside faucets, refrigerant lines, and/or gas supply pipes penetrate the exterior. Gaps should be sealed as necessary to prevent moisture intrusion and entry by vermin.

Photo 9  
SOFFIT ON TOP FLOOR ABOVE FRONT DOOR

Photo 12  
FRONT WATER FAUCET

Photo 20  
REAR FAUCET

Photo 32  
SOFFIT UNDER REAR ROOF
  14) One or more outside faucets aren't anchored securely to the structure's exterior. Fasteners should be installed or replaced as necessary so faucets are securely anchored to prevent stress on plumbing supply lines and possible leaks.

Photo 12  
FRONT WATER FAUCET

Photo 20  
REAR FAUCET
15) This property is clad with composition wood fiber siding. Many brands of this type of siding by different manufacturers are known to deteriorate and/or fail prematurely due to moisture penetration. Failure is typically visible in the form of swelling, cracking and delamination, especially at the bottom edges. Class action lawsuits have been filed or are being filed against most manufacturers of this material.

Some areas of siding on this structure show the symptoms described above, but it appears that the siding hasn't deteriorated to the point of needing replacement, some repairs have been performed Some manufacturers (Louisiana Pacific) recommend a repair process for this siding where affected areas are sealed with "Permanizer Plus", a flexible primer made by Pittsburgh Paint, followed by two coats of 100% acrylic latex paint. This sealant must be applied to the bottom edges using a brush. The face of the siding can be sprayed. The "Permanizer Plus" sealer isn't required for edges that aren't swollen, cracked or deteriorated, but the acrylic latex should still be brushed on these edges.

At a minimum, recommend having a qualified contractor seal and repaint as described above, or by other methods specified by the siding's manufacturer. The client(s) may wish to have a qualified contractor evaluate further to determine if some or all of the siding should be replaced.

For more information, visit:
Pittsburgh Paints, PRIMERS -THE FOUNDATION FOR A TOP QUALITY JOB
Failing LP Siding Help Page

Photo 16  

Photo 17  
TRIM ALONG TOP FLOOR, FRONT OF HOUSE

Photo 18  
SIDING ON FRONT OF HOUSE, TOP FLOOR

Photo 23  
E EDGE OF CHIMNEY UNDER REAR PORCH

Photo 105  
 
16) Caulk is missing or deteriorated in some areas and should be replaced and/or applied where necessary. For more information on caulking, visit The Ins and Outs of Caulking.

Photo 15  
MASTER BEDROOM WINDOW

Photo 16  

Photo 17  
TRIM ALONG TOP FLOOR, FRONT OF HOUSE

Photo 18  
SIDING ON FRONT OF HOUSE, TOP FLOOR

Photo 19  
SE CORNER OF FLOOR OVERHANG, TOP FLOOR

Photo 20  
REAR FAUCET

Photo 23  
E EDGE OF CHIMNEY UNDER REAR PORCH

Photo 24  
E ROOF EDGE OF CHIMNEY UNDER REAR PORCH

Photo 25  
E EDGE OF CHIMNEY UNDER REAR PORCH

Photo 29  
GUTTER/FACIA ABOVE PATIO DOOR

Photo 30  
REAR PORCH LIGHT

Photo 31  
EAST SIDE OF CHIMNEY

Photo 32  
SOFFIT UNDER REAR ROOF

Photo 36  

Photo 104  

Photo 105  
17) The exterior finish in some areas is failing. A qualified contractor should prep (pressure wash, scrape, sand, prime caulk, etc.) and repaint or restain areas as needed and as per standard building practices.

Photo 34  
W SIDE OF CHIMNEY

Photo 35  
E SIDE OF CHIMNEY
  18) Minor cracks were found in the driveway. However they don't appear to be a structural concern and no trip hazards were found. No immediate action is recommended, but the client(s) may wish to have repairs made or have cracked sections replaced for aesthetic reasons.

Photo 99  
DRIVEWAY
 
  19) Sidewalks were covered with snow, unable to determine their condition.
  20) Several gutters were full of snow, preventing a thourough inspection. However, the gutters that were not full of snow appear to be in servicable condition with proper slope towards drain pipes.
    21) The header joist on the rear porch has pulled slightly away from the support. This can be easily repaired by reseating the nails, or addeding deck screws to tighten the board before it gets worse.

Photo 33  
W EDGE OF REAR PORCH
 
    22) The front porch has moved slightly from its original postion over the years. Although this doesn't appear to be of a sturctural concearn, it should be patched to prevent insect, water, and rodent intrusion.

Photo 13  
WEST EDGE OF FRONT PORCH
 
 
Roof Return to table of contents  
Roof inspection method: Viewed from eaves on ladder
Roof type: Gable
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: 5-10 Yrs.?
Gutter & downspout material: Aluminum
Roof ventilation: Adequate
23) The siding on one or more exterior walls above lower roof sections is in contact with or has less than a one inch gap between it and the roof surface below. A gap of at least one inch is recommended so water isn't wicked up into the siding from the shingles below, and also to provide room for additional layers of roofing materials when the current roof surface fails. Recommend having a qualified contractor make repairs as necessary, such as trimming siding, so at least a one inch gap exists between the siding and the roofing below where necessary.

Photo 6  
SHINGLES BELOW SMALL DECORATIVE WINDOW ON FRONT OF HOUSE ABOVE FRONT DOOR
 
24) Debris has accumulated in one or more gutters. This is a conducive condition for wood destroying insects since gutters may overflow and cause water to come in contact with the structure's exterior or make water accumulate around the foundation. Gutters should be cleaned now and as necessary in the future.

Photo 10  
GUTTER ABOVE GARAGE/FRONT DOOR

Photo 14  
SE CORNER OF TOP FLOOR ROOF
  25) The roof was completely obscured by snow and couldn't be fully evaluated.
    26) One downspout terminates onto the roof top. This can cause premature wear on the composite shingles. A downspout extension should be added so that the downspout drains into the gutter below it.

Photo 28  
ROOF ABOVE REAR OF GARAGE
 
 
Garage Return to table of contents  
  27) The vehicle door isn't balanced. The door won't stay in place when it's partially opened and falls to the ground instead. This is a safety hazard since the door may fall when open. A qualified contractor should evaluate and make repairs as necessary. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
  28) The auto-reverse mechanism on the vehicle door opener is inoperable or requires too much force to activate. This is a safety hazard, especially for small children. A qualified contractor should evaluate and repair as necessary. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
  29) One or more garage electric receptacles appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all garage receptacles, except for one for use with a refrigerator or freezer, have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.
  30) Weatherstrip around or at the bottom of the garage-house door is damaged or deteriorated. It should be replaced as necessary to prevent vehicle fumes from entering living spaces.

Photo 38  
GARAGE TO HOUSE DOOR, (L SIDE OF DOOR IS AT BOTTOM OF PICTURE.)
 
  31) No infared "photo eye" devices are installed for the vehicle door's electric door opener. They've been required on all vehicle door openers since 1993 and improve safety by triggering the vehicle door's auto-reverse feature without need for the door to come in contact with the object, person or animal that's preventing it from closing. Recommend considering having a qualified contractor install these devices for improved safety. For more information on garage door safety issues, visit: http://www.cpsc.gov/cpscpub/pubs/523.html or http://www.ohdstl.com/safety.html
  32) The exterior entrance door has window highlight inserts installed rather than a solid core door. This may represent a security hazard since these doors are easily broken. Windowed exterior entrance doors should be replaced with solid core doors by a qualified contractor.
  33) Weatherstrip at the sides of the vehicle door is missing. It should be installed where missing to prevent water and vermin intrusion.
  34) The interior perimeter of the garage is excluded from this inspection due to lack of access from stored items.

Photo 37  
W WALL OF GARAGE
 
 
Attic Return to table of contents  
Inspection method: Viewed from hatch, Partially traversed
Roof structure type: Rafters
Ceiling structure: Trusses
Insulation material: Fiberglass loose fill
Insulation depth: x 8"
Insulation estimated R value: unknown
  35) No weatherstrip is installed around the attic access hatch. Weatherstrip should be installed around the hatch to prevent heated interior air from entering attic.
    36) Flashing on one of the sheet metal vents in the attic needs to be re-attatched to the roof.

Photo 74  
VENT PIPE IN ATTIC

Photo 75  
VENT PIPE IN ATTIC
 
Electric service Return to table of contents  
Primary service type: Underground
Primary service overload protection type: Circuit breakers
Service amperage (amps): 125
Service voltage (volts): 120/240
Location of main service switch: Back of house.
Location of main disconnect: Breaker at top of main service panel
Service entrance conductor material: Aluminum
System ground: Rebar
Main disconnect rating (amps): 100
Branch circuit wiring type: Copper, Aluminum multi-strand
Solid strand aluminum branch circuit wiring present: Can't verify
Smoke detectors present: Yes
  37) The electric service to this property appears to be rated at substantially less than 200 amps, and may be inadequate for the client(s) needs. Recommend consulting with a qualified electrician about upgrading to a 200 amp service.
  38) The legend for overcurrent protection devices (breakers or fuses) in the main service panel is missing, unreadable or incomplete. Recommend installing, updating or correcting the legend as necessary so it's accurate. Evaluation by a qualified electrician may be necessary.

Photo 22  
FUSE PANEL
 
    39) Grounding for meter appears to be grounded to rebar inbedded in foundation.

Photo 21  
FOUNDATION BELOW ELECTRIC METER
 
 
Water heater Return to table of contents  
Estimated age: 1996
Type: Tank
Energy source: Natural gas
Capacity (in gallons): 40
Manufacturer: Kenmore
Model: Economizer 6
Water temperature (degrees Fahrenheit): 97'
  40) The water heater flame is yellow rather than blue. This may be caused by scale on top of the burner, a dirty burner orifice, the flue being clogged, and/or improper gas pressure. A qualified contractor should evaluate and repair as necessary.
  41) The drain line to the water heater's temperature-pressure relief valve terminates less than 6 inches from the floor. This is a potential safety hazard due to the risk of explosion. A drain line that terminates less than 6 inches from the floor can result in the water heater exploding if or when the valve opens due to restricted venting. The drain line should be modified, and by a qualified contractor if necessary, so it terminates 6" from the floor.
  42) The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be approaching this age and may need replacing in the near future. Recommend budgeting for a replacement in the near future.
    43) The doors that close off the water heater and furnace come off of the track. It appears that the Track head is comming loose from the frame. The track footing guide is not installed, keeping the doors from staying in alignment.

Photo 97  
BASEMENT HEATER & FURNACE CLOSET
 
 
Heating and cooling Return to table of contents  
Estimated age: Unable to verify
Primary heating system energy source: Natural gas
Primary heat system type: Forced air
Primary A/C energy source: N/A
Primary Air conditioning type: N/A
Distribution system: Sheet metal ducts
Manufacturer: York
Model: UG080008N-1C
Filter location: At the base of the furnace
Last service date: Unknown
  44) Significant amounts of debris, dirt and/or dust are visible in one or more sections of supply and/or return air ducts. This can be a health hazard, especially for those with allergies or respiratory problems. The Environmental Protection Association (EPA) recommends considering having ducts professionally cleaned when "ducts are clogged with excessive amounts of dust and debris and/or particles are actually released into the home from your supply registers". At a minimum, the visible debris should be thoroughly cleaned. Recommend having a qualified contractor clean the ducts. For more information on duct cleaning in relation to indoor air quality, visit: http://www.epa.gov/iaq/pubs/airduct.html

Photo 58  
DUCT IN LIVING ROOM, (PICTURE IS ACTUALLY UPSIDE DOWN)

Photo 59  
DUCT IN LIVING ROOM, (PICTURE IS ACTUALLY UPSIDE DOWN)
  45) The estimated useful life for most forced air furnaces is 15 to 20 years. This furnace appears to be approaching this age and may need replacing at any time. Recommend budgeting for a replacement in the near future.
  46) One or more rooms' interior doors have no gap below, or have a gap less than 3/4". As a result, return air flow out of the room is restricted with closed door(s) and the heating/cooling system on. This may result in the heating and/or cooling system having a reduced efficiency and higher energy costs. To allow adequate return air flow, recommend either trimming the bases of doors as necessary to maintain a 3/4" gap below, or leaving doors open while the heating or cooling system is in operation.
  47) The last service date of this system appears to be more than one year ago, or the inspector was unable to determine the last service date. The client(s) should ask the property owner(s) when it was last serviced. If unable to determine the last service date, or if this system was serviced more than one year ago, a qualified heating and cooling contractor should inspect, clean, and service this system, and make repairs if necessary. This servicing should be performed annually in the future.
 
Plumbing and laundry Return to table of contents  
Water pressure (psi): 90
Location of main water shut-off valve: Under front stairs in basement
Location of main water meter: Unkown
Location of main fuel shut-off: SE corner of house
Visible fuel storage systems: None visable
Water service: Public
Service pipe material: Copper
Supply pipe material: Copper
Vent pipe material: Plastic
Drain pipe material: Plastic
Waste pipe material: Cast iron
  48) Copper water supply pipes in homes built prior to 1986 may be joined with solder that contains lead. Lead is a known health hazard, especially for children. Laws were passed in 1985 prohibiting the use of lead in solder, but prior to that solder normally contained about 50 percent lead. The client(s) should be aware of this, especially if children will be living in this structure. Evaluating for the presence of lead in this structure is not included in this inspection. The client(s) should consider having a qualified lab test for lead, and if necessary take steps to reduce or remove lead from the water supply. Various solutions such as these may be advised:

  • Flush water taps or faucets. Do not drink water that has been sitting in the plumbing lines for more than six hours.
  • Install appropriate filters at points of use.
  • Use only cold water for cooking and drinking. Hot water dissolves lead more quickly than cold water.
  • Use bottled or distilled water.
  • Treat well water to make it less corrosive.
  • Have a qualified plumbing contractor replace supply pipes and/or plumbing components as necessary.

    For more information visit:
    http://www.cpsc.gov/CPSCPUB/PUBS/5056.html
    http://www.epa.gov/safewater/lead/index.html
  •   49) The water supply pressure is greater than 80 psi. Pressures above 80 psi may void warranties for some appliances such as water heaters or washing machines. Flexible supply lines to washing machines are more likely to burst with higher pressures. Typically the pressure cannot be regulated at the water meter. Recommend having a qualified plumber evaluate and make modifications to reduce the pressure below 80 psi. Installing a pressure reducing valve on the main service pipe is a common solution to this problem. If one exists, then it should be adjusted for lower pressures.
      50) There is a very large plastic bin filled with water sitting where the washing machine would normally sit. Unaware of its purpose. The drain for the washer also appears to have been cut flush with the wall .

    Photo 90  
    LAUNDRY ROOM
     
      51) The inspector was not able to find the water meter. Recommend that the client(s) attempt to find the water meter by consulting with the property owner(s), searching for it themselves, or consulting with the local water municipality. It is especially important to find the meter if no main shut-off valve is found because the meter may be the only way to turn off the water supply in the event of an emergency, such as when a supply pipe bursts.
        52) Turning on the rear outside faucet produced a momentary surge of brown water, then ran clear. The water in the house also has a sulfur smell to it. This may be because the house may have been vacant for a while. Recommened operating ALL faucets for about 5-10 minutes to flush out the system, as well as draining and flushing the water heater as well. This will removing any stagnant water that may have been sitting for some time.
        53) Vinyl flooring in the laundry room shows evidence of past water damage. The dryer vent has been stuffed with paper towels that will need to be removed before use.

    Photo 89  
    LAUNDRY ROOM

    Photo 91  
    LAUNDRY ROOM
     
    Fireplaces, woodstoves and chimneys Return to table of contents  
    Fireplace type: Metal prefabricated
    Chimney type: Metal
      54) A significant amount of creosote (1/8 inch or more) is visible in the fireplace flue. A qualified chimney service contractor should inspect, clean, and repair if necessary now and annually in the future.

    Photo 83  
    FIREPLACE DAMPER
     
      55) Significant amounts of ashes, wood and/or debris are in the fireplace. The inspector was unable to fully evaluate it.
      56) All solid fuel burning appliances (woodstoves and fireplaces, etc.) should be inspected annually by a qualified chimney service contractor, cleaned and repaired as necessary.
        57) The left fireplace door hits the caution label on the inside of the fireplace. Recommend repairing to avoid further damage.

    Photo 84  
    L FIREPLACE DOOR
     
     
    Kitchen/Dining Room Return to table of contents  
      58) One or more electric receptacles that serve countertop surfaces within six feet of a sink appear to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that all receptacles that serve countertop surfaces within six feet of sinks have GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    Photo 54  
    KITCHEN SINK
     
      59) The dishwasher drain line is not configured with a "high loop" or "air gap". A high loop is created by routing the drain line up to the bottom surface of the counter top above, and securely fastening it to that surface. It is meant to prevent water from siphoning out of the dishwasher, and to prevent water from the sink drain or food disposal from entering the dishwasher. Some dishwashers have a built-in high loop where one is not required to be configured in the drain line. The clients should try to determine if a high loop is required for this brand and model of dishwasher (review installation instructions, etc.). If one is required, or it cannot be determined if one is not required, then a qualified contractor should install a high loop as per standard building practices.

    Also, no "air gap" is installed. Air gaps are another device meant to prevent water from the sink drain or food disposal from entering the dishwasher. These are required in some municipalities for new construction and when remodeling. The client(s) should consult with a qualified contractor to determine if an air gap should be installed.
      60) The dishwasher's door seal is damaged, deteriorated, misaligned or otherwise does not seal well. A qualified appliance technician should evaluate and repair as necessary.

    Photo 53  
    DISHWASHER
     
      61) Drawers are difficult to open and close in one or more cabinets. A qualified contractor should evaluate and repair as necessary.

    Photo 42  
    DRAWER BETWEEN REFRIGERATOR AND STOVE
     
      62) Refrigerator and freezer were turned down to thier lowest settings. Unable to check effective operating tempature of either.
      63) The range hood fan vents into the kitchen rather than outdoors. Ventilation may be inadequate and moisture may accumulate indoors. Recommend having a qualified contractor make modifications as necessary as per standard building practices so the range hood fan vents outdoors.
    64) Caulk is missing and/or deteriorated where countertops meet backsplashes in wet areas, such as around sinks. Caulk should be replaced where deteriorated and/or applied where missing to prevent water damage.

    Photo 55  
    BACK-SPLASH BETWEEN KITCHEN SINK AND STOVE
     
      65) Light fixture above sink appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repair or replacement of the light fixture by a qualified electrician may be necessary.
      66) The dishwasher appears to be near, at, or beyond its intended service life of 10 to 15 years. Recommend budgeting for replacements as necessary.
      67) The refrigerator ice maker is in the "off" position. The inspector was unable to evaluate this component.
      68) Water stains and/or evidence of past water damage was found in the shelving or cabinet components below the sink. The client(s) should evaluate and consider having repairs made.

    Photo 40  
    UNDER KITCHEN SINK
     
        69) Cover ring around drain pipe under sink is broken and sould be repaired/replaced as necessary.

    Photo 39  
    UNDER KITCHEN SINK
     
        70) Side wall in cabinet under counter between the sink and the stove has come loose and should be repaired/replaced as necessary.

    Photo 41  
    CABINET BETWEEN SINK AND STOVE
     
        71) Baseboards around the kithen and dining room are missing.

    Photo 45  
    BASEBOARD IN KITCHEN

    Photo 46  
    BASEBOARD IN KITCHEN

    Photo 47  
    BASEBOARD IN KITCHEN

    Photo 48  
    BASEBOARD IN KITCHEN

    Photo 49  
    BASEBOARD IN KITCHEN

    Photo 50  
    BASEBOARD IN DINNING ROOM BY PATIO DOOR

    Photo 51  
    BASEBOARD IN DINING ROOM CLOSET

    Photo 52  
    EDGING AT TOP OF STAIRS BY DINING ROOM CLOSET
        72) The wood flooring in the kitchen/dining room appears to have been recently replaced. However, there are two substaintial scratches on the new floor from what appears to be from replacing the kitchen appliuances back after the floor was put in.

    Photo 43  
    KITCHEN FLOOR

    Photo 44  
    KITCHEN FLOOR
     
    Lower Level Bathroom Return to table of contents  
      73) Receptacle that serves countertop surface is within six feet of a sink appears to have no ground fault circuit interrupter (GFCI) protection. This is a safety hazard due to the risk of shock. A qualified electrician should evaluate to determine if GFCI protection exists, and if not, repairs should be made so that receptacle that serves countertop surface within six feet of sink has GFCI protection. For example, install GFCI receptacles or circuit breaker(s) as needed.

    Photo 92  
    BASEMENT BATHROOM
     
    74) Caulk is missing and/or deteriorated where countertops meet backsplashes in wet areas, such as around sinks. Caulk should be replaced where deteriorated and/or applied where missing to prevent water damage.

    Photo 93  
    BASEMENT BATHROOM BACK-SPLASH
     
      75) The enamel coating on one or more sinks is damaged and/or deteriorated. For example, chipped or worn, and/or rust on some exposed steel. However, no leaks were found due to the deterioration. The client(s) should evaluate to determine if the sinks should be replaced.

    Photo 95  
    BASEMENT BATHROOM SINK
     
      76) One or more toilets have no water supply and could not be fully evaluated. The shut-off valve(s) may be turned off, or repairs may be necessary. The client(s) should ask the property owner(s) about this, and have a qualified plumber evaluate and repair if necessary.

    Photo 94  
    BASEMENT BATHROOM TOILET
     
      77) Water stains and/or evidence of past minor water damage was found in the shelving or cabinet components below the sink. The client(s) should evaluate and consider having repairs made.

    Photo 96  
    BASEMENT BATHROOM CABINET UNDER SINK
     
     
    Master Bathroom Return to table of contents  
      78) Cover plate is missing screws. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard due to the risk of fire and shock. Cover plate screws should be installed where missing.

    Photo 60  
    MASTER BATHROOM
     
    79) Tile and/or grout around one or more bathtubs is damaged or deteriorated. For example, deteriorated or missing grout, cracked, missing or loose tiles, etc. A qualified contractor should evaluate and repair tile and/or grout as necessary.

    Photo 62  
    MASTER BATHROOM BY TUB
     
      80) Toilet "runs" after being flushed, where water leaks from the tank into the bowl. Significant amounts of water can be lost through such leaks. A qualified plumber should evaluate and repair or replace components as necessary.
    81) Caulk is missing on old screw points for shower stall door frame. It should be applied where missing to prevent water intrusion and damage to the wall structure and underlying tile.

    Photo 63  
    L SIDE OF SHOWER STALL, (PICTURE IS ON ITS SIDE)

    Photo 64  
    R SIDE OF SHOWER STALL, (PICTURE IS ON ITS SIDE)
      82) One or more light fixtures appear to be inoperable. Recommend further evaluation by replacing bulb(s) and/or consulting with the property owner(s). Repairs or replacement of the light fixture(s) by a qualified electrician may be necessary.

    Photo 61  
    MASTER BATHROOM
     
      83) Water stains and/or evidence of past minor water damage was found in the shelving or cabinet components below the sink. It also appears that the plumbing is fairly new, indicating that any past leaks may have been repaired. The client(s) should moitor this area to make sure repairs were effective.

    Photo 65  
    MASTER BATHROOM CABINET

    Photo 66  
    MASTER BATHROOM SINK PLUMBING
      84) One or more light fixtures have missing bulbs and could not be fully evaluated. Bulbs may simply need to be installed, or repairs or replacement may be necessary.

    Photo 61  
    MASTER BATHROOM
     
     
    "Emma's" Bedroom Return to table of contents  
      85) The safety mechanism on one window is missing and/or damaged so that they are inoperable. Repairs should be made by a qualified contractor or service technician so that the windows safety mechanism works correctly.

    Photo 68  
    "EMMA'S ROOM" WINDOW
     
    86) Several holes were found in the outside wall, one going all the way through the wall to the outside.They do not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons and to prevent water and insect intrusion.

    Photo 67  
    "EMMA'S ROOM"
     
      87) Carpeting in one or more rooms is soiled and/or stained. Recommend having carpeting professionally cleaned as necessary.

    Photo 69  
    "EMMA'S ROOM" CARPET
     
      88) Numerous electric receptacles were not evaluated because childproof covers were installed at the time of the inspection.
     
    Downstairs Bedroom Return to table of contents  
      89) Screen is slightly bent in on the frame.

    Photo 85  
    BASEMENT BEDROOM WINDOW
     
      90) Screen(s) in one or more windows are torn or have holes in them. Screens should be replaced where necessary.
      91) There are two holes in the ceiling, either for coaxial cables or from previous ceiling hanger/hooks. There is also one in the closet. These do not appear to be of structural concearn and can be sealed fairly easily to prevnt insect intrusion into the ceiling cavities.

    Photo 86  
    BASEMENT BEDROOM CEILING

    Photo 87  
    BASEMENT BEDROOM CEILING

    Photo 88  
    BASEMENT BEDROOM CEILING
     
     
    Downstairs Den Return to table of contents  
      92) Screen(s) in one or more windows are missing. The client(s) should ask the property owner(s) about this. Screens are often removed for window cleaning and they may be stored somewhere. If not, then recommend installing screens where missing.

    Photo 81  
    BASEMENT WINDOW TO LEFT OF FIREPLACE
     
      93) There is an existing hole in the NE corner of the downstairs den wall with some cut coaxial cables inside of it. This does not appear to be a structural concern, but the client(s) may wish to repair these for aesthetic reasons.

    Photo 82  
    BASEMENT DEN, NE CORNER
     
     
    Master Bedroom Return to table of contents  
      94) Carpeting in one or more rooms is loose and poses a trip hazard. A qualified carpeting installation contractor should restretch or replace carpet as necessary.
      95) A screw in the outer sash of the window prevents the screen from sitting flush with the window frame. This should be repaired to prevent insect intrusion.

    Photo 71  
    MASTER BEDROOM
     
      96) One window that opens, comes loose on thge track, and is sometimes difficult to open, but will open. Repairs should be made as necessary, and by a qualified contractor if necessary so windows open fully, and open and close easily.

    Photo 72  
    MASTER BEDROOM
     
      97) The safety mechanism on one window is missing and/or damaged so that they are inoperable. Repairs should be made by a qualified contractor or service technician so that the windows safety mechanism works correctly.

    Photo 73  
    MASTER BEDROOM
     
      98) Carpeting in one or more rooms is soiled and/or stained. Recommend having carpeting professionally cleaned as necessary.

    Photo 76  
    CARPET IN MASTER BEDROOM
     
     
    Upstairs Livingroom Return to table of contents  
      99) Batteries in all the smoke alarms should be replaced after taking occupancy, and annually in the future. "Chirping" noises emitted from smoke alarms typically indicate that batteries need replacing. For more information, visit http://www.cpsc.gov/cpscpub/pubs/5077.html
      100) Ceiling fan in dining room wobbles slightly during operation. This may be caused by one or more of the following:

  • Loose screws
  • Loose blade(s)
  • A loose connection between the rod and the fan body
  • A loose connection between the fan body and the electric box above
  • Misaligned blades
  • Bent or warped blades
  • Unbalanced blades

    Recommend having a qualified contractor evaluate and repair as necessary. For more information, visit:

    http://www.faninfo.com/ceiling_fans_balance.html
    http://thefanshop.com/fanfaq/maintenance.htm
    http://www.lampdepot.com/service/wobble_problems.htm
  •   101) The doorbell button is loose or damaged. It should be repaired or replaced as necessary, and by a qualified contractor if necessary.

    Photo 11  
    FRONT DOORBELL
     
      102) Screen(s) in one or more windows are loose due to a raised screw on the outside of the screen at the windows edge.Screens should be repaired where necessary.

    Photo 56  
    UPSTAIRS LIVING ROOM WINDOW

    Photo 57  
    UPSTAIRS LIVING ROOM WINDOW
      103) The front door has a minor dent on the inside surface. This is strictly cosmmetic and doesn't affect the operation or safety of the door. It also is missingthe striker plate for the dead bolt, which should be repaired.

    Photo 79  
    FRONT DOOR

    Photo 80  
    FRONT DOOR
      104) Carpeting in one or more rooms is soiled and/or stained. Recommend having carpeting professionally cleaned as necessary.

    Photo 77  
    UPSTAIRS LIVING ROOM CARPET

    Photo 78  
    UPSTAIRS LIVING ROOM CARPET
     
    SUPPORT AFTER THE INSPECTION